UNO-1372G User Manual
24
SW7:
Digital Input
Input Channels: 3
–
Input Voltage (Wet Contact) Logic 0: 0~3 VDC (switch to 1 and 3)
Logic 1: 10 ~ 30 VDC
–
Input Voltage (Dry Contact) Logic 0: Open (switch to 2 and 4)
Logic 1: Shorted to GND
–
Input Current
10 VDC @ 2.67 mA
20 VDC @ 5.64 mA
30 VDC @ 8.91 mA
Digital output
Channels:3
–
Output Voltage: 5 ~ 30 VDC
–
Output Capability Sink: 24 mA max./channel
JP1:
1-2: control DO3 (default setting)
2-3: control PL LED