15
4.15 SETTING THE DAILY TIMER PROGRAMMING (PRESET
MODE)
Preset mode
Period 1: Valid
Period 2: Invalid
Period 3: Invalid
Period 4: Invalid
This function is used to set one to four daily periods, whose commands will then
be executed every day. After accessing the “Preset mode” function, you can press
the key for each period to activate or deactivate an individual period, choose the
operating mode to be used, the temperature set-point for processed water, and the
start and end times of the period itself.
Preset mode
Period 1: Valid
Mode: Heat
WOT Heat: 45°C
Start timer: 00:00
End timer: 00:00
Clicking on the "Period" label will open the page with the labels relating to period
activation, the mode to be used during the period, the water delivery temperature
and the start and end times. Click on each of these to set the appropriate value
(each data item may draw up additional windows for selecting or entering the re-
quired values). Lastly, press the top right button to save the data entered.
Note:
1.
If the compatible Aermec accessory tank for this model (refer to the installa-
tion manual for more information) is not installed and correctly set, the “DHW”
function will not be available;
2.
If timer programming with the Weekly timer and other settings with Preset
mode have been entered simultaneously, the latter will take priority;
3.
Up to four time bands can be set for each day, but their start and end times
must coherent (the beginning of one period must be later than the end of the
previous period);
4.
If the unit is switched on manually, the period timer programs will not be
implemented;
5.
If the relative function is activated (paragraph "8.3 Activating/deactivating the
memory (On/off memory) p. 25"), the value of this parameter will be stored
in the memory and automatically reset after any possible voltage failure;
6.
The default value for this function is “Off”.
4.16 DELETING CURRENT ERRORS (ERROR RESET)
This function is used to reset any errors active on the system. This operation must
only be performed after having resolved the alarm condition signalled. To reset the
alarms, press on the function label and then confirm with “OK” in the dialogue box;
Note: this function can only be performed if the unit is switched off.
4.17 WIFI CONNECTION RESET FUNCTION (WIFI RESET)
This function is used to reset the WiFi connection, eliminating any conflicts.
4.18 LOADING THE DEFAULT SETTINGS (RESET)
This function is used to load the default values (values pre-set in the factory) for all
functions by resetting the changes made by the user.
Note:
1.
This function can only be performed if the unit is switched off;
2.
This function interacts with the “Temp. timer“, “Clock timer“, “Preset mode“,
“Weekly timer“ and “Weather depend” functions.