Installer menu

1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating

It allows to set the Bypass operation parameters

Press OK to enter.

Use 

 or 

 to choose “Desired Temperature”, “Tmax Free Heating”, “Tmin Free 

Cooling”.

For definitions see “Bypass” (paragraph 7.3).

Press OK to select.

The setting ranges are:

Desired Temperature: 15°C ÷ 30°C 

Tmax Free Heating: 25°C ÷ 30°C 

Tmin Free Cooling: 15°C ÷ 20°C 

Use 

 or 

 to increase or decrease the temperature.

Press OK to select.

Press ESC to go back to the previous menu.

The factory settings (DEFAULT) are:

Desired Temperature: 23°C 

Tmax Free Heating: 28°C 

Tmin Free Cooling: 18°C 

Installer menu

1 Language
2 Date/Time
3 Machine orientation
4 Bypass settings
5 Heating

To be selected only in case an external heating element (not supplied) is present.

Press OK to enter.

Use 

 or 

 to choose NO/PRE/POST.

Press OK to select.

The factory setting (DEFAULT) is NO.

NO: HEAT output (Fig. 5.g) is never activated 

PRE: the heating element is intalled at “intake air side” (Fig. 7.a -       ).

HEAT output (Fig. 5.g) is activated and heating icon        displays on LCD when 

T21 < HEATING THRESHOLD (Fig. 7.a)

POST: the heating element is intalled at “supply air side” (Fig. 7.a -       ).

HEAT output (Fig. 5.g) is activated and heating icon  

   

   displays on LCD when

 T11 < HEATING THRESHOLD (Fig. 7.a)

C

A

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

This option displays only if “Heating” is set on PRE or POST.

It allows to set the heating threshold in case of PRE or POST heating.

Press OK to enter.

Use 

 or 

 to set the temperature.

Press OK to select.

Setting ranges:

PRE: -20°C ÷ 0°C

POST: +15°C ÷ +25°C

The factory settings (DEFAULT) are: 

PRE:-10°C 

POST:+20°C

Installer menu

6 Heating Threshold
7 Dehumidification
8 Speed Setting
9 Airflow Balancing
10 F7 filter

To be selected only in case an external dehumidifier (not supplied) is present.

Press OK to enter.

Use 

 or 

 to choose NO or YES.

The factory setting (DEFAULT) is NO.

The DH relay output is activated when the HY input is activated (Fig. 5.g) and the icon

  

      

AAAA

is displayed. 

Note: in case dehumidifier is installed, the BST input (Fig. 5.g) is used as alarm output.

Содержание QR400ABP

Страница 1: ...ion 2 3 1 General 2 3 2 Dimensions and Weight 3 3 3 Connections 3 3 4 Space required 4 3 5 Rating label 4 4 Transport and Storage 4 5 Installation 4 5 1 Unpacking 4 5 2 Where how to install 4 5 3 Inst...

Страница 2: ...r than those specified in this manual This appliance can be used by children aged from 8 years and above and persons with reduced physical sensory or mental capabilities or lack of experience and know...

Страница 3: ...e Winter condensation drainage Summer condensation drainage A B D C F E A B C D LEFT Connections from and to outside are set on the left side of the unit front view DEFAULT RIGHT Connections from and...

Страница 4: ...veled before it is put into operation Place the unit preferably in a separate room e g storage laundry room or similar WARNING Make sure that specific warnings and cautions in Chapter 2 Precautions ar...

Страница 5: ...ccordance with local rules and regulations 5 b Use the wall fixing bracket as template to indicate where to drill the holes in the wall make sure it is at spirit level Use appropriate screws and wall...

Страница 6: ...ns SLAVE input 1 10V J2 jumper for SLAVE mode AC power supply Heat output max 250Vac 5A Dehumidifier output max 250Vac 5A Boost momentary switch BST IAQ input Air Quality i e SEN CO2 HY input i e SEN...

Страница 7: ...t settings of the 0 10V signal to the motors Airflow and consumption refer to one single motor Table 6 b indicates the efficiency of the heat exchanger and of the condensation produced in different cl...

Страница 8: ...250 500 1 K 2 K 4 K 8K Tot 3m Intake 73 61 67 69 59 56 50 43 75 47 Supply 72 61 63 65 56 50 41 31 74 43 Extract 73 60 63 65 57 51 42 31 74 44 Exhaust 73 61 66 67 58 55 49 41 75 46 Breakout 71 64 62 67...

Страница 9: ...eset the Filter Alarm ESC key to exit and go back to the previous menu OK key to enter the selected menu to go DOWN with the menu selection to go UP with the menu selection to power off the ventilatio...

Страница 10: ...at speed 1 Press ESC or wait for about 60 sec to go back to the operation screen Fig 7 c In case of activation of either HY or IAQ sensor inputs OR logic the unit speed increases by 15 and the sensor...

Страница 11: ...boost speed Press OK to select The factory setting DEFAULT is 15 Time options are 15 30 45 60 Time is flashing use increase the time and to decrease Press OK to select User menu 1 Mode Selection 2 Bo...

Страница 12: ...lows to select the orientation of the duct connections from and to outside LEFT or RIGHT paragraph 3 3 Press OK to enter Use or to choose Press OK for setting The factory setting DEFAULT is LEFT 7 2 I...

Страница 13: ...s intalled at intake air side Fig 7 a HEAT output Fig 5 g is activated and heating icon displays on LCD when T21 HEATING THRESHOLD Fig 7 a POST the heating element is intalled at supply air side Fig 7...

Страница 14: ...idification 8 Speed Setting 9 Airflow Balancing 10 F7 filter Installer menu 11 Filter Alarm interval 12 Working Hours Counter 13 Save settings 14 Load settings 15 Restore Default Settings It allows to...

Страница 15: ...QR400ABP is equipped with a physical bypass which allows to mitigate the heat exchange when the indoor and outdoor temperature combinations are such that the heat exchange is not recommended In this c...

Страница 16: ...re life time lubricated and maintenance free It is possible to easily disconnect and replace the fans if necessary Filters The filters are of filter quality G4 for both the supply air and extract air...

Страница 17: ...may differ per situation depending on the internal and external environmental conditions Press FILTER button Fig 7 b to reset the Filter Alarm Filters must be replaced every year Clean the heat exchan...

Страница 18: ...18 Fig 8 i Fig 8 h Fig 8 j Fig 8 k Fig 8 l Fig 8 m...

Страница 19: ...ll 1 Drainage parts have not been installed correctly 2 Drain connection below the unit has a too low water level fill it up with water 3 Check filters Change of filters required 4 Check ducting syste...

Страница 20: ...2 Control typology Local demand control Central demand control Manual control no DCV o1 Maximum internal leakage rate 0 6 o2 Maximum external leakage rate 0 4 p1 Internal mixing rate N A p2 External m...

Страница 21: ...21 NOTE...

Страница 22: ...22 NOTE...

Страница 23: ...23 NOTE...

Страница 24: ...office viaCorsica10 25125Brescia C F e P IVA VAT 03369930981 REA BS 528635 Tel 39 030 674681 Fax 39 030 6872149 www aerauliqa com info aerauliqa it Aerauliqa srl reserves the right to modify make impr...

Отзывы: