It allows to adjust the balancing of the two airflows.
Press OK to enter.
Select the submenu item using
or
: press OK to confirm.
1 Advanced Balancing
It allows to set the airflow balancing at speed 1-2-3-Boost, in supply and extract, only if the
unit operates in Normal Mode 3V.
Choose NO or YES using
or
.
Press OK to confirm.
Factory setting (DEFAULT): NO
If “NO”, the submenu “2 Supply Airflow” is displayed.
It allows to adjust the supply airflow against the extract airflow: the selected value is applied
to any speed.
The setting range is: -30% ÷ +30%.
Factory setting (DEFAULT): 0%.
Increase/decrease the speed using
or
.
Press OK to select.
Press ESC to go back to the previous menu.
If “YES”, new submenu items are displayed which allows to set the airflow balancing for each
speed (1-2-3-Boost) and for each motor (supply/extract).
The setting range for any speed is: -30% ÷ +30%.
Factory setting for any speed (DEFAULT): 0%.
Increase/decrease the speed using
or
.
Press OK to select.
Press ESC to go back to the previous menu.
Installer Menu
8 Heating
10 Speed setting
11 Airflow Balancing
12 F7 filter
13 Filter Alarm interval
It allows to select the F7 filter in case the unit is not equipped with it from factory.
The F7 filter should be installed to the “supply air side T22” (Fig. 7 a and 7.b).
Press OK to enter.
Choose NO or YES using
or
.
Press OK to select.
Factory setting (DEFAULT) for QR400 and QR500: Yes.
Factory setting (DEFAULT) for QR280: NO.
Installer Menu
8 Heating
10 Speed setting
11 Airflow Balancing
12 F7 filter
13 Filter Alarm interval
It allows to set the Filter Alarm period: the system has a timer which activates the Filter
warning (Fig. 7c - ) on the LCD at regular intervals.
Press OK to enter.
Choose among 2-3-4-5-6 months using
or
.
Press OK to select.
Factory setting (DEFAULT): 3 months
Installer Menu
8 Heating
10 Speed setting
11 Airflow Balancing
12 F7 filter
13 Filter Alarm interval
Currently not available.
Installer Menu
15 Constant Pressure
17 Periodic purge
18 Working Hours Counter
19 ModBus settings
20 Save settings