5.6
Starting the UPS with utility
Startup preparation:
Before startup the UPS, please make sure that the wiring is securely connected,
otherwise there is a danger of electric shock.
•
Verify that the total UPS output load does not exceed the rated capacity of
the UPS.
•
The wiring of the UPS input and output is correctly connected according
to the required mode.
•
Confirm that the UPS output device is not started.
•
Make sure the UPS is reliably connected to the battery.
•
Connect communication interfaces that need to be used.
Startup the UPS with utility power:
Startup the UPS with utility power:
Startup the UPS with utility power:
Startup the UPS with utility power:
1.
Turn on input breaker and output breaker.
2.
The fan starts to rotate, the LCD displays startup animation, then enters
the main page.
3.
UPS default Bypass enable, the main page shows UPS working in bypass
mode.
4.
The default input/output mode is three-input and three-out. If it is
inconsistent with the actual wiring, it needs to be changed to the actual
wiring mode.
5.
Press the button for more than 1 second, the buzzer will beep and the UPS
will start up. After a few seconds, the UPS will go to normal mode.
6.
If the utility power is abnormal, the UPS will transfer to Battery mode.
7.
When the battery is not connected, the UPS can still be startup. After the
startup, there is alarm of battery not connected. If the utility power is
abnormal, the UPS load will not be protected.
Содержание PROTECT 1 LCD
Страница 5: ...Revision Change Date Name 00 Created 21 07 2021 AN ...
Страница 6: ......
Страница 32: ... Connect with user s own EBM Connect user s own EBM to UPS with Battery cable if configured ...
Страница 37: ... 3 3 configuration dual source 3 1 configuration single source ...
Страница 38: ... 3 1 configuration dual source 1 1 configuration single source ...
Страница 40: ...Note Note Note Note Common battery configuration is not suitable for standard model ...
Страница 46: ...5 3 Menu structure ...