HBI. 1011. 4138500_00
1 2 3 4
unit outline
expansion bolt hole
Auxiliar y Installation hole
PRECAUTIONS FOR INSTALLATION OF THE INDOOR UNIT:
• The indoor unit must be mounted vertically on the wall of the
room with the aid of Rawplugs.
• Keep the indoor unit as far away from heat sources as pos-
sible, e.g. heat sinks and similar present in the room.
• Keep the indoor unit as near as possible to the outdoor unit.
The level distance between the connection pipes cannot
exceed 30 m (8.0~16KW), while the vertical distance cannot
exceed 15 m (8.0~16KW).
Name
Connection diameters
1 Outlet water pipe
BSP 1” male red.
2 Return water pipe
BSP 1” male red.
3 Gas side pipe
3/8"
4 Liquid side pipe
5/8"
12. SPACE REQUISITES FOR INSTALLATION OF THE INDOOR UNIT
13. INDOOR UNIT DIMENSIONS
13.1. INDOOR UNIT CLEARANCE (HBI080E - HBI100E - HBI120E - HBI140E - HBI160E):