Condensate Neutralization Tank User Instructions
TID-0074_0H
•
8/22/2022 Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page
7
of
14
Figure 3: Elevated Multiple Boiler Units with Tank (P/N 89030)
NOTE:
The condensate neutralizer tank inlet and outlet ports must be lower than the boiler
condensate outlet.
Minimum Boiler Pad Height
BOILER MODEL
DIM. A (MIN. BOILER PAD HEIGHT)
BMK1500/2000
5-
1/4”
BMK2500/3000
5”
BMK 4000/5000N
6
”
Use Figure 3 and the above table for installations where a pit cannot be constructed for the
condensate neutralizer tank. For models not shown in this table: the condensate neutralizer can
be installed on the floor using a 4 inch pad
.