Condensate Neutralization Tank User Instructions
TID-0074_0H
•
8/22/2022 Technical Support
•
(800) 526-0288
•
Mon-Fri, 8 am - 5 pm EST Page
3
of
14
TABLE 1: Condensate Neutralizer Tank Contents (P/N 89030)
Qty.
Description
1
18 liter (4.8 U.S.
gallon) tank (1” FNPT inlet/outlet connections) and lid made from
polypropylene construction; comes filled with neutralization media (P/N 89031).
2
1” NPT PVC
unions
2
1” NPT PVC close nipples
Each Neutralization Tank will neutralize condensate from appliances up to 6,400,000 BTU/hr
input. Table 1 lists the parts included in the Condensate Neutralization Kit (P/N
89030
).
The neutralizer tank can be used for multiple appliance installation with a combined BTU/hr. input
not exceeding 6,400,000. See Tables 2 and 3 for selection guideline for all AERCO gas fired
products.
TABLE 2: Neutralizer Tank Application Chart (BMK, INN, MLX EXT)
AERCO Equipment
BTU/Hr. Input
Kit Qty Required
Eight (8) BMK750
6,000,000
1
Six (6) BMK1000
6,000,000
1
Four (4) BMK1500
6,000,000
1
Three (3) BMK2000
6,000,000
1
Two (2) BMK2500
5,000,000
1
Four (4) BMK2500
10,000,000
2*
Two (2) BMK3000
6,000,000
1
Four (4) BMK3000
12,000,000
2*
One (1) BMK6000
6,000,000
1
Eight (8) INN800
6,400,000
1
Six (6) INN1060
6,360,000
1
Four (4) INN1350
5,400,000
1
Eight (8) MLX EXT 802
6,416,000
1
Six (6) MLX EXT 962
5,772,000
1
Five (5) MLX EXT 1123
5,615,000
1
Four (4) MLX EXT 1530
6,120,000
1
Three (3) MLX EXT 1912
5,736,000
1
Two (2) MLX EXT 2295
4,590,000
1
Two (2) MLX EXT 2677
5,354,000
1
Four (4) MLX EXT 2677
10,708,000
2*
Two (2) MLX EXT 3060
6,120,000
1
Four (4) MLX EXT 3060
12,240,000
2*
* Use one (1) neutralizer tank for each pair of BMK 3.0/BMK 3000. Do not install