Clamp-On Ground Tester Model 6418
3. TECHNICAL CHARACTERISTICS
3.1. GENERAL REFERENCE CONDITIONS
Quantities of influence
Reference values
Temperature
73 ±5°F (23 ±3°C)
Relative humidity
50 ±10%RH
Supply voltage
6 ±0.2V
Electric field
<1V/m
Magnetic field
<40A/m
Operating position
clamp horizontal
Position of the conductor in the jaws
centered
Adjacent conductors carrying current in
impedance measurement
At least 3.9” (10cm)
Magnetic mass
At least 3.9” (10cm)
Frequency
50Hz, sinusoidal
Level of distortion
<0.5%
Current present in impedance measurement
0mA
The intrinsic uncertainty
is the error defined under the conditions of
reference.
The operational uncertainty
is the intrinsic uncertainty plus the
variation of the quantities of influence (position, supply voltage,
temperature) as defined in standard IEC 61557. The uncertainties are
expressed as a percentage of the reading (R) and as a number of
display counts (ct): ±(a%R+# ct).
3.2. ELECTRICAL CHARACTERISTICS
3.2.1.
IMPEDANCE MEASUREMENTS
Particular conditions of reference
Inductance in series with the resistance: zero.
Specified
measurement
range
0.010 to
0.099Ω
0.10 to
0.99Ω
1.0 to
49.9Ω
50 to
149Ω
Resolution (ct)
1 mΩ
10 mΩ
100 mΩ
1 Ω
Intrinsic
uncertainty (
δ
)
± (1.5%R +
0.01Ω)
± (1.5%R + 2
ct)
± (1.5%R +
2 ct)
± (2.5%R +
2 ct)
No-load voltage
≤ 45 mV to 2083 Hz