2    ADAM-4510/4510S/4520  Startup Manual

 

•  Automatic internal RS-485 bus supervision

•  No external flow control signals required for RS-485

•  Minimum 3000 V

DC

 isolation (ADAM-4510S/4520)

•  Transient suppression on RS-485 data lines

•  Baudrate up to 115.2 kbps

•  Networking up to 4000 feet

•  Reserved space for termination resistors

•  Power and data flow indicator for troubleshooting

•  Power requirement: +10 to +30 V

DC

•  Mounts easily on DIN-rail or panel 

Common

•  Power Requirement:

Unreg10 to +30 V

DC

 with protection from power 

reversals

•  Case: ABS with captive mounting hardware

•  Accessories (Supplied):

DIN-rail Mounting Adapter
Panel Mounting Bracket

•  Plug-in screw terminal wiring:

Accepts AWG 1-#12 to #22 (0.5 to 2.5 mm) wires

•  Operating Temperature

-10 ~ 70° C (14 ~ 158° F)

•  Storage Temperature: -25 ~ 85° C (13 ~ 185° F)

•  Humidity: 5 ~ 95%, non-condensing

ADAM-4510/4510S Specifications

•  Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 k, 38.4 k, 

57.6 k, 115.2 k, RS-422 (switchable)

•  Isolation Voltage: 3000 V

DC 

(4510S only)

•  RS-422/RS-485 interface connector: plug-in screw termi-

nal

•  Power Consumption: 1.4 W

ADAM-4520 Specifications

•  Baudrate (bps): 1200, 2400, 4800, 9600, 19.2 k, 38.4 k, 

57.6 k, 115.2 k, RTS control and RS-422 mode (switchable)

•  Isolation Voltage: 3000 V

DC

•  RS-232 Interface Connector: Female DB-9

•  RS-422/RS-485 Interface Connector: plug-in screw termi-

nal

•  Power Consumption: 1.2 W

Switch Descriptions

DIP switches in the ADAM converter and repeater mod-
ules set the data format (number of bits) and baudrate for 
the ADAM network. You can configure the other modules 
in the network via software commands. Your program and 
the PC's serial port should match the settings of the con-
verter and repeater modules.

SW1

Switch 1 controls the data format. Data can be 9, 10, 11 or 
12 bits. The factory default is 10 bits: one start bit, eight 
data bits, no parity bit and one stop bit.

When using the converter in combination with other 
ADAM modules, do not change the default setting as 
ADAM modules have a fixed data format of ten data bits. 
The option of changing to 9, 11 or 12 bits is for use with 
other modules (other than ADAM modules) that have dif-
ferent data formats. Should you change the data format, 
be aware that you will have to change the data format set-
tings on all the other modules in the network.

SW2

Switch 2 sets the baudrate. The options range from 1200 
bps to 115.2 kbps. The factory default is 9600 bps. Be 
aware that when you change the baudrate, you have to 
change the baudrate for all the connected modules 
accordingly. If the RS-422 mode is ON, the baudrate 
doesn't need to be set.

Default Settings

Both Modules are not addressable by the host computer, 
the baud rate and data format must be set using SW1 and 
SW2 located inside the module. The default settings are:

Function

Setting

Baud rate

9600 bps

Data format

10 bits

Data Format Settings (SW1)

Features

Specifications

Switch Settings

9 bits

10 bits
(default)

11 bits

12 bits

1

2

O N

1

2

O N

1

2

O N

1

2

O N