Power Quality Analyzer Model 8335
51
5.1.1.1 Programming and Starting a Search
To program the search for a transient, proceed as follows:
Select the submenu by pressing the icon’s yellow button. The
Detection
Schedule
screen is displayed.
5
1
2
3
4
6
7
8
Figure 5-2
Item
Function
1
Reminder of the mode used
2
Display of sub-mode used
3
Flashing
icon: indicates that the search has been started
4
Memory indicator. Black area = used memory; White area = available memory
5
Transients search start time
6
Transients search end time
7
Number of transients
8
Name of transient
To Configure and Start the Programming of a Search:
1.
Select and set the desired configurations for the Start/Stop date and time, the
Voltage and Current threshold, Count and Series name.
2.
To start programming a search between the start and end times which you
have defined press the yellow button for the
OK
icon.
•
The
OK
icon disappears and the
i
con appears instead.
•
When the start time is reached the message
Detection in progress
is
displayed.
•
When the stop time is reached, the
OK
icon (bottom right of screen) is
displayed again. It is then possible to program a new search.