background image

 

11 of 24

  

© 

2006 

 D 410 - 01/06

The control can be mounted 
on a standard DIN rail. First 
remove the control from its 
base and then, using the hooks 
and spring clip on the back of 
the control, mount it onto the 
DIN rail. This will be a popular 
option for those who prefer to 
mount the control inside a larger 
electrical panel.

The wiring can enter the 
bottom or the back of the 
enclosure. Knock-outs pro-
vided in the base allow the 
wiring to be run in conduit 
up to the enclosure. The 
base also has holes that 
line up with the mounting 
holes of most common 
electrical boxes.

Press down at the fi ngertip grips 
on top of the front cover and pull 
out and down.

Lift the front cover up and away 
from the control.

Loosen the screws at the front 
of the wiring cover.

The wiring cover pulls straight out 
from the wiring chamber.

The base is ready for mounting.

The control lifts up and away 
from the base.

Press the control release clip 
on the base inside the wiring 
chamber and slide the control 
upwards.

Remove the safety dividers 
from the wiring chamber by 
pulling them straight out of their 
grooves.

There are 10 conduit knock-outs at the back 

and bottom of the wiring chamber.

13 Mounting holes

Control 

release 

clip

Control release clip

STEP TWO 

   

MOUNTING THE BASE

 STEP THREE 

 ROUGH-IN WIRING

All electrical wiring terminates in the control base wiring chamber. The base has standard 7/8” (22 mm) knockouts, which accept 
common wiring hardware and conduit fittings. Before removing the knockouts, check the wiring diagram and select those sections 
of the chamber with common voltages. Do not allow the wiring to cross between sections, as the wires will interfere with safety 
dividers which should be installed at a later time.

Power must not be applied to any of the wires during the rough-in wiring stage.

•• 

All wires are to be stripped to a length of 3/8” (9 mm) to ensure proper connection to the control.

•• 

Install the Outdoor Sensor 00228 according to the installation instructions in this brochure and run the wiring back to the control.

•• 

Install the Boiler Sensor 00229 according to the installation instructions in this brochure and run the wiring back to the control.

•• 

Run wire from other system components (pumps, boilers, etc.) to the control.

•• 

Run wires from the 115 V (ac) power to the control. Use a clean power source with a 15 A circuit to ensure proper operation.  
Multi-strand 16 AWG wire is recommended for all 115 V (ac) wiring due to its superior flexibility and ease of installation into 
the terminals.

Содержание Pavilion Control 410

Страница 1: ...mand Input DHW Demand Output Boiler Pump Input 115 V ac Power Supply Output Primary Pump Input Timer Output DHW Pump or DHW Valve OR M 1 Boil Dem 2 Com Dem 3 DHW Dem Prim P1 4 5 N L 6 Power 7 8 9 10 1...

Страница 2: ...push buttons Menu Item for selecting and adjusting settings As you program your control record your settings in the ADJUST menu table which is found in the second half of this brochure Menu All of the...

Страница 3: ...ext Occupied Displays when the control is in occupied mode Modulating Output Scale Displays the total modulation output level of the boiler UnOccupied Displays when the control is in Unoccupied mode B...

Страница 4: ...cupied mode the UNOCC segment is displayed in the LCD The control adjusts the supply water temperature based on the UNOCC settings made in the control EXERCISING The control has a built in exercising...

Страница 5: ...drives the fan at a speed RPM which is proportional to the control s modulating output signal The control displays the current percentage modulation using the BOIL Modulation item in the VIEW menu Wh...

Страница 6: ...g the Primary Pump Purge setting The primary pump continues to run until either the purging time has elapsed or the boiler supply temperature drops more than a differential below the Boiler Minimum se...

Страница 7: ...d to heat the building when the outdoor air temperature is as cold as the outdoor design temperature BOILER INDOOR DESIGN TEMPERATURE BOIL INDR The indoor design temperature is the room temperature th...

Страница 8: ...TION The control has four different modes of DHW operation which depends on the piping arrangement of the DHW tank It is often desirable to limit or even stop the flow of heat to the heating system wh...

Страница 9: ...ty for DHW and possibly heating as well As long as the boiler supply temperature is maintained near its target DHW and heating occurs simultaneously DHW POST PURGE After the DHW Demand is removed the...

Страница 10: ...emperature in the heating system can exceed the maximum desired temperature and can result in damage to the heating system DHW Mode 4 Operation In DHW MODE 4 the space heating zones must be prevented...

Страница 11: ...chamber 13 Mounting holes Control release clip Control release clip STEP TWO MOUNTING THE BASE STEP THREE ROUGH IN WIRING All electrical wiring terminates in the control base wiring chamber The base h...

Страница 12: ...MOD MOD P2 BOIL OUT N COM DEM STEP FOUR ELECTRICAL CONNECTIONS TO THE CONTROL General The installer should test to confirm that no voltage is present at any of the wires Push the control into the bas...

Страница 13: ...al 4 and the second side of the pump circuit to the neutral Power N side of the 115V ac power supply DHW Pmp Vlv Contact The DHW Pmp Vlv terminals 7 and 8 are an isolated output There is no power avai...

Страница 14: ...plugged from its header on the control before power is applied for testing To remove the terminal block pull straight down from the control The following tests are to be performed using standard testi...

Страница 15: ...the pump does not turn on check the wiring between the terminal block and pump and refer to any installation or troubleshooting information supplied with the pump If the pump operates properly disconn...

Страница 16: ...ld Test button for 3 seconds Advanced Exercise Off Installer Do not apply power DIP Switches Advanced Exercise Off Installer Advanced Exercise Off Installer Dip Switch Settings Connecting The Control...

Страница 17: ...ng this item 0 to 1999 hr Display Description Range I n s t a l l e r A d v a n c e d Adjust Menu 1 of 2 Room Occupied The desired room air temperature during the occupied period 35 to 100 F 2 to 38 C...

Страница 18: ...OFF WWSD Occupied The system s warm weather shut down temperature during the Occupied period 35 to 100 F OFF 2 to 38 C OFF Default 70 F 21 C WWSD Unoccupied The system s warm weather shut down tempera...

Страница 19: ...modulation output increases to 100 Modulation Step 5 If there is a demand present the modulation output decreases to the minimum modulation percentage Step 6 The modulation output decreases to 0 and...

Страница 20: ...r has been repaired press either the Menu or Item button The control is no longer able to read the outdoor sensor due to an open circuit In this case the control assumes an outdoor temperature of 32 F...

Страница 21: ...sure The sensor should be mounted on a wall which best represents the heat load on the building a northern wall for most buildings and a southern facing wall for buildings with large south facing glas...

Страница 22: ...to earth ground Follow the sensor testing instruction in this brochure and connect the wires to the control Replace the front cover of the sensor enclosure Installation Boiler Sensor 00229 STEP ONE MO...

Страница 23: ...mometer is not available a second sensor can be placed alongside the one to be tested and the readings compared First measure the temperature using the thermometer and then measure the resistance of t...

Страница 24: ...1 Boil Dem 2 Com Dem 3 DHW Dem Prim P1 4 5 N L 6 Power 7 8 9 10 11 12 13 14 15 16 Com Boil Out UnO Sw Boiler Control 410 Outdoor Reset DHW Mod V dc Boil P2 DHW Pmp Vlv HXXXXA Menu Item Boiler Demand D...

Отзывы: