background image

 

 

4/22 

 

 

 
 

 

TF5774_C 

Aereco S.A. 

 

 

GENERAL 

The VBP+ R is a very-low-pressure assistance fan delivering pressure compatible with the design of passive stack ventilation. 

It is intended to improve and optimize the draught of passive stack ventilation ducts, and belongs to the category of hybrid 
ventilation systems.  

It is available in 2 pre-configured versions:  

ST version (VB21184):

 Version pre-configured in ST mode, uncontrolled stand-alone, at constant speed adjustable on a built-

in potentiometer. 

MS version (VB21183):

 Version pre-configured in MS mode, controlled by a management system: 

 

Management of the fans in groups (up to 5 groups of 5 VBP+), 

 

Individual setting/adjustment of the speed of each fan according to the site configuration (number of storeys, 

ductwork...) 

 

Speed control of each fan according to the temperature, (item sold by Aereco), wind or by using a clock (items 

not sold by Aereco) 

 

Indication of operation of the system and alarm reporting. 

This version requires the use of two specific types of modules. 

The versions (ST and MS) are the same product with different pre-configurations. It is therefore possible to change 
from one version to the other. The possible change of configuration will imply a specific identification of the product 
(the label states the baseline configuration). 

 

MAIN FUNCTIONS 

 

Hybrid operation: in passive stack or mechanical mode (low pressure losses when stopped) 

 

Compatibility with demand-controlled ventilation  

 

Low power consumption 

 

Direct power supply at 230 V~, 50-60Hz 

 

Adjustment of the speed according to the temperature, wind or by using a clock ("MS" mode) 

 

Reporting of information for working or default 

(“MS” mode)

 

 

Possibility of grouping several ducts (in case of large aeraulic section) 

 

RANGE OF USE 

 

Ventilation of residential buildings, offices, and other general-purpose premises 

 

Renovation or new construction

1

 

 

Individual or collective ventilation ducts, which may be made of concrete or metal. 

 

Remarks: 

 

Use of the fan on ducts serving connected gas-fired appliances is subject to specific approval by the competent 

authorities. 

 

The height of the buildings equipped varies according to the regulation flow rate requirements, which are specific 

to each country. 

 

In France, the MS version of this product is sold under the name 

HELYS H800 R

 by the Acthys Company. 

 

 

 

 

1

 

In some countries, a specific permit may be required for use in new buildings

 

Содержание VB21183

Страница 1: ...EN Document not contractual Aereco can realise technical modifications on its products without prior notice Installation and maintenance VBP R Hybrid assistance ventilation fan TF5774_C ENGLISH ...

Страница 2: ...8 CASE OF DUCTS GROUPED UNDER 2 FANS 9 ANTICIPATION OF MAINTENANCE AND CHIMNEY SWEEPING CONSTRAINTS 10 INSTALLING THE FAN 10 CONNECTIONS 11 GENERAL CONNECTION DIAGRAM 11 POWER CONNECTION 15 CONFIGURING IN ST OR MS MODE 16 CONNECTION IN ST MODE 17 CONNECTION IN MS MODE 17 STARTING UP OPERATION 18 ST MODE 18 MS MODE 19 5 3 INSTALLATION CHECK UP 19 MAINTENANCE 20 PRIOR WARNINGS 20 MAINTENANCE AND CLE...

Страница 3: ...signed to be installed or used by persons whose intellectual and or mental faculties are impaired or who lack experience and knowledge including children unless they have been trained and are supervised by a person responsible for their safety during installation To eliminate any risk of an accident keep them away from the appliance The electrical installation and connection work must be done by a...

Страница 4: ... It is therefore possible to change from one version to the other The possible change of configuration will imply a specific identification of the product the label states the baseline configuration MAIN FUNCTIONS Hybrid operation in passive stack or mechanical mode low pressure losses when stopped Compatibility with demand controlled ventilation Low power consumption Direct power supply at 230 V ...

Страница 5: ... PRODUCT DATA COMPONENTS Note the MS mode also requires two specific modules a temperature probe and other electrical components These elements are described in the manual specific to this mode DIMENSIONS Dimensions in mm Fan ...

Страница 6: ...ctrical design W 42 Inrush protection IP of motor IP54 Control setting of speed By built in potentiometer By MS management system Degree of pollution 1 Characteristics Weight kg 17 Colour Metallic grey black Material envelop Galvanized steel PE Outside dimensions mm 904 x ø610 Installation Number of suction connections available 1 Inlet connection mm ø354 Installation On roof head of duct 3 x ø8mm...

Страница 7: ...op of the stack is sufficient For the grouping of ducts an adaptation plenum compliant with the recommendations stated below is necessary to ensure proper aeraulic operation of the whole minimized pressure losses and for attachment and tightness with the fan s General recommendations for the placement of adaptation components The adaptation components must be made of a material strong enough to be...

Страница 8: ...st 600 x 600 mm The opening cross section of the duct must not exceed Ø350 mm if it is desired to avoid reducing its cross section The fan must be centred on the duct CASE OF DUCTS GROUPED UNDER A SINGLE FAN For all grouped ducts configurations an adaptation plenum is necessary The plenum must provide a top platform measuring at least 600 x 600 mm provide a circular outlet Ø350 mm centred on the s...

Страница 9: ...ed on the outlets Ø350 mm Each Ø350 mm outlet must be at least 1 000 mm from the other and at least 500 mm from the bulkhead separating the volumes The plenum must provide 2 virtual platforms measuring at least 800 x 600 mm each see example below Example of grouping of 8 individual ducts LIMITS All the following cases must be avoided because they would lead to non compliance with European EMC requ...

Страница 10: ...s and catches Attachment that can be removed from and refitted on the top plate INSTALLING THE FAN 1 Ensure the proper adaptation of the fan on its stack see section above The plate holding the outlet Ø350 mm can be designed with 3 crimped M8 nuts positioned as shown below to allow the attachment of the fan 2 Remove the fan from the pallet Use only the 2 handles located under the uprights to handl...

Страница 11: ...CONNECTIONS All electrical connection operations must be made by a qualified professional and comply with the standards in force No cable used for the connection may pass though the interior of the stack or of the plenum GENERAL CONNECTION DIAGRAM The following drawings show the electrical connections according to the chosen working mode ST or MS mode Two cases can be identified Case A 230 V elect...

Страница 12: ... comply with the installation standards in force colour code in particular have conductors with a cross section of at least 1 5 mm and be able to withstand the environment in which it is installed in particular be resistant to UV Switch general isolating switch A manual circuit breaker must be located on the 230V supply upward the fan s It has to be visible and accessible from each connected fan I...

Страница 13: ...13 22 TF5774_C Aereco S A MS mode Case A 230 V electrical box is far from the fans for example in the stairs Case B 230 V electrical box is close to the fans in terrace ...

Страница 14: ...14 22 TF5774_C Aereco S A MS mode recommendations ...

Страница 15: ... annotation 230 V 50 Hz at its edge Each wire is marked N neutral PE earth protection L phase Edge of the power connection cable Make the connection in accordance with standard practice via an IP65 junction box installed at the base of the fan Recommendation Add a grounding strap and connect it with the M6 screw on the crimped nut provided for this purpose located on the fan casing2 2 Reliée à la ...

Страница 16: ...pre configured mode is marked on the label on the outside of the product If you wish to change the management mode proceed as follows Check that the power supply has in fact been cut off for at least 5 minutes before starting to eliminate the risk of electrical shocks from the discharging of certain components 1 Remove the cover from the top of the fan 2 Remove the cover from the protection box of...

Страница 17: ...y with the installation standards in force have 4 conductors each having a cross section of at least 1 5 mm be no longer than 25 m between the fan and its management module and be able to withstand the installation environment in particular be resistant to UV Depending on the EMC specific to the installation site the cable must be put in a metallic shield These recommendations ensure the EMC and l...

Страница 18: ...e fails to start and begins vibrating slightly Do not touch anything the appliance will itself initiate a starting cycle until it actually starts 2 To adjust the speed unscrew the plug on the left Take all the usual precautions because the appliance is still working Do not insert anything through the unit Set the speed level operating the potentiometer Any curve between the minimum a and maximum b...

Страница 19: ...ing key points Actions Comments Check that a 300mA is used for the main differential circuit breaker Measure the power supply 230V in the derivation box for each fan Check that all RJ12 cables between modules are pluged according to the installation and maintenance manual Check the fixation from devices to plenum 3 Ø8mm screws washers Check the grounding strap connection on the fan body insert Che...

Страница 20: ...ontrol circuit of the MS version with a risk of injury Never insert anything through the fan and in particular the suction stream in which the turbine is located Never handle an appliance or remove it from its stack when it is connected Cut off the power supply and make sure that it cannot be reconnected Wait for the turbine to come to a full stop MAINTENANCE AND CLEANING We recommend carrying out...

Страница 21: ...t that connectors are correctly connected to the engine PCB Make sure there is power supply 230V in each fan bypass box Check into the product s body that there is no foreign body that can make noise or prevent the turbine from rotation Check the coupling s condition visual control Possible cause The main circuit breaker dedicated to the power supply is not a 300 mA Only for R version Connectors a...

Страница 22: ...y unqualified personnel If there is any problem please get in touch with your installer or else your dealer PROTECTION OF THE ENVIRONMENT Treatment of the electrical or electronic appliance at end of life applicable in the countries of the European Union and other countries having selective collection systems This logo indicates that the product must not be treated as household waste It must be ta...

Отзывы: