Reco-Boxx ZXR / ZXA / Flat – Operation and maintenance instructions
[03/
2022 ]
7.1.3 Basic Setup
When the air handling unit is started up for the first time,
the commissioning menu is automatically displayed. At
the very end of the commissioning (menu) the commis-
sioning of the unit has to be confirmed by the service
technician. Once the commissioning has been confirmed,
the commissioning menu will not be displayed as first
menu any more. The commissioning menu, however,
will remain accessible through the advanced setup. See
Section 7.1.4.
Language
The language desired can be set here. The language set-
ting can be changed at any time in the basic setup menu.
Setting
Settings range
Factory setting
Language
Languages as
displayed
English
Units
The desired unit can be set here. The unit setting can be
changed at any time in the basic setup menu.
Setting
Settings range
Factory setting
Unit
m³/h
l/s
m³/h
Airflow regulation
The desired control mode can be set here. The setting can
be changed at any time in the basic setup menu. De-
pending on the selected function, flows can be set as (l/s,
m /h), pressure (Pa), input signal strength (%) or torque
(%). For both “Airflow control” and “Torque control”, three
setpoints are available: Low, medium and high.
Setting
Settings range
Factory setting
Operating mode
OFF
Airflow
Demand control
Pressure
Torque
Airflow
33
Operation and maintenance instructions
BASIC SETUP
6.1.3 BASIC SETUP
When the air handling unit is started up for the first time, the
commissioning menu is automatically displayed. At the very end
of the commissioning (menu) the commissioning of the unit has
to be confirmed by the service technician. Once the commis-
sioning has been confirmed, the commissioning menu will not
be displayed as first menu any more. The commissioning menu,
however, will remain accessible through the advanced setup
. See
Section 6.1.4.
Language
The language desired can be set here. The language setting can
be changed at any time in the basic setup menu.
Setting
Settings
range
Factory
setting
Language
Languages as
displayed
English
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
Units
The desired unit can be set here. The unit setting can be changed
at any time in the basic setup menu.
Setting
Settings
range
Factory
setting
Unit
m³/h
l/s
m³/h
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
Airflow regulation
The desired control mode can be set here. The setting can be
changed at any time in the basic setup menu. Depending on
the selected function, flows can be set as (l/s, m³/h), pressure
(Pa), input signal strength (%) or torque (%). For both “Airflow
control” and “Torque control”, three setpoints are available: Low,
medium and high.
Setting
Settings
range
Factory
setting
Operating mode
OFF
Airflow
Demand control
Pressure
Torque
Airflow