background image

3

Classification VFI SS 111 acc. to IEC 62040-3

Protect 3.M 2.0

Power type rating

20 kVA

40 kVA

60 kVA

80 kVA

100 kVA

120 kVA

16 kW

32 kW

48 kW

64 kW

80 kW

96 kW

SyStEM

Nominal input current

29 A

59 A

88 A

117 A

145 A

172 A

Efficiency (typical)

95 %

Efficiency in ECO mode

98 %

Waste heat from power (typical)

1.3 kW

2.6 kW

3.9 kW

5.2 kW

6.5 kW

7.8 kW

4436 BTU/h

8872 BTU/h

13308 BTU/h

17744 BTU/h

22180 BTU/h

26616 BTU/h

Airflow (max.) m³/h

309

617

926

1234

1543

1852

INPut

Nominal voltage

3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral

Input voltage range

305 – 477 V

Frequency

50 Hz/ 60 Hz (adjustable)

total harmonic distortion (tHDv)

≤3 % 

1)

Power factor

>0.99

INVErtEr

Nominal voltage

3 x 400 V (380 V, 415 V adjustable), 3 phase + neutral

Frequency

50 / 60 Hz (adjustable)

Precision  static /dynamic

 ±1 % / ±7 %

total harmonic distortion (tHDv)

<3 % ( linear load), <5 % (non-linear load)

Max. phase displacement

±1.5 % (balanced load), ±2 % (100 % unbalanced load)

Admissible overload

125 % for 10 min., 150 % for 60 s

Crest factor

2.7 : 1

Max. short circuit current

>270 % of the rated current

Admissible power factor

0.1 inductive to 0.1 capacitive

BAttEry

rated voltage

±240 V DC

Max. charging power

5 A

10 A

15 A

20 A

25 A

30 A

Charging principle

Load switching per power module

Autonomy time

Selectable over external battery cabinet

StAtIC ByPASS

Nominal voltage

3 x 400 V (380, 415 V adjustable), 3 phase + neutral

Frequency

50 Hz / 60 Hz (adjustable)

Synchronization range

±0.1 – ±5 % (adjustable)

transfer time at mains outage

0 ms (without interruption)

Admissible overload

175 % for 10 ms

GENErAl DAtA

Parallel mode

Up to 4 UPS (central battery possible)

Audible noise

62 – 69 dB(A) dependent on equipment installed and load state

Operating  temperature  range / humidity

0 – 40 °C / <95 % (without condensation)

Protection

IP20

Color

RAL 7035

Cable entry

Underside

Environmental conditions

Free from corrosive air and conductive dust

COMMuNICAtION

Display

320 x 240 graphical LCD display

Alarm signals

Acoustic and visual

Interfaces

Remote signal contact, RS232, 2 x communication slots for SNMP / Modbus / additional relay cards

DIMENSIONS

Dimensions approx. D x W x H (mm)

910 x 520 x 1165

975 x 520 x 1655

Footprint (m²)

0.47

0.51

Weight approx.

139 kg

204 kg

Weight approx. (incl. module)

169 kg

199 kg

229 kg

259 kg

354 kg

384 kg

1) by THDv ≤2 %

Содержание Protect 3.M 2.0

Страница 1: ...The flexible redundancy concept ensures a steady power supply to any connected devices Lower operating costs for energy and cooling with high efficiency and fast module replacement in the event of power failure reduce operational costs and ensure an optimal price vs performance ratio for the Protect 3 M 2 0 UPS solution Key features Modular design allows for flexible adaption to the current power ...

Страница 2: ...pts the permitted UPS power according to your current power needs This can be done without additional installation costs since the power modules can be easily inserted and are automatically recognized by the system hot swappable No additional connections are required for this operation Dynamic redundancy An automatic load balancing to all modules within an appropriately designed system delivers N ...

Страница 3: ...d current Admissible power factor 0 1 inductive to 0 1 capacitive Battery Rated voltage 240 V DC Max charging power 5 A 10 A 15 A 20 A 25 A 30 A Charging principle Load switching per power module Autonomy time Selectable over external battery cabinet Static bypass Nominal voltage 3 x 400 V 380 415 V adjustable 3 phase neutral Frequency 50 Hz 60 Hz adjustable Synchronization range 0 1 5 adjustable ...

Страница 4: ...ignal contacts MODBUS extension card and SNMP adapter Battery Management Each UPS power module contains its own battery charger with intelligent charging electronics These can be adapted to the battery in use and facilitate the use of vendor independent standard batteries A temperature compensated charging curve ensures an optimum charging regime Automatic testing informs you of the charging state...

Отзывы: