WISE-4471 Series User Manual
24
Invert Signal:
WISE digital input channels support the invert digital input status
function. To enable/disable this, select the
Invert Signal
check box on the Con-
figuration page.
Digital Filter:
Digital input channels have a digital filter that can remove high-
frequency noise. The filter can be enabled/disabled by clicking the Digital Filter
check box. When the filter is enabled, the minimum acceptable signal width can
be defined in the
Min. Low Signal Width
and
Min. High Signal Width
boxes
(increment: 0.1 ms).
Counter:
When counter mode is selected for a given channel, a counter will
count the number of pulses in the digital signal from that channel and then
record the value to the register. In the
Status
page, the current count value of
the selected channel is displayed in the
Counter
value
box. The counter can be
started/stopped by pressing
Start/Stop
, which is located beside the counter
value. The counter can be reset (the value in the register will be initialized to the
startup value, which is zero by default) by clicking Reset. The predefined startup
value will be the value shown in the
Counter value
box. When this value is
reset, either by pressing
Reset
on the
Status
page or by issuing a command, it
Содержание WISE-4470 Series
Страница 1: ...User Manual WISE 4471 Series ...
Страница 9: ...Chapter 1 1 Product Overview ...
Страница 11: ...Chapter 2 2 Product Overview ...
Страница 16: ...WISE 4471 Series User Manual 8 2 5 Block Diagram Figure 2 5 WISE 4471 S250 Block Diagram ...
Страница 17: ...Chapter 3 3 Hardware Installation ...
Страница 24: ...WISE 4471 Series User Manual 16 ...
Страница 25: ...Chapter 4 4 System Configuration ...
Страница 50: ...WISE 4471 Series User Manual 42 ...
Страница 51: ...Appendix A A iSensing MQTT ...