WISE-4471 Series User Manual

Chapter 4

S

ystem

Configuration

will return to the startup value, which is zero by default.
If 

Keep Last Value

 is enabled, the last counter value will be kept in the register 

when the module is powered off. When the module is powered on, the counter 
will continue to count from that value. When this function is disabled, powering 
off the module will cause the counter to be reset and the count value in the reg-
ister to be reset to zero.

Frequency: 

For pure digital input channels, WISE modules support frequency 

mode, which calculates the frequency of the digital input signal of the selected 
channel. The frequency value will be displayed in the 

Frequency value

 box on 

the DI Status page. 

Precision

 can be configured here to decide the unit of fre-

quency for different kind of input range. 

Value Reset Time

 function is design for 

deciding when will the frequency value been reset to zero if pulse bandwidth 
longer than expect.

Low-to-High Latch: 

Under low-to-high latch mode, once a digital input channel 

detects that the logic level has changed from low to high, the logic status will 
remain as "logic high" until the latch is cleared manually, which will return the 
logic status to "logic low." The logic status is viewable on the latch status LED 
display on the

 DI Status

 page. Clear the latch by clicking 

Clear

 on this page. 

High-to-Low Latch:

 Under high-to-low latch mode, once a digital input channel 

detects that the logic level has changed from high to low, the logic status will 
remain as "logic low" the latch is cleared manually, which will return the logic 
status to "logic high." The logic status is viewable on the latch status LED dis-
play on the

 DI Status

 page. Clear the latch by clicking 

Clear

 on this page.

Содержание WISE-4470 Series

Страница 1: ...User Manual WISE 4471 Series ...

Страница 2: ...lation Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers never need to use our repair service If an Advantech product is defec tive it will be repaired or replaced at no charge during the warranty period For out of warranty repairs you will be billed accord...

Страница 3: ...t installed and used in accordance with the instructions may cause harmful interfer ence to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interfer ence to radio or television reception which can be determined by turning the equip ment off and on the user is encouraged to try to correct the inter...

Страница 4: ...al we would welcome comments and constructive criticism Please send all such in writing to support advan tech com Package List Before setting up the system check that the items listed below are included and in good condition If any item does not accord with the table please contact your dealer immediately WISE 4471 S250 module x 1 Mounting bracket x 1 Quick startup manual x 1 China RoHS declare x ...

Страница 5: ... liquid into an opening This may cause fire or electrical shock 13 Never open the equipment For safety reasons the equipment should be opened only by qualified service personnel 14 If one of the following situations arises get the equipment checked by service personnel 15 The power cord or plug is damaged 16 Liquid has penetrated into the equipment 17 The equipment has been exposed to moisture 18 ...

Страница 6: ...om damage To avoid electrical shock always disconnect the power from your PC chassis before you work on it Don t touch any components on the CPU card or other cards while the PC is on Disconnect power before making any configuration changes The sudden rush of power as you connect a jumper or install a card may damage sensitive elec tronic components ...

Страница 7: ...Pin Assignment 7 2 5 Block Diagram 8 Figure 2 5 WISE 4471 S250 Block Diagram 8 Chapter 3 Hardware Installation 9 3 1 Interface Introduction 10 Figure 3 1 WISE 4471 Interface Introduction 10 3 2 Mounting 10 Figure 3 2 WISE 4471 Series Mounting Kit Dimensions 10 3 2 1 DIN Rail Mounting 11 Figure 3 3 WISE 4471 DIN rail Mounting Installation 11 Figure 3 4 WISE 4471 DIN rail Mounting front 11 Figure 3 ...

Страница 8: ...guration 23 4 2 7 System Configuration 32 4 2 8 Data Logger 35 4 2 9 Diagnostician 38 4 2 10 Push Notification 38 4 2 11 iSensing MQTT 39 Appendix A iSensing MQTT 43 A 1 iSensing MQTT Format for publishing 45 A 1 1 Topic Format Advantech MAC_Address data 45 A 1 2 Payload Format 45 A 1 3 Example 46 A 2 iSensing MQTT Format for subscribing 48 A 2 1 Topic Format Advantech MAC_Address ctl doIndex 48 A...

Страница 9: ...Chapter 1 1 Product Overview ...

Страница 10: ... S250 Cellular IoT WSN with 6 digital inputs 2 digital outputs and 1 port RS 485 LED Color Indication Behavior Status Green Blink 2Hz Awaiting connection 0 5Hz Connected to network Error Red Blink 2hZ Network Error Error 1st Signal Strength Red Green Blink RF Related Error Error 2nd Signal Strength Red Green Blink IO Related Error Cellular Rx Green Blink Receiving data via cellular network Cellula...

Страница 11: ...Chapter 2 2 Product Overview ...

Страница 12: ... accuracy 2 s day Enclosure PC Mounting DIN 35 rail wall pole and stack Dimensions W x H x D 69 x 112 x 38 mm Operation temperature 20 60 C 4 140 F Storage temperature 40 85 C 40 185 F Operating humidity 20 95 RH non condensing Storage humidity 0 95 RH non condensing Note WISE 4471 modules can operate below 30 humidity However envi ronments with low relative humidity are prone to problems with ele...

Страница 13: ... power off Supports frequency input function maximum signal frequency 3 kHz Supports inverted digital input status 2 2 2 Digital Outputs Channels 2 Open collector to 30 V 100 mA maximum for resistance load Inductive loads require an external diode to eliminate back EMF when the digital output is OFF On resistance RDS ON 4Ω max 100 mA 25 C Supports 5 kHz pulse output Supports high to low and low to...

Страница 14: ...WISE 4471 Series User Manual 6 2 3 Application Wiring Figure 2 1 WISE 4471 S250 Digital Output Wiring Diagram Figure 2 2 WISE 4471 S250 Digital Input Wiring Diagram ...

Страница 15: ...7 WISE 4471 Series User Manual Chapter 2 Product Overview Figure 2 3 WISE 4471 S250 RS 485 Wiring Diagram 2 4 Pin Assignment Figure 2 4 Pin Assignment ...

Страница 16: ...WISE 4471 Series User Manual 8 2 5 Block Diagram Figure 2 5 WISE 4471 S250 Block Diagram ...

Страница 17: ...Chapter 3 3 Hardware Installation ...

Страница 18: ...anual 10 3 1 Interface Introduction Figure 3 1 WISE 4471 Interface Introduction 3 2 Mounting Applicable installation methods are briefly described in the following sections Figure 3 2 WISE 4471 Series Mounting Kit Dimensions ...

Страница 19: ... can be fixed to a cabinet with mounting rails Use a flathead screwdriver to fasten the DIN rail adapter to your module You can then use the end brackets included in the package in order to keep it from sliding Figure 3 3 WISE 4471 DIN rail Mounting Installation Figure 3 4 WISE 4471 DIN rail Mounting front ...

Страница 20: ...l 12 Figure 3 5 WISE 4471 DIN rail Mounting back 3 2 2 Wall Mounting The plastic wall mounting bracket that comes with the module can be used to mount it on a wall panel or cabinet Figure 3 6 WISE 4471 Wall Mounting Installation ...

Страница 21: ...ng For pole mounting feed the pole mounting ring through the hole in the middle of the module The pole mounting ring needs to be unlocked with a screw driver before it can be inserted through the module To mount the module on the pole tightly lock the pole mounting ring Figure 3 8 WISE 4471 Pole Mounting Installation ...

Страница 22: ...y Wiring WISE 4471 modules are designed to support a standard industrial unregulated 24 VDC power supply For other applications they can also accept 10 to 50 VDC input with 200 mV of peak to peak power ripple The immediate ripple voltage should be maintained between 10 and 50 VDC The screw terminals labeled Vs and Vs are for the power supply wiring Figure 3 10 WISE 4471 S250 Power Wiring ...

Страница 23: ...odules The terminal block accepts wires from 0 5 mm to 2 5 mm Use the correct wire gauge note that the terminal block accepts wires from 0 5 to 2 5 mm Use a continuous length of wire do not join separate wires to form a continuous length Use the shortest wire length possible Use wire trays for routing wherever possible Avoid running wires near to high energy wiring Avoid running input wiring near ...

Страница 24: ...WISE 4471 Series User Manual 16 ...

Страница 25: ...Chapter 4 4 System Configuration ...

Страница 26: ...steps Please insert micro B USB cable here and be noted that it don t provide power for WISE module 4 Plug a DC power source into the Vs Vs pin of your module to turn on the power 4 2 Configuring WISE 4471 Using WISE Studio 4 2 1 Minimum System Requirements The minimum system requirements for WISE Studio are as follows Microsoft Windows 7 or above Internet Explorer 11 or above 4 2 2 Installing WIS...

Страница 27: ...bedded web page or you could open web page via browsers Communication Box In this box there are several communication interfaces for configuring different WISE modules The WISE 4471 series uses the USB serial interface for configuration Refresh Pressing this button refreshes the USB serial interface USB Serial This block is for connecting to a WISE module via USB The avail able USB serial port num...

Страница 28: ...be given here Cellular Information This block shows information on the cellular RF module and cellular network status PIN Status The PIN code status of the SIM card Register Status Registration status with the cellular network operator Current Service Mode Network service mode e g LTE CAT NB1 Signal Strength Indicates reference signal receiving power RSRP of the cel lular network IP Address IP add...

Страница 29: ... Connecting to a Cellular Network Enter the PIN Code First insert a SIM card into the WISE module and then go to the Configuration page and click the Cellular tab Enter the PIN of the SIM card in the PIN Authentica tion dialog box Selecting the Auto Write PIN Code check box will save the PIN code to the WISE module Cellular Information After the PIN code has been entered information on the cellula...

Страница 30: ...f the modem IMSI Code International Mobile Subscriber Identity of the SIM card Cellular Configuration After the SIM card has been inserted into the WISE module it can be configured in this page Auto Write PIN Code Enables the PIN code to be saved to the WISE module PIN Code Configure or modify the PIN code here Access Point Name APN Configure the APN of the cellular network provider ...

Страница 31: ...ion modes and can be configured from this page Channel Select the channel to be configured Tag Name Each channel can be given a tag name for identification Mode The operation mode of each channel can be configured here or chan nels can be disabled to improve the performance of enabled channels After a channel has been configured pressing Submit at the end of this page will apply the changes Channe...

Страница 32: ...xes increment 0 1 ms Counter When counter mode is selected for a given channel a counter will count the number of pulses in the digital signal from that channel and then record the value to the register In the Status page the current count value of the selected channel is displayed in the Counter value box The counter can be started stopped by pressing Start Stop which is located beside the counte...

Страница 33: ...t of fre quency for different kind of input range Value Reset Time function is design for deciding when will the frequency value been reset to zero if pulse bandwidth longer than expect Low to High Latch Under low to high latch mode once a digital input channel detects that the logic level has changed from low to high the logic status will remain as logic high until the latch is cleared manually w...

Страница 34: ... Series User Manual 26 4 2 6 2 Digital Output Status The values of all digital output channels can be controlled via the status switch the color of which indicates the current value of the digital output channel ...

Страница 35: ...n the WDT times out If the FSV check box is clear the module will set the output channel to logic low if the WDT times out To set the module so that the FSV is triggered by the WDT go to Net work App on the Configuration page to enable Communication WDT Trigger FSV for all of the module s output channels and then set the communication WDT mode to Communication WDT The default host idle time is 720...

Страница 36: ...lay when the output value changes from logic high to logic low The delay time can be set by entering its value in the Delay Time box on the Configuration page The digital output value can be controlled by clicking DO its current value can be viewed through the digital output status LED display in the DO Status page 4 2 6 3 COM1 RS 485 Port The WISE 4471 S250 has one RS 485 port for Modbus gateway ...

Страница 37: ...lve ID of RS 485 Modbus slave devices Slave Address Indicates the address of a bit or word from an RS 485 Modbus slave device For a writable bit or word you can click Edit to switch to edit mode here you can change the values and then click Apply to write the Modbus addresses individually Modbus Configuration Common Settings Tab In this tab you can configure the parameters of the RS 485 port Baud ...

Страница 38: ...has been submitted successfully Start Address Enter the first address number that you are going to poll The address base is 1 if you are going to polling the first address of a holding regis ter i e 40001 then simply enter the number 1 here you do not need to enter the entire address 40001 Length Enter the length of the address that you are going to poll in this rule For example if you are going t...

Страница 39: ... be logged in the data logger Deviation Change of Status COS When this check box has been set the difference of polling values between the current poll and the last poll can trigger the deviation COS change of state for push data or log data Rule Status The web configuration interface will check whether the rule set tings have any overlap or conflict The enabled rules which are enable the rule by ...

Страница 40: ...nnect a fifth host In this case if one of the hosts stops communicating with the WISE module for longer than the configured host idle time default 720 seconds for example the WISE module will close the TCP connection with the host Communication WDT After configuring Host Idle time and will be triggered when all TCP connections are closed This includes all hosts which visit WISE and also the commun...

Страница 41: ... User Manual Chapter 4 System Configuration Time Date WISE modules have a built in RTC that allows you to view the current time set the time zone and adjust the time by pressing Click Me to read the time from host devices ...

Страница 42: ...when clicking the icon System Restart This module s system will reboot when clicking the icon Firmware To update the firmware go to the Firmware page in System Configuration and click the icon of the file you wish to use in the update You can find the latest official firm ware releases on the Advantech support site http support advantech com ...

Страница 43: ...nute If you select the By Communication WDT check box the I O status will be logged once the WDT condi tion has been met All data can be stored even when the module is powered off You can clear all data in the logger when powering up the WISE module by selecting the Clear Log when Power Up check box When the memory is full the logger will stop logging unless you select the Circular Log when Memory...

Страница 44: ... for module diagnostics and troubleshooting You can decide type of system events you would like to log Logger Configuration On this page you can enable the local memory storage function There are separate switches for enabling the logging of I O data or system data Simply turn ON the switches to enable logging ...

