background image

Thank you for purchasing an AEMC

®

 

Simple Logger

®

 II.

For best results from your instrument and for your safety, read the enclosed operating 

instructions carefully and comply with the precautions for use. These products must be only 

used by qualified and trained users.

Signifies that the instrument is protected by double or reinforced insulation.

CAUTION - Risk of Danger! Indicates a WARNING and that the operator must 

refer to the user manual for instructions before operating the instrument in all cases 

where this symbol is marked.
Risk of electric shock. The voltage at the parts marked with this symbol may be 

dangerous.

Refers to a type A current sensor. This symbol signifies that application around and 

removal from HAZARDOUS LIVE conductors is permitted.

Ground/Earth

Important instructions to read and understand completely.

Important information to acknowledge.

Battery

Fuse

USB socket

Compliance with the Low Voltage & Electromagnetic Compatibility European direc-

tives (73/23/CEE & 89/336/CEE)
In the European Union, this product is subject to a separate collection system for 

recycling electrical and electronic components In accordance with directive WEEE 

2002/96/EC

Definition of Measurement Categories (CAT)

• CAT IV

 -  3-Phase at utility connection, outdoor conductors:

 

-

Origin of installation, or where low-voltage connection is made to utility power 

 

-

Electricity meters, primary overcurrent protection equipment 

 

-

Outside and service entrance, service drop from pole to building, runs between 

meter & panel 

 

-

Overhead line to detached building, underground line to well pump

• CAT III 

-  3-Phase distribution, including single-phase commercial lighting:

 

-

Equipment in fixed installations, such as switchgear and polyphase motors 

 

-

Bus and feeder in industrial plants 

 

-

Feeders and short branch circuits, distribution panel devices 

 

-

Appliance/equipment outlets with short connections to service entrance

• CAT II 

 -  Single-phase, receptacle-connected loads:

 

-

Appliances, portable tools, and other similar light industrial/household loads 

 

-

Outlet and long-branch circuits 

 

-

Outlets at more than 30 ft from CAT III source 

 

-

Outlets at more than 60 ft from CAT IV source

-4-