Power & Energy Logger Model PEL 105 - Quick Start Guide
19
3-Phase 4-Wire Y
(3P-4WY)
• VE/GND test lead to ground
• VN test lead to neutral (N)
• V1 test lead to L1
• V2 test lead to L2
• V3 test lead to L3
• IN probe to neutral
• I1 probe to L1
• I2 probe to L2
• I3 probe to L3
3-Phase 3-Wire ∆ Balanced
(1 current probe)
(3P3W∆b)
• VE/GND test lead to ground
• V1 test lead to L1
• V2 test lead to L2
• I3 probe to L3
3-Phase 4-Wire Y Balanced
(3P-4WYb)
• VE/GND test lead to ground
• VN test lead to neutral (N)
• V1 test lead to L1
• IN probe to neutral
• I1 probe to L1
3-Phase 4-Wire Y 2½ Element
(3P-4WY2)
• VE/GND test lead to ground
• VN test lead to neutral (N)
• V1 test lead to L1
• V3 test lead to L3
• IN probe to neutral
• I1 probe to L1
• I2 probe to L2
• I3 probe to L3
L2
L3
L1
N
V1 V2 V3 N
I1
I2
I3
L1
L2
L3
N
L2
L3
L1
N
V1 V2 V3
N
I1
I2
I3
L1
L2
L3
N
L2
L1
L3
V1 V2 V3
N
I1
I2
I3
L1
L2
L3
L2
L3
L1
N
V1 V2 V3 N
I1
I2
I3
L1
L2
L3
N