C.4 Software A/D Trigger — BASE+00H
You can trigger an A/D conversion from software, the card's on-board
pacer or an external pulse. If you select software triggering, a write to the
register BASE+00H with any value will trigger an A/D conversion.
Bits 1 and 0 of register BASE+09H select the trigger source. See pages
57 and 58 for BASE+09H register layout and programming information.
Table C-3 Register for Software A/D Trigger
C.5 A/D RangeControl — BASE+01H
Each A/D channel has its own individual input range, controlled by a
range code stored in on-board RAM. If you want to change the range
code for a given channel, select the channel as the start channel in register
BASE+02H, MUX scan (described in the next section), then write the
range code to bits 0 to 3 of BASE+01H.
Table C-4 Register for A/D Range Control
G3 ~ G0
A/D range control
G0
the least significant bit (LSB) of the A/D range
G3
the most significant bit (MSB)
Write
Software A/D trigger
Bit #
7
6
5
4
3
2
1
0
BASE + 00H
X
X
X
X
X
X
X
X
Write
A/D range control
Bit #
7
6
5
4
3
2
1
0
BASE + 01H
X
X
X
X
G3*
G2*
G1
G0
Содержание PCL-818 Series
Страница 1: ...PCL 818 Series 12 bit ISA Multifunction Card User Manual ...
Страница 14: ...PCL 818 Series User Manual 6 Figure 1 1 Installation Flow Chart ...
Страница 28: ...PCL 818 Series User Manual 20 ...
Страница 45: ...2 APPENDIX A Specifications ...
Страница 49: ...2 APPENDIX B Block Diagram ...
Страница 51: ...2 APPENDIX C Register Structure Format ...
Страница 71: ...2 APPENDIX D Calibration ...