background image

33

English

AGLL10/20NFJ 07/11_4528571_00

If the thermostat is configured for use 
without a valve (

dip1 OFF

) or with a 

probe upstream of the valve (

dip2 ON

), 

then the water temperature detected is 
that available on the terminal, there-
fore the season is forced to Hot or Cold 
according to this temperature.
The thresholds of the season changeover 

are shown in the table below. 
In this configuration, the indications of 
the left LED correspond to the active 
mode.
The ventilation is enabled only if the 
water temperature is suitable for the 
cooling mode or the heating mode. This 
allows on one side to avoid unwanted 

cold ventilation in the winter season, 
and on the other side to check the turn-
ing on and off of all terminals, accord-
ing to the actual condition of the water 
available (centralized control of the 
On-Off and Hot-Cold commands).

The normal band (hot enabled at 39° C, 
cold enabled at 17° C) or the reduced 
band (hot enabled at 35° C, cold ena-
bled at 22° C) is selected based on the 
(

dip4)

.

The season changeover of some systems 
is based on air temperature, these are:
- 2-pipe systems with the Water Probe 

downstream of the valve.

- All 2-pipe systems without water probe.
- All 4-pipe systems.
The season changeover occurs as follows:

Cold mode:

 if the ambient temperature 

detected is below the setpoint of an 
interval equal to the dead band (2° C or 
5° C) it switches to the hot mode.

- Hot  mode: 

if the ambient temperature 

detected is above the setpoint of an 
interval equal to the dead band (2° C or 
5° C) it switches to the cold mode.

 The dead band is decided through 

dip7 or rather if it has a dead band of 
5° C (dip7 OFF) while if the dead band 
is 2° C (dip7 ON).

HOT/COLD MODE CHANGE OVER 

COLD SEASON CHANGEOVER 

THRESHOLD 

HOT SEASON CHANGEOVER 

THRESHOLD 

DIP SWITCH 

MEANING

12 

°C / 

22

°C

35 

°C

 / 39 

°C

Normal band (dip 4 off)

22

°C / 

25

°C

31 

°C

 / 35

°C

Reduced band (dip 4 on)

WATER SIDE SEASON CHANGEOVER 

SEASON CHANGEOVER BASED ON THE AIR 

VENTILATION ENABLING 

ANTI-FREEZE PROTECTION

The anti-freeze protection allows you to 
check that the room temperature never 
falls to freezing values (even when the 
selector is in the OFF position). If the 
temperature drops below 7° C, the ther-
mostat still operates in HEATING mode 
with SETPOINT at 12° C and ventilation 
in AUTO, if the temperature of the water 
permits so. In case of Water Probe not 
present or continuous ventilation, the fan 

is always enabled. If the valve is present 
and the water probe is upstream or the 
water probe is absent, the pre-heating of 
the heat exchanger is still executed.
The thermostat exits the Anti-freeze 
mode when the room temperature 
exceeds 9°C.

The thermostat also includes an external 
contact that allows to set it to OFF if it 
is closed (except if the thermostat is in 
anti-freeze mode or as a slave in the TTL 
network). This contact could be useful to 
manage inputs such as window contacts, 
faulty circulation pump, etc.

CE input status

Machine status

Closed

OFF

Open

ON

EXTERNAL CONTACT LOGIC

Содержание GLL10N

Страница 1: ... A T I O N B E D I E N U N G S U N D I N S T A L L A T I O N S A N L E I T U N G MANUAL DE USO E INSTALACIÓN CORNICE DI MANDATA E D ASPIRAZIONE DELIVERY AND INTAKE FRAME GRILLE DE SOUFFLAGE ET D ASPIRATION AUSBLAS UND ANSAUGGITTER INVERTER PLAFON DE ENVÍO Y DE ASPIRACIÓN AGLL10 20NFJ 1107_4528571_00 GLL10N GLL20N ...

Страница 2: ...non mentionnée dans ce manuel contac ter aussitôt le service après vente de votre secteur Lors de l installation de l appareil il faut prévoir l espace nécessaire pour les opérations d entretien et ou de réparation La garantie de l appareil ne couvre pas les coûts dérivant de l utilisation de voitures avec échelle mécanique d échafauda ges ou d autres systèmes de levée employés pour effectuer des ...

Страница 3: ...eries to which this declaration refers complies with the following standardised regulations soddisfando così i requisiti essenziali delle seguenti direttive Direttiva Bassa Tensione LVD 2006 95 CE Direttiva Compatibilità Elettromagnetica EMC 2004 108 CE thus meeting the essential requisites of the following directives Low Voltage Directive LVD 2006 95 EC Electromagnetic Compatibility Directive EMC...

Страница 4: ...hlich mit Sorgfalt behan deln Frágil manejar con cuidado Freccia alto Arrow high flèche haut Pfeil hoch Flecha alto 25Kg Pericolo Pericolo Pericolo Tensione Organi in movimento Danger Danger Danger Power supply Movings parts Danger Danger Danger Tension Organes en mouvement Gefahr Gefahr Gefahr Spannung Rotierende Teile Peligro Peligro Peligro Tensión Elementos en movimiento SIMBOLI DI SICUREZZA S...

Страница 5: ...accessory that must be connected to the electronic cards applied to fan coils Consult the manu als of the fan coils and cards if they have been provided as an accessory and apply all safety precautions indi cated for the electronic cards WARNING the fan coil is connected to the power supply and water circuit Operations performed by unqualified personnel can lead to personal injury to the operator ...

Страница 6: ...ing Cooling The night time comfort function Sleep Supervisor controlled operating mode VMF E5 See the accessories manual for complete information on its features VMF E4 FCLI GLLI10N FCLI GLLI20N VMF E4 VMF E4 FCLI SLAVE FCLI SLAVE FCLI MASTER LUNGHEZZA MAX 30 m VMF E5 VMF E4 VMF E4 VMF E4 MASTER 1 MASTER 2 MASTER 3 FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI GLLI10N FCLI GLLI20N FCLI ...

Страница 7: ...FCLI GLLI_N RS485 TTL TTL TTL RS485 RS485 VMF E5B VMF E5N MASTER 2 FCLI GLLI_N MASTER 64 FCLI GLLI_N VMF E4 VMF E4D TTL MAX 30m VMF E4 VMF E4D RS485 MAX 1000m VMF E4 VMF E4D WARNING the VMF E5 panel allows the management of the individual masters the slave units connected to each master cannot be individually managed from the VMF E5 panel but they acquire the settings of the master to which they a...

Страница 8: ...GLLI_N card as shown 1 2 3 4 TX RX GND TTL MODE 5V 1 2 3 4 5 6 1 2 3 4 5 6 Characteristics of the cable to be used for the connection EIB Bus cable 4 poles shield Mutual max capacity 100nF km 800Hz Resistance max 130 ohm km Key A 4 pole shielded cable not supplied for connection betweenVMF E4 and GLLI_N B Shield folded on the cable for earth connection C Clamp made of plastic conductive material s...

Страница 9: ...F E4 EXTERNAL CONTACT CONNECTION ECONOMY CONTROL WINDOW CONTROL CONNECTION MODBUS RS485 SERIAL TTL NETWORK CONNECTION M26 CONTROL BOARD 1 2 3 4 5 6 1 2 3 4 5 6 TX RX CE TX RX GND TTL GND CF A B GND GND MODE 5V MODBUS RS485 CE EXTERNAL CONTACT TTL SERIAL TTL WITH VMF E4 ECONOMY CONTROL WINDOW CONTROL ...

Страница 10: ...t 5 A M13 V1 minimum speed output Voltage 230 Vac current 5 A M14 Support input not connected M26 Service control board M22 Control board for connection to the receiver CN2 SW water probe NTC 10Kohm CN1 SA air probe NTC 10Kohm CN3 SC auxiliary water probe NTC 10Kohm M15 M16 SR electric resistor tempera ture probe NTC 4Kohm 200 C M17 Out 0 10V Inverter reference Voltage 10 Vdc current 10 mA M18 GND...

Страница 11: ...robe reading display of the data read by the probes display of the alarm log start of the Autotest procedure The new display card must have a layout as shown in the following figures AUX key Blue Red LED Yellow Green LED To exit the test correction functions an ON OFF command via VMF E4 panel or a change mode command AUTO V1 V2 V3 AUX must be given to the cassette OFF AUX V3 V2 V1 AUTO AUTOTEST AU...

Страница 12: ...view other probes The number of flashes by the green LED indicates which probe is displayed see table Green LED Probe displayed 2 SW probe 3 Aux SW probe 4 SA probe 5 Resistor probe SR ALARMS LOG The receiver cyclically indicates the last 5 alarms occurred on the machine in the alarms log view mode yellow LED cyclically flashes 5 times and then remains off for 5 seconds red LED lights at the same ...

Страница 13: ...ce is the selection of the correc tion that is linked to the season of the thermostat SEASON TYPE OF PROBE CORRECTION Ambient probe temperature cold Ambient probe temperature hot Parameters cold and hot can be dif ferent from one another and can take integer values between 0 and 6 C To set the hot value for example the fan coil should be set to winter mode and in standby after pressing the AUX key...

Страница 14: ...irements V2 In this position the average ventilation speed V2 is always active regardless of thermostat requirements V3 In this position the maximum ventilation speed V3 is always active regardless of thermostat requirements Aux In this position the minimum Aux ventilation speed is always active VENTILATION CONTROL If a shut off valve is present dip1 ON the position of the probe can be man aged bo...

Страница 15: ... mode Hot mode if the ambient temperature detected is above the setpoint of an interval equal to the dead band 2 C or 5 C it switches to the cold mode The dead band is decided through dip7 or rather if it has a dead band of 5 C dip7 OFF while if the dead band is 2 C dip7 ON HOT COLD MODE CHANGE OVER COLD SEASON CHANGEOVER THRESHOLD HOT SEASON CHANGEOVER THRESHOLD DIP SWITCH MEANING 12 C 22 C 35 C ...

Страница 16: ...at the resistance to the startup of the thermostat is in the OFF state will then be activated only if the water temperature is below the threshold of qualification which is 35 C with normal bandwidth 31 C with band reduced The activation of the electrical resistan ce however provides management of ventilation as a function proportional to the error but where is the minimum gua ranteed speed V2 Thi...

Страница 17: ...e probe Position Functions Dip 1 Default OFF Check water valve Thermostat in centralised network See table OFF No shut off valve ON Shutoff valve present Thermostat in centralised network Dip 2 Default OFF Position water temperature probe Thermostat in centralised network See table OFF Water temperature probe downstream from shutoff valve Thermostat in centralised network ON Water temperature prob...

Страница 18: ... the water but on the sheer demand for the thermostat opera tion AMBIENT PROBEABSENT 2 PIPES In this case the thermostat operates as follows OFF Aux Mode The valve is closed The fan is off AUTO V1 V2 V3 mode The valve is always open Operating season always hot The ventilation runs On Off cycles The duration of the ON cycle is pro portional to the setpoint set in the VMF E4 panel The total duration...

Страница 19: ...ases according to settings different from those dictated by the master AMBIENT PROBE the ambient control probe is not needed on slave fan coils be cause these can use the control probe of the master However if you want to avoid having micro climates it can be installed on the slaves that will then adjust with the respective probe In particular cases where the ambient probe on the master is faulty ...

Страница 20: ...m the last command received from it The master will also send the OFF com mand to all the slaves The user inter face also gives the visual alarm AL 1 TTL NETWORK CONSTRAINTS The constraint concerns the management of the adjustment dead band this should be set on the master fan coil being that it is ignored on the slaves because both the setpoint and the operating season of these depend on the mast...

Страница 21: ...ing cold functioning The opening positions are indicated on the side section of the deflectors GLL10N for correct machine heating 20 opening and cooling 10 open ing operation For units with GLL20N grilles the deflec tor should be fully opened in the heat ing operation and it should be rotated halfway in the cooling operation Depending on the user s needs the fins can be adjusted to the intermediat...

Страница 22: ... possible replacement Remove the delivery frame Extract the thermostat card Open the thermostat box Replace the faulty fuses The fuses are 5 x 20 T series delayed from 2 A to 10 A WARNING for correct replacement the 2 A fuse must be inserted in loca tion F3 while the 10 A fuse must be inserted in F2 as shown in the image below Before installing the electric box the configuration of the electronic ...

Страница 23: ...el agua instalaciones de 4 tubos VHL Valvola Valve Vanne Ventil Válvula Componenti non forniti Components not supplied Composants non fournis Nicht lieferbare Teile Componentes no suministrados Componenti forniti optional Optional components Composants en option Optionsteile Componentes opcionales Collegamenti da eseguire in loco On site wiring Raccordements à effectuer in situ Vor Ort auszuführen...

Страница 24: ...rät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma FCL GLL10N GLL20N SA LED CE GND CF A B GND RS485 TX RX GND TTL BL1 5 7 MA1 5 1 M MP VHL 4 3 2 1 F 10A F 2A RL1 RL2 RL3 RL4 RL5 RL6 RL7 L N N AUX RE MA Y2 Y1 N1 V3 V2 V1 N TR1 M28 M14 M27 C1 M25 M22 CN2 CN1 CN...

Страница 25: ...ät gelieferte Schaltschema beziehen El cableado de las máquinas es sometido a actualizaciones constantes Por favor para cada unidad hagan referencia a los esquemas suministrados con la misma FCL GLL10N GLL20N CE GND CF A B GND RS485 TX RX GND TTL BL1 5 7 MA1 5 1 M MP 4 3 2 1 F 10A F 2A RL1 RL2 RL3 RL4 RL5 RL6 RL7 L N N AUX RE MA Y2 Y1 N1 V3 V2 V1 N TR1 M28 M14 M27 C1 M25 M22 CN2 CN1 CN3 L17 M21 M1...

Страница 26: ...rve le droit de modifier à tous moments les données considérées nécessaires à l amelioration du produit Technical data shown in this booklet are not binding Aermec S p A shall have the right to introduce at any time whatever modifications deemed necessary to the improvement of the product Im Sinne des technischen Fortsschrittes behält sich Aermec S p A vor in der Produktion Änderungen und Verbesse...

Отзывы: