8.7. GENERAL
FUNCTIONS
CONTROL BOARD
The regulator is prepared for mana-
gement of different machine models
depending on the position of the DIP
switches present on the control.
To select the AIR-CONDITIONING mo-
del, the DIP switches must be set ac-
cording to the layout shown here. The
control and all loads must be discon-
nected from the main power supply.
8.8. TERMINALS
CONNECTION
NETWORK - CONTROLS.
8.8.1. Electric
connections
Shielded and twisted bipolar cables
must be used to connect the terminals
to the control or the controls network,
at the relative clamps indicated on the
terminal and on the control panel.
The maximum distance from the termi-
nal from the relative control is 30 m.
The power supply voltage is 24 Vdc
with data transmission on the twisted
pair connection cable with packs at a
transmission speed of 4800 bit/s and
proprietor protocol.
8.8.2. IO list: electrical data
The platform for control of the forced
air heaters envisions a base board,
developed with a layout for the maxi-
mum configuration, which will then be
mounted in the different versions to ge-
nerate different product codes depen-
ding on the requests and applications.
All parameters will be configurable and
many functions present can be acti-
vated according to requirements and
applications.
The inputs and outputs will all be con-
figurable via software in the different
functionalities for greater flexibility and
easy installation.
Below find the IO table with electric
data for every input and output. The
configuration default values relative to
the model are specified below in the
"Default configurations" chapter
ON
OFF
1 2 3 4 5 6 7 8
8.8.3. High voltage terminal board
Type #
N° Ter-
minal
Code
Description
Electric features at nominal
voltage
NOTES
X1
1
1
L
Power supply line
230 Vac +10%, -15 % at 50 Hz.
Max. absorption 8 VA (without addi-
tional loads) to confirm
Screw Terminal Board
2
2
N
Neutral power supply
Screw Terminal Board
3
3
EARTH
Service earth
Screw Terminal Board
X2
1
4
Compressor control faston
Max passage current on contact =
20A with resistive load
Potential free con-
tact on Power Relay
2
5
CK4
Compressor control faston
3
6
Common Relay Reference
4
7
Common Relay Reference
5
8
Common Relay Reference
6
9
Common Relay Reference
7
10
CK3
Fan 3 speed control
Max output current on contact =
5A with resistive load
Max total current for all digital
outputs = 10°
Potential free
contact
8
11
CK2
Fan 2 speed control
9
12
CK1
Fan 1 speed control
10
13
Line
Relay voltage
Power supply
voltage for the
loads
X7
1
24
CE+
TTL terminal serial connection
2
25
CE-
TTL terminal serial connection
X5
1
30
B1-NTC NTC1
NTC 10 k
Ω
at 25 °C, ß = 3435 (clamps
9 – 10)
2
31
B1-NTC NTC1
3
32
B2-NTC NTC2
4
33
B2-NTC NTC2