Error Messages 

(1 of 1)

The control was unable to read a piece of information stored in its memory. Because of this, the control 
was required to reload the factory settings into all of the items in the ADJUST menu. The control will 
stop operation until all of the items in the ADJUST menu of the control have been checked by the user 
or installer. 

Note: 

The 

Advanced / Installer

 DIP switch must be set to 

Advanced

 in order to clear the error.

The control is no longer able to read the outdoor sensor due to a short circuit. In this case the control 
assumes an outdoor temperature of 32

°

F (0

°

C) and continues operation. To clear the error message 

from the control after the sensor has been repaired, press either the 

Menu 

or 

Item 

button.

The control is no longer able to read the outdoor sensor due to an open circuit. In this case the control 
assumes an outdoor temperature of 32°F (0°C) and continues operation. To clear the error message 
from the control after the sensor has been repaired, press either the 

Menu 

or 

Item 

button.

The control is no longer able to read the boiler supply sensor due to a short circuit. The control will not 
operate the boiler(s) until the sensor is repaired. To clear the error message from the control after the 
sensor has been repaired, press either the 

Menu 

or 

Item 

button.

The control is no longer able to read the boiler supply sensor due to an open circuit. The control will not 
operate the boiler(s) until the sensor is repaired. To clear the error message from the control after the 
sensor has been repaired, press either the 

Menu 

or 

Item 

button.

Содержание Pavilion Control 410

Страница 1: ...mand Input DHW Demand Output Boiler Pump Input 115 V ac Power Supply Output Primary Pump Input Timer Output DHW Pump or DHW Valve OR M 1 Boil Dem 2 Com Dem 3 DHW Dem Prim P1 4 5 N L 6 Power 7 8 9 10 1...

Страница 2: ...push buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST menu table which is found in the second half of this brochure Menu All of the...

Страница 3: ...ext Occupied Displays when the control is in occupied mode Modulating Output Scale Displays the total modulation output level of the boiler UnOccupied Displays when the control is in Unoccupied mode B...

Страница 4: ...cupied mode the UNOCC segment is displayed in the LCD The control adjusts the supply water temperature based on the UNOCC settings made in the control EXERCISING The control has a built in exercising...

Страница 5: ...drives the fan at a speed RPM which is proportional to the control s modulating output signal The control displays the current percentage modulation using the BOIL Modulation item in the VIEW menu Wh...

Страница 6: ...g the Primary Pump Purge setting The primary pump continues to run until either the purging time has elapsed or the boiler supply temperature drops more than a differential below the Boiler Minimum se...

Страница 7: ...d to heat the building when the outdoor air temperature is as cold as the outdoor design temperature BOILER INDOOR DESIGN TEMPERATURE BOIL INDR The indoor design temperature is the room temperature th...

Страница 8: ...TION The control has four different modes of DHW operation which depends on the piping arrangement of the DHW tank It is often desirable to limit or even stop the flow of heat to the heating system wh...

Страница 9: ...ty for DHW and possibly heating as well As long as the boiler supply temperature is maintained near its target DHW and heating occurs simultaneously DHW POST PURGE After the DHW Demand is removed the...

Страница 10: ...emperature in the heating system can exceed the maximum desired temperature and can result in damage to the heating system DHW Mode 4 Operation In DHW MODE 4 the space heating zones must be prevented...

Страница 11: ...chamber 13 Mounting holes Control release clip Control release clip STEP TWO MOUNTING THE BASE STEP THREE ROUGH IN WIRING All electrical wiring terminates in the control base wiring chamber The base h...

Страница 12: ...MOD MOD P2 BOIL OUT N COM DEM STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROL General The installer should test to confirm that no voltage is present at any of the wires Push the control into the bas...

Страница 13: ...al 4 and the second side of the pump circuit to the neutral Power N side of the 115V ac power supply DHW Pmp Vlv Contact The DHW Pmp Vlv terminals 7 and 8 are an isolated output There is no power avai...

Страница 14: ...plugged from its header on the control before power is applied for testing To remove the terminal block pull straight down from the control The following tests are to be performed using standard testi...

Страница 15: ...the pump does not turn on check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump If the pump operates properly disconn...

Страница 16: ...ld Test button for 3 seconds Advanced Exercise Off Installer Do not apply power DIP Switches Advanced Exercise Off Installer Advanced Exercise Off Installer Dip Switch Settings Connecting The Control...

Страница 17: ...ng this item 0 to 1999 hr Display Description Range I n s t a l l e r A d v a n c e d Adjust Menu 1 of 2 Room Occupied The desired room air temperature during the occupied period 35 to 100 F 2 to 38 C...

Страница 18: ...OFF WWSD Occupied The system s warm weather shut down temperature during the Occupied period 35 to 100 F OFF 2 to 38 C OFF Default 70 F 21 C WWSD Unoccupied The system s warm weather shut down tempera...

Страница 19: ...modulation output increases to 100 Modulation Step 5 If there is a demand present the modulation output decreases to the minimum modulation percentage Step 6 The modulation output decreases to 0 and...

Страница 20: ...r has been repaired press either the Menu or Item button The control is no longer able to read the outdoor sensor due to an open circuit In this case the control assumes an outdoor temperature of 32 F...

Страница 21: ...sure The sensor should be mounted on a wall which best represents the heat load on the building a northern wall for most buildings and a southern facing wall for buildings with large south facing glas...

Страница 22: ...to earth ground Follow the sensor testing instruction in this brochure and connect the wires to the control Replace the front cover of the sensor enclosure Installation Boiler Sensor 00229 STEP ONE MO...

Страница 23: ...mometer is not available a second sensor can be placed alongside the one to be tested and the readings compared First measure the temperature using the thermometer and then measure the resistance of t...

Страница 24: ...1 Boil Dem 2 Com Dem 3 DHW Dem Prim P1 4 5 N L 6 Power 7 8 9 10 11 12 13 14 15 16 Com Boil Out UnO Sw Boiler Control 410 Outdoor Reset DHW Mod V dc Boil P2 DHW Pmp Vlv HXXXXA Menu Item Boiler Demand D...

Отзывы: