SPL User Manual Page 18 of 24
0412-6180864-rev.00
*
INTAKE TEMP. ^
*
DELIVERY TEMP. ^
*
EXTERNAL TEMP. - DYNAMIC SET
*
ANTI-FREEZE
*
DIFF. PRESS. DEL. FAN
*
HUMIDITY LIMIT ^
*
EXTERNAL HUMIDITY ^
*
AMBIENT HUMIDITY ^
*
AIR QUALITY ^
*
HIGH PRESSURE, CIRCUIT 1
*
HIGH PRESSURE, CIRCUIT 2
*
LOW PRESSURE CIRCUIT 1
*
LOW PRESSURE CIRCUIT 2
*
COND. TEMP. CIRCUIT 1 **
*
COND. TEMP. CIRCUIT 2 **
Error description
Action
Troubleshooting
Reset type
TIMEOUT INT. EXP.
Replacement performed by AERMEC service
dept.
CRC EEPROM BIOS
ERROR
The default of the parameters are
automatically reset
Evaluate to restore parameters or replacement
by the AERMEC service Dept.
CRC EEPROM USER
ERROR
The default of the parameters are
automatically reset
Evaluate to restore parameters or replacement
by the AERMEC service Dept.
REAL TIME CLOCK NEED
TO BE SET
Set date/time, if not resolved replace by the
AERMEC service Dept.
REAL TIME CLOCK
COMM. ERROR
Set date/time, if not resolved replace by the
AERMEC service Dept.
REAL TIME CLOCK
REGISTERS
Set date/time, if not resolved replace by the
AERMEC service Dept.
11.2.3 Probe error alarms status list
11.3.1 Description and resolution of BIOS alarms