Logic inputs
Make and carry :
30A for 3s
Carry :
5A continuous
Break :
DC : 50W resistive
DC : 25W inductive (L/R = 40ms)
AC : 1250VA
AC : 1250 VA inductive (cos
ϕ
= 0.5)
Maxima :
5A and 300V
Loaded contact :
10 000 operation minimum
Unloaded contact :
100 000 operation minimum
Operation time
< 7 ms
Output Relay Contacts
Energization of the logic inputs is realised with a DC or ACauxiliary voltage.
The output contacts of
HF9024
RELAY
are
AgCdO dry contacts.
All the logic inputs are optically-isolated and independent :
HF
9024 relay has
2 logic inputs.
Auxiliary voltage: 48-150VDC/32-100VAC
Logic input recognition time = 5 ms