Digital Ground Resistance Tester Model 4500
29
4.5
Ground Resistance Measurement Procedures
(3-Point)
Y
X
X
v
TEST
RANGE
TEST CURRENT
2 10 50
2
20 200 2 20
Alligator Clips
Y
Z
X
52% 62% 72%
0%
100% of distance
between X and Z
Ground Rod
Y Electrode
Z Electrode
Ground Rod
Y Electrode
Z Electrode
Ground
Strip
-10% 3rd
Measurement
+10% 2nd
Measurement
Figure 15
Warning:
Do not disconnect the ground of a live circuit.
• X and Xv (C1, P1) are shorted.
• Connect X to the ground rod to be tested.
• Connect Y (P2) to the central electrode.
• Connect Z (C2) to the farther electrode.
• Use the range selector switch, and select a range with a measurement
capability between 2 and 2000
Ω
.
• Using the test current selector switch, select the highest current for
which you observe a stable reading, and for which the display is not
blinking, or use the following guidelines:
2
Ω
1m
Ω
10mA or
50mA
20
Ω
10m
Ω
200
Ω
0.1m
Ω
2000
Ω
1
Ω
2mA or
10mA
20k
Ω
10
Ω
2mA or
10mA
Ranges
Resolution
Recommended
Current Ranges
2mA, 10mA,
or 50mA