Страница 45: ... and Time GMT format will have time stamps like 2015 08 27T15 20 29 08 00 and those that support Coordi nated Universal Time UTC format will have time stamps like 1440660089 After the data format has been selected the data can be filtered by selecting Amount of Latest Data to query a certain number of data entries or Time Filter to query data entries within a specific period of time To query all d...

Страница 46: ...ions such as the Private Server function data are extracted from the local memory of the WISE module You can pack data from the WISE data logger into a file and then push the file to a web server whenever the log condition is triggered The WISE module will push a notification in Json format to your private server You can switch the I O Log or System Log to ON and the WISE module will then start pu...

Страница 47: ...ation Cloud and select iSens ing MQTT Enter the Host Name of MQTT broker here we use public broker pro vided by HiveMQ for demonstration Then go to Advanced Data Logger Data Configuration user can decide the update period in Log Conditions The minimum update period is 10 second so user can configure 100 0 1 sec as following figure ...

Страница 48: ...ogger Configura tion and enable I O Log in Push Notification then WISE will star to update the data Please be noted that user need to unplug USB cable from the micro USB configura tion port on WISE before start updating data If the USB port been connected WISE will stop update data and waiting for configuration Go to HiveMQ web site http www hivemq com demos websocket client enter the Host and Por...

Страница 49: ... Subscriotions block and click Add New Topic Subscriotion Enter the topic Advantech IMEI_Code data you can find the IMEI code by WISE Studio it s in the page of Configuraiton Cellular Cellular Information After subsctibe the topic of WISE you can see the data from WISE ...

Страница 50: ...WISE 4471 Series User Manual 42 ...

Страница 51: ...Appendix A A iSensing MQTT ...

Страница 52: ...e networks Advantech iSensing MQTT is Advantech defined MQTT topic and payload for iSensing and iConnectivity devices including WISE 4000 wireless I O ADAM 6000 Ethernet I O and B B Wizard mesh I O There are two differences between WISE 4000 wireless I O and ADAM 6000 Ether net I O 1 WISE supports TLS SSL but ADAM does not 2 WISE uses web socket format package and ADAM uses TCP format package ...

Страница 53: ...pecial conditions Configuration Change c Configuration change affecting the reading e g scaling calibration 0 9 0 9 Digital Input di Digital Input Mode true false Counter 0 4294967295 Frequency Mode 0 30000 default unit 0 1Hz 0 300000 default unit 0 01Hz Digital Output do Digital Output true false Analog Input ai Engineering value of analog input 10000 000 10000 000 unit mV 20 000 20 000 unit mA T...

Страница 54: ...true do2 false ai1 0 763 ai2 0 763 ai3 0 763 ai4 0 763 The value of do1 and do2 can be false true The value of the sensor in engineering units if ai disable the value is 9999 9999 ai_st AI status number meaning 0 AI Channel disable 1 Streaming 2 High latch 3 High momentary 4 Low latch 5 Low momentary WISE 4050 4 DI 4 DO s 6 t 2017 11 03T15 06 16Z q 192 c 2 di1 true di2 false di3 true di4 false do1...

Страница 55: ...can be false true The value of do1 and do2 can be false true The value of coil can be true false The value of register can be 0x0 to 0xFFFF WISE 4470 S214 4 AI 4 DI s 1 t 2014 07 11T15 26 37Z q 192 c 1 ai1 1 234567 ai_st1 1 ai2 123 4567 ai_st1 2 di1 false di2 true The value of the sensor in engineering units if ai disable the value is 9999 9999 ai_st AI status number meaning 0 AI Channel disable 1...

Страница 56: ...ary 4 Low latch 5 Low momentary The value of di1 and di2 can be false true Note The channel number on WISE module is 0 based and the channel number of MQTT topic is 1 based For example DO0 of WISE mod ule use topic do1 Field Description Advantech Vendor of WISE Series MAC_Address MAC address of WISE Series doIndex The index of the DO channel Note that the index start with 1 Note The channel number...

Страница 57: ...ech MAC_Address ctl do2 v false The DO1 value will be set as false WISE 4470 S250UA 6 DI 2 DO 1 RS 485 Advantech MAC_Address ctl do3 v false The DO2 value will be set as false WISE 4471 S250UA 6 DI 2 DO 1 RS 485 Advantech MAC_Address ctl do1 v false The DO0 value will be set as true Note The channel number on WISE module is 0 based and the channel number of MQTT topic is 1 based For example DO0 of...

Страница 58: ...ations are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of the publisher All brand and product names are trademarks or registered trademarks of their respective companies Advantech Co Ltd 2018 ...

Отзывы: