Special precautions
The unit is heavy: wear safety shoes and use vacuum lifter preferentially
for handling operations.
All handling operations will require at least two people (unpacking, lifting,
installation in rack system).
Before and after the installation, if the UPS remains de-energized for a
long period, the UPS must be energized for a period of 24 hours, at least
once every 6 months (for a normal storage temperature less than 25°C).
This charges the battery, thus avoiding possible irreversible damage.
During the replacement of the Battery Module, it is imperative to use the
same type and number of elements as the original Battery Module
provided with the UPS to maintain an identical level of performance and
safety.
This is a category C3 UPS product. In a residential environment, this
product may cause radio interference, in which case the user may be
required to take additional measures.