5
•
When choosing the location it should be kept in mind that the unit requires maintenance regularly and that the inspection doors
should be easily accessible.
• Leave free space for opening the removable panels and for removal of the main components (see 3.4).
•
The outdoor air grilles if possible be put in the northern or eastern side of the building and away from other exhaust outlets like
kitchen fan exhausts or laundry room outlets.
5.3 Installation
The unit must be installed in the following position.
It is important that the unit is vertical in order for the condensation drainage to work properly.
Fig. 5.a.b
Fig. 5.c
Spirit level
Fig. 5.d
Fig. 5.f
Fig. 5.e
H=min. 60mm
5.a
Prepare the surface where the unit is to be mounted. Make sure that the surface is flat, leveled and that it supports the weight
of the unit. Perform the installation in accordance with local rules and regulations.
5.b
Use the wall fixing bracket as template to indicate where to drill the holes in the wall: make sure it is at spirit level. Use
appropriate screws and wall plugs (not supplied) to fix the wall fixing bracket.
5.c
Hook the unit at its bracket and fix it by means of the safety screw.
5.d
Connect the supplied condensation elbow(s) to the drainage hole(s) in the opening at the bottom of the unit: in case close
and seal the non-used hole with the 2 supplied plugs (one each side of the hole). Make sure of water and air tightness of all
connections. It is necessary to use a U-bend (or similar) in the condensation drainage pipe. The water drainage connections
can be made either through the holes at the bottom side of the casing or through the opening at the rear side of the casing.
5.e
Connect the unit to the duct system. Make sure that all necessary accessories are used to create a functional ventilation solution.
5.f
Connect the unit electrically according to point 5.4. Check that it starts up correctly.