6 Mounting
6.1 Mounting location requirements
The Steca battery chargers STM 80, STM 81, STM 860 and STM 861 must
be mounted on the wall in a vertical (standing) position.
The deviation from the plumb line may not exceed 15°.
The background must be even, and must not be easily flammable, e.g. con-
crete or stone.
In order to guarantee circulation at the rear of the casing, there must be
clearance of at least 0 cm above and below.
Mount in the vicinity of a mains power socket. The mains cable has a length
of 1.7 m.
STM 80/81 must be mounted in enclosed rooms.
STM 860/861 may be mounted outdoors.
Safety instruction
Do not open the device.
WARNING
Risk of electrical shock and fire due to cables coming loose!
Make sure that no tension is applied to the mains cables or charging cables.
6.2 Mounting the STM 860/861
Attach the mounting plate to the wall with four M5 screws (not provided).
Allow the device to slide down from above, onto the hooks which project
out at the front. In so doing, make sure that the locking mechanism drops
over the cooling plate fins.
This secures the device and prevents it from falling.
Check that the device is mounted correctly.
The cooling fin furthest on the right must drop over the edge rising up
on the fixing plate.
Plug in the mains plug.
6.3 Mounting the STM 820/821
CAUTION
Risk of injury and damage to the casing when drilling!
Do not use the casing as a drilling template.
Mark the upper two fastening holes.
Drill holes and screw in the screws.
Hang the device on the upper screws.
Mark the lower two fastening holes.
Remove the device again.
Drill the lower holes.
Hang the device on the upper screws again.
Screw the device firmly in place at the lower holes.
Plug in the mains plug.
•
•
•
•
•
•