OPERATION 

Please make sure that you have already read and fully understand the WARNING section on page 1. 

Making Measurements with the AC Current Probe Model JM850A 

• Connect the black and red terminals to the Ampere AC range of your DMM or current measuring 

instrument. Select the appropriate current range. If the current magnitude is unknown, select the highest 
range (3000A AC / 1A AC) on the switch probe located inside the handle. Clamp the probe around the 
conductor to be tested, with the arrow pointed toward the load. If the reading is less than 200 mA or 20 
mA, select the lower range until you obtain the best resolution. Read the value display on the DMM and 
multiply it by the range selected. (If reading = 0.259A on the 1000/1 range, the current flowing through 
the probe is 0.259A x 1000 = 259 A AC). 

• For best accuracy: carefully center the conductor inside the probe jaw, avoid if possible, the proximity of 

other conductors which may create noise. 

Tips for Making Precise Measurements 

• When using a current probe with a meter, it is important to select the range that provides the best 

resolution. Failure to do this may result in measurement errors. 

• Make sure that probe jaw mating surfaces are free of dust and contamination. Contaminants cause air 

gaps between the jaws, increasing the phase shift between primary and secondary. It is very critical for 
power measurement. 

MAINTENANCE: 

  Warning

 

• For  maintenance use only original replacement parts. 

• To avoid electrical shock, do not attempt to perform any servicing unless you are qualified to do so. 

• To avoid electrical shock and/or damage to the instrument, do not get water or other foreign agents into 

the probe. 

Maintenance 

To ensure optimum performance, it is important to keep the probe jaw mating surfaces clean at all times. 
Failure to do so may result in error in readings. The following is the recommended procedure for cleaning 
the probe jaws: Use a very fine sand paper (fine 600) to avoid scratching the jaw, then gently clean with a 
soft, oil cloth. 

REPAIR AND CALIBRATION 

You must contact our Service Center for a Customer Service Authorization number (CSA#). This will 
ensure that when your instrument arrives, it will be tracked and processed promptly. Please write the CSA# 
on the outside of the shipping container. If the instrument is returned for calibration, we need to know if you 
want a standard calibration, or a calibration traceable to N.I.S.T. (includes calibration certificate plus 
recorded calibration data).  

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

 

15 Faraday Drive 

 Dover, NH 03820 USA 

Tel: 

(800) 945-2362  (Ext. 360)  or  (603) 749-6434  (Ext. 360) 

 

Fax: 

(603) 742-2346 or (603) 749-6309 

 [email protected] 
(Or contact your authorized distributor) 
Costs for repair, standard calibration, and calibration traceable to N.I.S.T. are available. 

NOTE: All customers must obtain a CSA# before returning any instrument. 

TECHNICAL AND SALES ASSISTANCE 

If you are experiencing any technical problems, or require any assistance with the proper use or 
application of this instrument, please call our technical hotline: 

(800) 343-1391 • (508) 698-2115 • Fax (508) 698-2118 

Chauvin Arnoux

®

, Inc. d.b.a. AEMC

®

 Instruments 

[email protected]

 

www.aemc.com 

AC Current Probe 
Model JM850A 

User Manual

 

 

DESCRIPTION 

The JM850A (Catalog # 2110.87) is designed for use in industrial environments. The “squared” jaws 
permit multiple conductor or bus bar positioning. The current output makes it the perfect tool for 
measurement with DMMs, recorders, power and harmonic meters. Three ranges allow you to obtain the 
best resolution even on low current measurement.  The Model JM850A is compatible with any AC 
ammeter, multimeter, or other current measuring instrument with an input impedance lower than 2.5

Ω

. To 

achieve the stated accuracy, use the JM850A with an Ammeter having an accuracy of 0.75% or better.

 

WARNING 

These safety warnings are provided to ensure the safety of personnel and proper operation of the 
instrument. 
•  Read the instruction manual completely and follow all the safety information before attempting 

to use or service this instrument. 

•  Use caution on any circuit: Potentially high voltages and currents may be present and may 

pose a shock hazard. 

•  Read the Safety Specifications section prior to using the current probe. Never exceed the 

maximum voltage ratings given. 

•  Safety is the responsibility of the operator. 

•  ALWAYS connect the current probe to the display device before clamping the probe onto the 

sample being tested. 

•  ALWAYS inspect the instrument, probe, probe cable, and output terminals prior to use. 

Replace any defective parts immediately. 

•  NEVER use the current probe on electrical conductors rated above 600 V in overvoltage 

category III (CAT III). Use extreme caution when clamping around bare conductors or bus bars. 

INTERNATIONAL ELECTRICAL SYMBOLS 

This symbol signifies that the current probe is protected by double or reinforced insulation. Use 
only factory specified replacement parts when servicing the instrument. 

This symbol signifies CAUTION! and requests that the user refer to the user manual before 
using the instrument. 

This is a type A current sensor. This symbol signifies that application around and removal 
from HAZARDOUS LIVE conductors is permitted. 

DEFINITION OF MEASUREMENT CATEGORIES 

Cat. I:

  For measurements on circuits not directly connected to the AC supply wall outlet such as 

protected secondaries, signal level, and limited energy circuits. 

Cat. II: 

For measurements performed on circuits directly connected to the electrical distribution system. 
Examples are measurements on household appliances or portable tools. 

Cat. III:

 For measurements performed in the building installation at the distribution level such as on 

hardwired equipment in fixed installation and circuit breakers. 

Cat. IV: 

For measurements performed at the primary electrical supply (<1000V) such as on primary 
overcurrent protection devices, ripple control units, or meters. 

RECEIVING YOUR SHIPMENT 

Upon receiving your shipment, make sure that the contents are consistent with the packing list. Notify 
your distributor of any missing items. If the equipment appears to be damaged, file a claim immediately 
with the carrier and notify your distributor at once, giving a detailed description of any damage.

www.

GlobalTestSupply

.com

Quality AEMC Products Online at:

[email protected]

Содержание JM850A

Страница 1: ...ical hotline 800 343 1391 508 698 2115 Fax 508 698 2118 Chauvin Arnoux Inc d b a AEMC Instruments techsupport aemc com www aemc com AC Current Probe Model JM850A User Manual DESCRIPTION The JM850A Catalog 2110 87 is designed for use in industrial environments The squared jaws permit multiple conductor or bus bar positioning The current output makes it the perfect tool for measurement with DMMs rec...

Страница 2: ...ge 42V max by limiting circuit Influence of Adjacent Conductor 0 005A A AC Influence of Conductor in Jaw Opening 1 5 0 2A on 1000 1 range 1 0 2A on 2000 1 range 1 0 2A on 3000 1 range MECHANICAL SPECIFICATIONS Operating Temp 14 to 122 F 10 to 50 C Storage Temp 13 to 176 F 25 to 80 C Influence of Temperature 0 1 per 10 K Jaw Opening 3 54 90 mm Maximum Conductor Size Cable 2 52 max 64mm Bus bar 1 97...

Страница 3: ...ge 42V max by limiting circuit Influence of Adjacent Conductor 0 005A A AC Influence of Conductor in Jaw Opening 1 5 0 2A on 1000 1 range 1 0 2A on 2000 1 range 1 0 2A on 3000 1 range MECHANICAL SPECIFICATIONS Operating Temp 14 to 122 F 10 to 50 C Storage Temp 13 to 176 F 25 to 80 C Influence of Temperature 0 1 per 10 K Jaw Opening 3 54 90 mm Maximum Conductor Size Cable 2 52 max 64mm Bus bar 1 97...

Страница 4: ...ical hotline 800 343 1391 508 698 2115 Fax 508 698 2118 Chauvin Arnoux Inc d b a AEMC Instruments techsupport aemc com www aemc com AC Current Probe Model JM850A User Manual DESCRIPTION The JM850A Catalog 2110 87 is designed for use in industrial environments The squared jaws permit multiple conductor or bus bar positioning The current output makes it the perfect tool for measurement with DMMs rec...

Отзывы: