2 ADAM-4510/4510S/4520 Startup Manual
• Automatic internal RS-485 bus supervision
• No external flow control signals required for RS-485
• Minimum 3000 V
DC
isolation (ADAM-4510S/4520)
• Transient suppression on RS-485 data lines
• Baudrate up to 115.2 kbps
• Networking up to 4000 feet
• Reserved space for termination resistors
• Power and data flow indicator for troubleshooting
• Power requirement: +10 to +30 V
DC
• Mounts easily on DIN-rail or panel
Common
• Power Requirement:
Unreg10 to +30 V
DC
with protection from power
reversals
• Case: ABS with captive mounting hardware
• Accessories (Supplied):
DIN-rail Mounting Adapter
Panel Mounting Bracket
• Plug-in screw terminal wiring:
Accepts AWG 1-#12 to #22 (0.5 to 2.5 mm) wires
• Operating Temperature:
-10 ~ 70° C (14 ~ 158° F)
• Storage Temperature: -25 ~ 85° C (13 ~ 185° F)
• Humidity: 5 ~ 95%, non-condensing
ADAM-4510/4510S Specifications
• Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 k, 38.4 k,
57.6 k, 115.2 k, RS-422 (switchable)
• Isolation Voltage: 3000 V
DC
(4510S only)
• RS-422/RS-485 interface connector: plug-in screw termi-
nal
• Power Consumption: 1.4 W
ADAM-4520 Specifications
• Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 k, 38.4 k,
57.6 k, 115.2 k, RTS control and RS-422 mode (switchable)
• Isolation Voltage: 3000 V
DC
• RS-232 Interface Connector: Female DB-9
• RS-422/RS-485 Interface Connector: plug-in screw termi-
nal
• Power Consumption: 1.2 W
Switch Descriptions
DIP switches in the ADAM converter and repeater mod-
ules set the data format (number of bits) and baudrate for
the ADAM network. You can configure the other modules
in the network via software commands. Your program and
the PC's serial port should match the settings of the con-
verter and repeater modules.
SW1
Switch 1 controls the data format. Data can be 9, 10, 11 or
12 bits. The factory default is 10 bits: one start bit, eight
data bits, no parity bit and one stop bit.
When using the converter in combination with other
ADAM modules, do not change the default setting as
ADAM modules have a fixed data format of ten data bits.
The option of changing to 9, 11 or 12 bits is for use with
other modules (other than ADAM modules) that have dif-
ferent data formats. Should you change the data format,
be aware that you will have to change the data format set-
tings on all the other modules in the network.
SW2
Switch 2 sets the baudrate. The options range from 1200
bps to 115.2 kbps. The factory default is 9600 bps. Be
aware that when you change the baudrate, you have to
change the baudrate for all the connected modules
accordingly. If the RS-422 mode is ON, the baudrate
doesn't need to be set.
Default Settings
Both Modules are not addressable by the host computer,
the baud rate and data format must be set using SW1 and
SW2 located inside the module. The default settings are:
Function
Setting
Baud rate
9600 bps
Data format
10 bits
Data Format Settings (SW1)
Features
Specifications
Switch Settings
9 bits
10 bits
(default)
11 bits
12 bits
1
2
O N
1
2
O N
1
2
O N
1
2
O N