IST6
Series (200K-600K) Modular UPS
User Manual
3 Installation
All rights reserved ©
Allis Electric
Co., Ltd.
43
Step 3
Connect the IN port of SNMP card with the RS232 port of system monitor card through the equipped
with network wire, as shown in Figure3-16.
SNMP card
System monitor card
BSC
PARALLEL
NORMAL
ALARM
FAULT
BSC
PARALLEL
NORMAL
ALARM
FAULT
NC NO COM
ND1
NC NO COM
ND2
NC NO COM
ND3
NC NO COM
ND4
COM NC
ND5
COM NC
ND6
COM NO
EPO1
COM NC
B-Temp
NC COM
EPO2
RS232
MODBUS/
RS485
MDU
NETWORK
A B
COM1
R
E
IN
Figure3-16
SNMP card connection diagram
----End
3.5 System Wiring
There are two types of
IST6200
、
IST6300
UPS with up and bottom wiring. The
IST6400
、
IST6500
、
IST6600
UPS are compatible with top and bottom wiring.
3.5.1
IST6200
,
IST6300
(Bottom wiring)
Step 1
Open the front door and rear door of the cabinet, as shown in Figure3-17.
Figure3-17
Remove the sealing plate diagram