background image

A121APPX,  AL121APPX & MV121 APPELLO  

Alarm Tone and Voice Annunciation Sounder 

 

1)  Introduction 

The  Appello  tone  and  speech  annunciation 
sounder has three different styles in AC and DC. 

·

 

A121APPX & MV121     Sounder 

·

 

AL121APPX   Sounder-Beacon Combination 
Sounder-Beacon  Combination  units  are 
available  as  either  a  high  output  LED  or 
Xenon strobe. 
 

These  Sounder  units  share  a  common  set  of 
functions:- 

·

 

4  stages,  each  stage  can  record  up  to  30 
seconds of CD quality audio. 

·

 

Facility to record via an on board microphone 
or a line in input. 

·

 

The  recorded  message  can  be  played  back 
proceeded  either  with  or  without  the  choice 
of one of forty five tones. 
 

The Beacon functions are either:- 

·

 

Xenon Strobe - 1Hz flash rate 

·

 

LED - Either Steady or 2Hz blink rate 

2)  Operating and Marking 

 
All 

units 

have 

the 

following 

operating 

requirements and limitations. 
 
Unit Type No.     Voltage    Range          Current 
Sounder only outputs 
A121APPX DC   24Vdc    14-30Vdc      1.51A  
& MV121 DC 
 

 

Max Current 1.85A @ 30Vdc 

A121APPX AC  115Vac   90-260Vac   542mA 
&  MV121 AC 

230Vac   90-260Vac   517mA 

 

 

Max Current 668mA @ 90Vac 

 
AL121APPX combined unit - Add selected 
sounder & beacon currents to calculate total 
current required. 
  
 

 

Beacon only outputs 

LED Beacon DC   24Vdc    10-30Vdc      157mA 
 

 

Max Current 166mA @ 30Vdc 

LED Beacon AC  115Vac   90-260Vac   60mA 
 

 

230Vac   90-260Vac   35mA 

 

 

Max Current 60mA @ 90Vac 

 
Xenon Beacon DC 12Vdc   10-14Vdc      500mA 
 

 

  24Vdc   20-28Vdc      250mA 

Xenon Beacon AC /-10%Vac   100mA 
 

 

 230Vac  +/-10%Vac    50mA 

 
Operating Temp:  -20 to +55

°

All units IP Rating: Type 4 / 4X / 3R / 13 , IP66 
MV121    

additional IP Rating: IP67 

 

Marking:  

 

 
 

3)  Installation & Wiring Requirements

 

 
A121APPX 

 

 
 
AL121APPX 

 

 
 
MV121 

 

 
 
 

                                        

INSTRUCTION MANUAL 

W>KϭϮϭͲĐŽŵŵĞƌĐŝĂůƌĞĨ

ϭϮϭyͲĨĂĐƚŽƌLJƌĞĨ

ae&t - 4 impasse Joliot Curie - 64110 Jurançon - tél 05 59 06 06 00 - [email protected] - aet.fr

Содержание APPELLO A121APPX

Страница 1: ...ts have the following operating requirements and limitations Unit Type No Voltage Range Current Sounder only outputs A121APPX DC 24Vdc 14 30Vdc 1 51A MV121 DC Max Current 1 85A 30Vdc A121APPX AC 115Vac 90 260Vac 542mA MV121 AC 230Vac 90 260Vac 517mA Max Current 668mA 90Vac AL121APPX combined unit Add selected sounder beacon currents to calculate total current required Beacon only outputs LED Beaco...

Страница 2: ... Recording The unit will need to be configured to suit the end user If recording either via the onboard microphone or the in line connector the unit will need to be supplied with power DC units can be powered when completing recording and set up Warning During set up on AC units care must be taken not to touch the live terminals This is because on the AC units there is a risk of electric shock See...

Страница 3: ...l Ie for Stage 2 link the ve supply to the S2 terminal for Stage 3 link the ve supply to the S3 terminal etc AC Units Second Third and Fourth Stage Selection The Appello unit uses Live switching to change the tone to the second third and fourth stages To change to the second third or fourth stage tone whilst maintaining the ac supply to the Live and neutral also link the Live supply line to termin...

Страница 4: ...o unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or Microphone inputs o Select the required alarm tone o Delete unwanted messages To re record a message on a particular stage the previous message on that stage must be deleted first Once the user has conf...

Страница 5: ...icrophone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Playback Message only Playback 7 Single Message or Mass Erase Mode OFF Single Message or Mass Erase Mode ON Quick Ref Playback Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 1 2 3 5 to ON Alternatively for For Stage 2 Set Switch S2 positions 1 3 5 to ON For Stage 3 Set Switch S2 position...

Страница 6: ...in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Switch on power or Press reset button 3a Press action button Start recording 3b Speak into microphone or plug line in It is suggested that a 5cm gap is maintained to the microphone The peak detector L E D should flash regularly to maintain a good recording level However if it stays on for most of the ti...

Страница 7: ...ch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stage 3 Set Switch S2 positions 2 7 to ON For Stage 4 Set Switch S2 position 7 to ON 2 Switch on power or Press reset button 3a Press action button Erase will begin 3b erase complete ...

Страница 8: ...l Stages 1 Set Switch S2 position 7 to ON 2 Set jumper ME to ON position centre and bottom pin connected 3 Switch on power or Press reset button 4a Press action button Erase will begin 4b erase complete 5 Reset Jumper ME to OFF position ...

Страница 9: ...ve position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Master unit first Then switch power onto the Slave unit Master Unit Slave Unit 4a Press action button on the Master Unit Synchronisation will begin Duration 13 Minutes Master Unit Slave Unit 4b Synchronisation complete Switch off Power to units Master Unit Slave Unit 5 Reset on both units jumper SY to ...

Страница 10: ...ne 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 sec Intermittent Tone 2 Tone 5 Tone 29 Tone 23 800Hz 2Hz Intermittent Tone 6 Tone 5 Tone 29 Tone 24 800 1000Hz 50Hz Sweeping Tone 29 Tone 5 Tone 29 Tone 25 2400 2900Hz 50Hz Sweeping Tone 29 Tone 5 Tone 29 Tone 26 Bell Tone 2 Tone 15 Tone 29 Tone 27 554Hz Continuous Tone 26 Tone 5 Tone 29 Tone 28 440Hz...

Отзывы: