Local Time Configuration

You can see the current time here, decide which time zone for your local time, and also do 
the time calibration by read the time from host devices.

SNTP Configuration

You can enable the SNTP function, so the module can act as a SNTP client to do time syn-
chronization from assigned SNTP server.

Modbus Configuration

In this page, you can choose which Modbus address mode you want to use. Default 
Address means apply the Modbus by the default setting. Auto-Allocate Address means the 
Modbus address will be allocated automatically. Different from default Modbus address, it 
will fill in the unused address. Basically, there're two kinds of Modbus address section (0X 
and 4X) for you to configure each function item.

Содержание ADAM-3600-A1F

Страница 1: ...User Manual ADAM 3600 A1F Intelligent Remote I O Module ...

Страница 2: ... Advantech assumes no liability under the terms of this warranty as a consequence of such events Because of Advantech s high quality control standards and rigorous testing most of our customers never need to use our repair service If an Advantech product is defec tive it will be repaired or replaced at no charge during the warranty period For out of warranty repairs you will be billed according to...

Страница 3: ...ause harmful interference to radio communications Opera tion of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense Technical Support and Assistance 1 Visit the Advantech web site at www advantech com support where you can find the latest information about the product 2 Contact your dist...

Страница 4: ...pour any liquid into an opening This may cause fire or electrical shock 13 Never open the equipment For safety reasons the equipment should be opened only by qualified service personnel 14 If one of the following situations arises get the equipment checked by service personnel The power cord or plug is damaged Liquid has penetrated into the equipment The equipment has been exposed to moisture The ...

Страница 5: ... Relay Output Wiring 10 Figure 2 2 Relay Output Wiring 10 2 4 Pin Assignment 10 Chapter 3 Hardware Installation 11 3 1 Interface Introduction 12 3 2 Mounting 12 3 2 1 DIN Rail Mounting 12 Figure 3 1 DIN Rail Installation 12 3 2 2 Wall Mounted Installation 13 Figure 3 2 Wall Mounted Installation 13 3 2 3 Expansion Module Installation 13 Figure 3 3 Expansion Module Installation 13 Figure 3 4 Expansi...

Страница 6: ... 1 Operation Framework 37 4 4 Configuring ADAM 3600 A1F with ADAM NET Utility software 41 Appendix A I O Modbus Mapping Table 45 A 1 Modbus Function Code Introduction 46 A 2 ADAM 3600 A1F Default Modbus Mapping Table 46 A 3 Auto Allocated Modbus Address 48 Appendix B REST for ADAM 3600 A1F 51 B 1 Introduction 52 B 2 REST Resources for ADAM 3600 A1F 53 B 2 1 Digital Input 53 B 2 2 Digital Output 58...

Страница 7: ...Chapter 1 1 Product Overview ...

Страница 8: ...age Function File based cloud storage and data log function makes the data can be access at any time and in anywhere User will never need to care about how to collect the data into any data logger or data gateway 1 2 3 Access by Mobile Devices Direct mobile devices access functions make the information easier to been access With 3 levels security these data can storage access and publish in more s...

Страница 9: ...3 ADAM 3600 A1F User Manual Chapter 1 Product Overview 1 4 Mechanical Design and Dimensions 1 4 1 ADAM 3600 A1F ...

Страница 10: ...ow voltage of RTC battery Link Speed 1 Green Link 1 ON Ethernet is connected Blink When TX RX is in transmission Yellow Speed 1 ON OFF ON Ethernet speed is at 100 Mbps OFF Ethernet speed is at 10 Mbps Link Speed 2 Green Link 2 ON Ethernet is connected Blink When TX RX is in transmission Yellow Speed 2 ON OFF ON Ethernet speed is at 100 Mbps OFF Ethernet speed is at 10 Mbps Digital Input Green ON O...

Страница 11: ...n and Safety Standards FCC FCC 47 CFR PART 15 Class A IC ICES 003 CE EN 55011 55022 Class A EN 61000 6 4 EN 61000 3 2 EN 61000 3 3 EN 55024 EN 61000 6 2 IEC 61000 4 2 IEC 61000 4 3 IEC 61000 4 4 IEC 61000 4 5 IEC 61000 4 6 IEC 61000 4 8 IEC 61000 4 11 RoHS China RoHS WEEE ...

Страница 12: ...ADAM 3600 A1F User Manual 6 ...

Страница 13: ...Chapter 2 2 Product Specifications ...

Страница 14: ...wer Input Voltage 10 30 VDC 24 VDC Standard Software Configuration Interface Web Interface Windows Utility Driver ADAM APAX NET Class Library Industrial Protocol Modbus TCP Supported Protocols TCP IP UDP HTTP DHCP ARP SNTP Supports RESTful Web API in JSON format Supports Web Server in HTML5 with JavaScript CSS3 Reset Button Users can push the Reset button on the left panel of the ADAM 3600 A1F to ...

Страница 15: ...pecifications Channel 16 Wet Contact Uni direction Logic 0 0 5 VDC Logic 1 10 30 VDC Isolation Protection 2500 VDC Max Input Frequency 3 kHz Max Counter Frequency 3 kHz Channel 8 Form A Contact Rating resistive load 250 VAC 5A 30 VDC 5 A Max Switching Rate 20 operations minute Breakdown voltage 500VAC 50 60Hz Relay operation time On 10ms Off 5ms Mechanical Endurance 20 Million operations Insulatio...

Страница 16: ...DAM 3600 A1F User Manual 10 2 3 2 Relay Output Wiring Figure 2 2 Relay Output Wiring 2 4 Pin Assignment Channel Symbol 0 1 2 3 4 5 6 7 8 9 A B C E D F Channel Number 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 ...

Страница 17: ...Chapter 3 3 Hardware Installation ...

Страница 18: ...s 3 2 1 DIN Rail Mounting The ADAM 3600 A1F can also be fixed to the cabinet by using mounting rails You need to assemble the DIN rail adapter to the module with flathead screw driver as below When the module is mounted on a rail you may also consider using end brackets at each end of the rail to keep the module from sliding horizontally along the rail Figure 3 1 DIN Rail Installation ...

Страница 19: ...al Chapter 3 Hardware Installation 3 2 2 Wall Mounted Installation Figure 3 2 Wall Mounted Installation 3 2 3 Expansion Module Installation Figure 3 3 Expansion Module Installation Figure 3 4 Expansion I O Connector Installation ...

Страница 20: ...er ripple and the immediate ripple voltage should be maintained between 10 and 30 VDC Screw terminals PWR and PWR are for power supply wiring Figure 3 5 Power Supply Wiring 3 3 2 Ethernet Daisy Chain Wiring The ADAM 3600 A1F module has built in Ethernet switches to allow daisy chain con nections in an Ethernet network making it easier to deploy and helping improve scalability The two Ethernet port...

Страница 21: ...considered when connect ing electrical devices to I O modules 1 The terminal block accepts wires from 0 5 mm to 2 5 mm 2 Always use a continuous length of wire Do not combine wires 3 Use the shortest possible wire length 4 Use wire trays for routing where possible 5 Avoid running wires near high energy wiring 6 Avoid running input wiring in close proximity to output wiring 7 Avoid creating sharp b...

Страница 22: ...ADAM 3600 A1F User Manual 16 ...

Страница 23: ...Chapter 4 4 System Configuration ...

Страница 24: ...s below Safari 6 in Apple iOS Web Browser in Google Android 4 0 Ice Cream Sandwich Chrome in Google Android 4 0 Ice Cream Sandwich For PC platforms the minimum requirement of web browsers as below Internet Explorer version 11 Google Chrome version 30 Mozilla Firefox version 25 4 2 2 List of ADAM 3600 A1F Default Ethernet Ports Mobile Browse Chrome Android Safari Configuration Y Y Y File Upload N N...

Страница 25: ...1 Subnet Mask 255 0 0 0 Default Gateway 0 0 0 0 Default Connection Timeout 720 second HTTP Port 80 4 2 4 Module Authorization Account Default Password Access Ability Root 00000000 All the privileges Admin 00000000 All the privileges except access control configuration User 00000000 View module status only not allow to do configuration ...

Страница 26: ...en open the browser of your computer or mobile device 2 Enter IP address of module with config for example the default URL http 10 0 0 1 config 3 Then you will see the login page please enter the account and pass word then click Login button 4 After login you will see the Informa tion page 5 Scroll down the tab you can change the login user here 6 You can switch to other pages by choosing the sele...

Страница 27: ...onfiguration to perform the configuration Users can view the basic information of the module Users can view Module ID Custom ID Location and Description of the module Users can view the Network information of the module Users can see which expansion modules are installed in the ADAM 3600 A1F ADAM 3600 A1F is always at Slot 0 then Slot 1 4 correspond to 4 expansion module slots in sequence ...

Страница 28: ...oose the Information tab then user can edit Module Information which contains Customized Name Universally Unique Identifier UUID and Description Users can edit the location information for the module While the edition of Module and Location Information had been completed click the button Submit to restore the new infor mation ...

Страница 29: ...n set the sub net address and default gateway in this page For DIP Switch IP mode users can set the IP address by setting the 6 bit DIP switch on the right up corner of ADAM 3600 A1F For example if the default IP is 192 136 0 38 and after you adjust the DIP Switch IP shown in the figure below the IP address will become 192 136 0 8 Note If the DIP switch was set to 0 it will keep the original IP ad...

Страница 30: ...a SNTP client to do time syn chronization from assigned SNTP server Modbus Configuration In this page you can choose which Modbus address mode you want to use Default Address means apply the Modbus by the default setting Auto Allocate Address means the Modbus address will be allocated automatically Different from default Modbus address it will fill in the unused address Basically there re two kind...

Страница 31: ... the module will be cleared and restored to factory default after it s clicked Reset Password You can reset the password here System Restart The system of this module will reboot after it s clicked General Configuration You can set the Scan interval in this page After Communication WDT has been enabled in Network App tab you can enable the IO FSV triggered by communica tion WDT Firmware Update You...

Страница 32: ...t0 ADAM 3600 A1F Click it the onboard I O statuses are shown in this page For the output status you can also change the I O status here If ADAM 3600 A1F has been installed with expansion I O mod ules then the user will see the other options which corresponding to the expansion I O mod ules They can check and change the I O statuses of the expansion modules in that page too ...

Страница 33: ...n do detail I O setting in the configuration tab that include the Tag Name Invert Sig nal enable Digital Filter and also the working mode of each channel In the end there is an overview table for the configuration summary of each channel Trend The status trend of I O will be shown here ...

Страница 34: ...ADAM 3600 A1F User Manual 28 Relay setting The user can also check and change the local Relay output statuses in the Relay related pages that included Status Configuration and Trend ...

Страница 35: ...al Chapter 4 System Configuration Advanced Functions There are 3 advanced functions which contained Access Control Data Logger and Diagnosti cian Access Control The status trend of I O will be shown here Data Logger Diagnostics ...

Страница 36: ... in storage memory here Log Conditions The log period can be decided in By Period box Pleased been noted that the period is increased by 0 1seconds It means if user set 600 here the status of the I O will be logged each minute Otherwise If the communication WDT been enable and user also choose By Communication WDT Log once the condition of WDT had been met the status of I O will be logged General ...

Страница 37: ...er to log the data when the I O status is changed by check the box of Change of State Tab Local Viewer Query Format User can configure which kind of ID and the timestamp format will be logged here Query Filter This filter is for setting the criteria to query the logged data User can select the filter mode and click Query button to query the logged data ...

Страница 38: ... in the internal memory at the field Current Total Amount Users can set how many records of data with different timestamps they want to query by setting the field Total Amount Note The data querying page had supported the data drawing function However if there were too much data had been drawn on the web page it would cause the web browser at the state of over loading Thus we set the limitation th...

Страница 39: ... for each log way Event or Periodic also would be drawn at Log Type Proportion area The explanation of I O Type is indicated in the form below Users also can see the data trend in Value Trend area I O Type Description 1 The digital input is in general DI mode 2 The digital input is in Counter mode 3 The digital input is in Frequency mode 4 The digital output is in general DO mode 5 The digital out...

Страница 40: ... the data list in Data area Select Media Storage and choose the Media Log Configuration tab users can enable the data logger function in the external storage device and choose to use USB Thumb or SD card as the storage device In the field of Data Format you can see the data will be stored in CSV format ...

Страница 41: ...of the oldest file and the latest file in the storage device Then users can set the time period by setting Start Time and End Time This period has to be between the oldest time stamp and the latest timestamp Then they can query the files in the storage device that the timestamps in this period If users select Amount of Latest Files Filter they can see the total number of files in the stor age devi...

Страница 42: ...a main folder ADAM_log in the external storage device It would contain the first sub folders which named with the index 0 and the logged file would be stored in the sub folder The file name would be the last two bytes of the MAC address and the index started from 0 The indication of the CSV file format is shown below ...

Страница 43: ...tion as below Now you can define the network mode of the module in the beginning After that you will be able to perform other settings 4 3 1 Operation Framework The operation window mainly contains 4 areas including Menu Toolbar Module Tree screen and Main Operation screen 4 3 1 1 Menu a File Open Favorite Group You can import the favorite configuration group file XML from your computer Save Favor...

Страница 44: ...Screen Group Configuration Group Configuration is on ADAM 3600 A1F module It can help you efficiently configure or maintain massive ADAM 3600 A1F modules with the same config uration file or firmware upgrade at one time in the local network The following steps will instruct you how to operate it Terminal for Command Testing The ADAM 3600 A1F module Modbus TCP as communication protocol so you can l...

Страница 45: ...on is used to add serial COM ports in ADAM NET Utility You won t need to use this option for ADAM 3600 A1F modules Show TreeView Check this option to display the Module Tree Screen area Allow Calibration Check this option to allow calibration function enabled on AI O module d Help Check Up to Date on the Web It will automatically connect to support and download page of Advantech web site when it e...

Страница 46: ...ht click on the ADAM 3600 A1F item under the Favorite Group item and you can select Add New Group to create a new group After you create your own group right click on your group and Add New Device into your group You can also select Diagnose con nection to check the communication ADAM 4500_5510 Series This is a DOS interface utility for remote controllers such as ADAM 4500 and ADAM 5510 series Wir...

Страница 47: ... as the same domain as ADAM 3600 A1F module For the new ADAM 3600 A1F which default IP address is 10 0 0 1 the IP address of computer can be configured as 10 0 0 99 for example as follow ing 2 Open the Adam Apax NET Utility then you can see the IP address of computer been shown under Ethernet tree You can right click to refresh the subnodes of this tree Or click Search Device to find ADAM 3600 A1F...

Страница 48: ...vious section 5 There are some function provide in same pages in utility first you can enter the account and password faster in Login Info tab 6 In the Device Info tab the detail information of this module will been shown 7 The QR tab will generate the QR code of the web configuration web page for mobile device to access the module User can also click the QR code to open the browser for further co...

Страница 49: ...in the same domain as the computer after power up and searching for it in the utility the device name will been shown in the Others tree Users have to change the device network setting to the same domain with the computer in the page as below Then the module just can be accessed by the computer ...

Страница 50: ...ADAM 3600 A1F User Manual 44 ...

Страница 51: ...Appendix A A I O Modbus Mapping Table ...

Страница 52: ...ibute Digital Input Default Coil Base 00001 Default Register Base 40001 00001 00016 0 15 0 DI Value 1 addr ch Read 40001 40032 0 15 0 Counter value 2 addr ch Read 00017 00032 0 15 1 Read 40033 40064 0 15 1 Read 00033 00048 0 15 2 Read 40065 40096 0 15 2 Read 00049 00064 0 15 3 Read 40097 40128 0 15 3 Read 00065 00080 0 15 4 Read 40129 40160 0 15 4 Read 00101 00116 0 15 0 Counter Start Stop 1 addr ...

Страница 53: ... 41033 41064 0 15 1 R W 01033 01048 0 15 2 R W 41065 41096 0 15 2 R W 01049 01064 0 15 3 R W 41097 41128 0 15 3 R W 01065 01080 0 15 4 R W 41129 41160 0 15 4 R W 41301 All 0 DO Value R W 41302 All 1 R W 41303 All 2 R W 41304 All 3 R W 41305 All 4 R W 41401 41432 0 15 0 Pulse Output High Level Width 2 addr ch R W 41433 41464 0 15 1 R W 41465 41496 0 15 2 R W 41497 41528 0 15 3 R W 41529 41560 0 15 ...

Страница 54: ... 40219 40220 4 Read 00501 00516 0 15 0 Clear Overflow 1 addr ch R W 40221 40222 0 FW Major Ver 2 addr module Read 00517 00524 0 7 1 R W 40223 40224 1 Read 40225 40226 2 Read 00601 00616 0 15 0 DI Latch Status 1 addr ch R W 40227 40228 3 Read 00617 00624 0 7 1 R W 40229 40230 4 Read 40231 40232 0 FW Build Ver 2 addr module Read 40233 40234 1 Read 40235 40236 2 Read 40237 40238 3 Read 40239 40240 4 ...

Страница 55: ...49 ADAM 3600 A1F User Manual Appendix A I O Modbus Mapping Table 41801 41816 0 7 0 Set Incremental Pulse 2 addr ch R W 41817 41832 0 7 2 R W ...

Страница 56: ...ADAM 3600 A1F User Manual 50 ...

Страница 57: ...Appendix B B REST for ADAM 3600 A1F ...

Страница 58: ...ponse and message delivery It can be developed compatible with popular protocols or standards like HTTP URI JSON HTML With the advantage of scalabil ity simplicity and performance it s already adopted in Web service by Amazon Yahoo The Web service of is developed based on HTML5 language if user need to integrate this into other Web services the following information command list should be referred...

Страница 59: ...on Retrieves information about the digital input value resource on specific slot URL Structure http 10 0 0 1 di_value slot_index http 10 0 0 1 di_value slot_index ch_num HTTP Method GET Returns the representation of all of digital input value resource PUT Replace all of digital input value resource PATCH Apply partial modifications to digital input value resource ...

Страница 60: ...ntent type application json Response 200 OK DIVal Ch 0 Md 0 Stat 1 Val 1 Cnting 0 ClrCnt 0 OvLch 0 Ch 1 Md 0 Stat 0 Val 0 Cnting 0 ClrCnt 0 OvLch 0 Ch 2 Md 1 Stat 0 Val 3378 Cnting 1 ClrCnt 0 OvLch 0 Ch 3 Md 3 Stat 0 Val 1 Cnting 0 ClrCnt 0 OvLch 0 Request GET di_value slot_0 ch_2 Content type application json Response 200 OK Ch 2 Md 0 Stat 1 Val 1 Cnting 0 ClrCnt 0 OvLch 0 ...

Страница 61: ... di_value slot_0 Content type application json DIVal Ch 0 Md 0 Stat 0 Val 0 Cnting 0 ClrCnt 0 OvLch 0 Ch 1 Md 0 Stat 0 Val 0 Cnting 0 ClrCnt 0 OvLch 0 Ch 2 Md 1 Stat 0 Val 3378 Cnting 0 ClrCnt 1 OvLch 0 Ch 3 Md 3 Stat 0 Val 0 Cnting 0 ClrCnt 0 OvLch 0 Response 200 OK Request PUT di_value slot_0 ch_2 Content type application json Ch 2 Md 1 Stat 0 Val 3378 Cnting 0 ClrCnt 1 OvLch 0 Response 200 OK ...

Страница 62: ...el Request PATCH di_value slot_index ch_num Example Request PATCH di_value slot_0 Content type application json DIVal Ch 2 Cnting 1 Ch 3 OvLch 0 Response 200 OK Request PATCH di_value slot_0 ch_3 Content type application json Ch 3 ClrCnt 1 Response 200 OK Field Abbreviation Data Type Array of Digital input configurations DIVal Array ...

Страница 63: ...tart Stop counter counting Read 1 counter is counting 0 not counting Write 1 start counting 0 stop counting Clear Counter ClrCnt Number W 1 Clear the counter value Get Clear Counter Overflow or Latch Sta tus OvLch Number RW counter overflow or latch status Read 1 overflow latch occurred 0 no overflow or latch Write 0 clear the overflow or latch status 0 DI 1 Counter 2 LowToHighLatch 3 HighToLowLat...

Страница 64: ...gital output value resource on specific slot URL Structure http 10 0 0 1 do_value slot_index http 10 0 0 1 do_value slot_index ch_num HTTP Method GET Returns the representation of all of digital output value resource PUT Replace all of digital output value resource PATCH Apply partial modifications to digital output value resource ...

Страница 65: ...GET do_value slot_0 Content type application json Response 200 OK DOVal Ch 0 Md 0 Stat 1 Val 1 PsCtn 0 PsStop 0 PsIV 0 Ch 1 Md 0 Stat 0 Val 0 PsCtn 0 PsStop 0 PsIV 0 Ch 2 Md 1 Stat 1 Val 3378 PsCtn 0 PsStop 0 PsIV 0 Ch 3 Md 3 Stat 1 Val 1 PsCtn 0 PsStop 0 PsIV 0 Request GET do_value slot_0 ch_2 Content type application json Response 200 OK Ch 2 Md 0 Stat 1 Val 1 PsCtn 0 PsStop 0 PsIV 0 ...

Страница 66: ...lot_0 Content type application json DOVal Ch 0 Md 0 Stat 1 Val 1 PsCtn 0 PsStop 0 PsIV 0 Ch 1 Md 0 Stat 0 Val 0 PsCtn 0 PsStop 0 PsIV 0 Ch 2 Md 1 Stat 1 Val 3378 PsCtn 0 PsStop 0 PsIV 0 Ch 3 Md 3 Stat 1 Val 1 PsCtn 0 PsStop 0 PsIV 0 Response 200 OK Request PUT do_value slot_0 ch_2 Content type application json Ch 2 Md 2 Stat 0 Val 0 PsCtn 0 PsStop 0 PsIV 0 Response 200 OK ...

Страница 67: ..._index Single Channel Request PATCH do_value slot_index ch_num Example Request PATCH do_value slot_0 Content type application json DOVal Ch 2 Md 2 Ch 3 PsStop 1 Response 200 OK Request PATCH do_value slot_0 ch_3 Content type application json Ch 3 PsCtn 1 Response 200 OK Field Abbreviation Data Type Array of Digital input configurations DOVal Array ...

Страница 68: ...s or set its status Pulse Output Get or set the absolute pulse count value LowToHighDelay Get the current signal status or set its status HighToLowDelay Get the current signal status or set its status Pulse Output Continue State PsCtn Number RW 1 0 Pulse outputting is continuous or not Stop Pulse Output PsStop Number W 1 Stop the pulse outputting Continue is disabled Absolute and incremental value...

Страница 69: ...63 ADAM 3600 A1F User Manual Appendix B REST for ADAM 3600 A1F ...

Страница 70: ...ations are subject to change without notice No part of this publication may be reproduced in any form or by any means electronic photocopying recording or otherwise without prior written permis sion of the publisher All brand and product names are trademarks or registered trademarks of their respective companies Advantech Co Ltd 2015 ...

Отзывы: