background image

8

Calibration

Control Set

Setpoint 500.0

Diff 050.0

Direction: Rise

High Alarm 700.0

Low Alarm 300.0

Limit hh:mm

Display Units: mA

Decimal:  XXX.X

  4mA =  000.0

20mA = 999.9

Timer Set

Pulse

Run After 0100

Run Time mm:ss

Post Control

010% of Cntrl

Limit Time hh:mm

With Control

Limit Time hh:mm

Alarm Control

Batch

Run Tim mm:ss

28-Day (Bio)

A: All Days

A: All Weeks

A: Start 12:00a

A: Run Time hh:mm

A: Prbld hh:mm

A: Lkout hh:mm

B: All Days

B: All Weeks

B: Start 12:00a

B: Run Time hh:mm

B: Prbld hh:mm

B: Lkout hh:mm

Recycle

Off Time hh:mm

Run Time mm:ss

Utility

Only shows

if WM active  

Water Meter

Clock Set

Force Set

Diagnostics

Password 0000

Reset Meter? N

Set Time

Force On: Both

Nano-4-20

Flow Sw: Close

Meter Units

Set Date

FW: ?.?.?

DigIn: W Meter

Meter Value

Set Day & Week

Test Keypad

Meter Debounce

Test Display

R1 Cntrl mm:ss

Reset Cal? N

R2 Timer mm:ss

Feed OK w/Ctrl

No Feed No Flow

Raw A/D: ????

Digi 0/1

If Yes is selected the

current calibration A/D 

values are stored.

If a Reset Cal is done

these A/D values are 

restored for the 4 & 20. 

0-32,767 scale

Identify logic

state of vaious

digital inputs.

Only shows

if WM active  

Pulse: ON

4-20 Output

4 mA = 000.0

Sim 4mA:  OFF

20mA= 999.9

Sim 20mA: OFF

Pulse Output

HiMax = 0125

HiRate= 700.0

HiMax should

match pump 

max stroke/ min

speed rate.

LoRate is sensor

reading desired

for slowest pulse

output.

Hi Rate is sensor

reading for high

pulse rate.

LoRate= 000.0

Set 4 and 20mA 

out at desired 

sensor reading.

Sim 4 and 20mA

will force output

to either 4 or 20

regardless of 

reading.

4mA applied: N

4mA In:  04350

20mA applied: N

20mA In:  21350

Press Enter only

if a 4mA or 20mA

signal is being

received when in

those calibration

screens.

Select if Pulse

Output of mA

input is on/off  

  Set the decimal

for displayed 

numerical format

and the 4mA and 

20mA for what the

value of that range

desired at those 

two mA values  

CAL 20: 2948

CAL 4:  0590

Set Default? N

Increase the

Debounce to

prevent false

contacts.

Set to 0 when

a paddle wheel

meter is used. 

The CAL 4 or 20

can be used to 

change the signal

of either the 4 or 

20 value to match

those two points 

with the recieving

device  

Disabled

Select WM or 

Drum Level for

relay 1 , relay

2 or 1 & 2  

Содержание NANO-N

Страница 1: ... mA Input Installation Maintenance Repair Manual Advantage Controls 4700 Harold Abitz Dr Muskogee OK 74402 Phone 918 686 6211 Fax 888 686 6212 www advantagecontrols com email support advantagecontrols com 4 2019 ENTER ...

Страница 2: ...nstallation Mounting Instructions 4 Electrical Wiring 4 Relay Cards 4 Logic Cards 5 IV Front Panel Description 6 V System Operation Overview 6 Description of Menus 6 VI Maintenance 7 VII Troubleshooting 7 VIII NanoTron mA Menu Map 8 IX Warranty 30 Day Billing Memo Policy 10 ...

Страница 3: ...her external devices via two control relay outputs The pulse output can pace a metering pump or convert a mA flow rate into contact style water meter pulses like used in a MegaTron Follow the steps below to program the Pulse Out based on the mA range of the flow device using an example of 500 gpm as the max 20mA signal 1 In the Configure menu set the Pulse output to ON 2 In the Configure menu defi...

Страница 4: ...side the controller even when the power switch on the front panel is in the OFF position Never open the front panel without first disconnecting power from the outlet Prewired controllers are supplied with an 8 foot 18 AWG power cord with USA style plug A 1 Phillips driver is required to open the front panel 2 Low voltage signal wires probes flow switch water meter etc should never be run in condui...

Страница 5: ...al 24 VDC Power Output J2 NanoTron N Logic Card Contrast Power 1 2 3 4 5 ON OFF If the mA OUT Power switch is on INT the unit s internal 24 VDC is applied to the output If set for EXT the external loop out power supplied is used on the output Pulse Out mA OUT Flow Switch WM or Dig In mA IN Internal 24 VDC Ext Out Loop Power Input Device Input Device Jump from 24 to mA IN Wiring for two wire input ...

Страница 6: ...ill read system values If an alarm is present the display flashes with the alarm status The Run menu will display values such as day time date and other values depending upon the features present on the unit The unit will automatically return to the Run mode if no keys are pressed for three minutes Menu This mode is used to make adjustments to settings and readings on the controller To access the ...

Страница 7: ...g needs to be done less often VII Troubleshooting The Advantage NanoTron controller is designed for many years of trouble free operation Should a problem occur refer to the following chart to help identify the problem If replacement is required follow the procedures listed in the Warranty and Factory Service portion of this manual SYMPTOM POSSIBLE CAUSE SOLUTION False reading Bad or dirty electrod...

Страница 8: ...Password 0000 Flow Sw Close DigIn W Meter Feed OK w Ctrl No Feed No Flow Pulse ON 4 20 Output 4 mA 000 0 Sim 4mA OF 20mA 999 9 Sim 20mA OF Set 4 and 20 out at desired sensor readin Sim 4 and 20 will force outp to either 4 or regardless of reading 4mA applied N 4mA In 04350 20mA applied N 20mA In 21350 Press Enter only if a 4mA or 20mA signal is being received when in those calibration screens Sele...

Страница 9: ...ate is sensor reading for high pulse rate LoRate 000 0 Set 4 and 20mA out at desired sensor reading Sim 4 and 20mA will force output to either 4 or 20 regardless of reading Select if Pulse Output of mA input is on off Set the decimal for displayed numerical format and the 4mA and 20mA for what the value of that range desired at those two mA values CAL 20 2948 CAL 4 0590 Set Default N Increase the ...

Страница 10: ...n If we are unable to diagnose and solve your problem over the phone a fully warranted replacement unit will be shipped usually within 48 hours on a 30 Day Billing Memo This service requires a purchase order and the replacement unit is billed to your regular account for payment The replacement unit will be billed at current list price for that model less any applicable resale discount Upon return ...

Страница 11: ...11 Notes ...

Страница 12: ...ollers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage 5 4 3 2 1 ENTER HELP 5 4 3 CHANGE RUN SET UP 0 9 8 2 1 7 6 HOME BACK 3 4 5 2 1 8 9 0 7 6 SET UP RUN CANCEL HELP BACK ENTER HOME ...

Отзывы: