Digital Ground Resistance Tester Model 4500
9
CHAPTER 3
SPECIFICATIONS
3.1
Electrical Specifications
Reference Conditions:
23°C ±3K, 30 to 50% RH; power supply -12V ± 0.2V; no electrical or
magnetic field, no auxiliary rod resistance, no noise voltage.
NOTE:
Specifications given for 60Hz distribution systems; if 50Hz, consult factory.
2
Ω
1m
Ω
10mA or
50mA
20
Ω
10m
Ω
200
Ω
0.1m
Ω
2000
Ω
1
Ω
2mA or
10mA
20k
Ω
10
Ω
2mA or
10mA
Ranges
Resolution
Recommended
Current Ranges
2mA, 10mA,
or 50mA
Maximum Output Voltage:
38Vrms
Accuracy (see chart on following page):
±2% of Reading ± 1ct from 10% to 100% of range
Test Current Ranges:
2mA, 10mA, 50mA
Maximum Auxiliary Electrode Resistance:
Ry: 50k
Ω
on 20
Ω
, 200
Ω
, 2000
Ω
, and
20k
Ω
ranges; 5k
Ω
on 2
Ω
range
Rz: 2mA range: 15k
Ω
10mA range: 3000
Ω
50mA range: 400
Ω
Noise Influence on Accuracy:
0.5% of range (max) to 20V peak-to-peak (20 x peak)
Operating Frequency:
128Hz square wave
Dielectric Test:
2000Vrms, 50/60Hz between four interconnected mea
-
suring terminals and any external metal ground between line input and
measuring terminals on front panel.
Power Supply:
One built-in rechargeable 12V battery, or external 12V
DC
Battery Life:
4 hrs on 50mA test current (800 15-second measurements)
7 hrs on 2mA and 10mA test currents (1500 15-second measurements)