Titan Central Chillers
Page: 48
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: [email protected]
C.
In normal running mode the head pressure and
the suction pressure for a single refrigerant zone
is continuously displayed. The small arrows along
the bottom of the display window indicate that
the relay contacts are closed and the system is
functional.
D.
When either the head pressure or suction
pressure is measured out of the set point range
the corresponding arrows will disappear. If the
head pressure is out of range the red LED will
come on and the reset button will have to be
manually pushed after the condition has been
corrected.
E.
If the suction pressure is out of range
the system will reactivate automatically
after the pressure rises above the
differential value.
3.14 DIGITAL PRESSURESTAT SET UP
A.
Some models of this central chiller provide optional digital pressurestats for refrigerant
high and low pressure monitoring and display in lieu of traditional analog gauges.
B.
The digital refrigerant pressurestat is a dual pressure safety switch as well as a current
value refrigerant pressure display that uses transducers with a 0-10v output an in input
source.
RESET TRIP
REFRIGERANT PRESSURESTAT
HEAD
PRESSURE
SUCTION
PRESSURE
SET UP
TOGGLE DISPLAY
SET DOWN
539
505
Head Pressure Trip
LED Indicator
Head Pressure
Reset Button
Increase Button
Change Screen Button
Decrease Button
Head Pressure Value
Relay Contacts Closed Indicator
Head Pressure
Relay Contacts Closed Indicator
Suction Pressure
Suction Pressure Value
HEAD
PRESSURE
SUCTION
PRESSURE
Power Up
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
RESET TRIP
HEAD
PRESSURE
SUCTION
PRESSURE
539
505
HEAD
PRESSURE
SUCTION
PRESSURE
675
505
Содержание Titan
Страница 2: ......
Страница 6: ...Page 6 THIS PAGE INTENTIONALLY BLANK ...
Страница 24: ...Page 24 THIS PAGE INTENTIONALLY BLANK ...
Страница 50: ...Page 50 THIS PAGE INTENTIONALLY BLANK ...
Страница 58: ...Page 58 THIS PAGE INTENTIONALLY BLANK ...
Страница 74: ...Page 74 THIS PAGE INTENTIONALLY BLANK ...
Страница 94: ...END 2021 ADVANTAGE ENGINEERING INC RE 20210407 ...