background image

4

Electrical Wiring

The controller has an internal regulated power supply that will operate in the range of approximately 100 to 

240 VAC on the incoming wiring. Output relay(s) are protected with a replaceable fuse.  Relay output voltage 

will equal the incoming line voltage. 

Prewired units are supplied with a 16 AWG cable with a 3-wire grounded USA 120 volt plug for incoming power 

and 18 AWG 3-wire grounded receptacle cords for all control relay outputs.  Conduit units are supplied with 

liquid tights and adaptors for easy hard wiring to supplied connector.

NOTES: 

1. 

Liquid tight fittings and some labeled signal leads are provided for signal (low voltage) connections, 

such as water meter inputs.

2. 

Hall effect meters that r12 VDC must use an external power supply (TFS-PWR).

+5 VDC

Ground

Conductivity

Temp

NanoCond PW

A Rev G

R B W G

Conductivity Probe

mA

Output

-

+

P S G

Meter

+

-

Flow

+

-

Level

Signal

Note 1: Contacting head water meters just use signal 

and ground.  The +5 VDC is used with hall effect meters.

-

Alarm Dry

Contact Output

+

Note 2: The alarm dry 

contact output is normal 

open.  12 VDC max be 

connected to output.

FUSE

FUSE

Ground

Relay 1

Power Supply

Relay 2

Neutral

Hot

NeutralGroundN/O N/C

NeutralGroundN/O N/C

Relay 1 Out

Relay 2 Out

Power In

Powered relay

output jumper

configuration

Dry contact relay

output jumper 

configuration

Relay Card

NanoTron-C & B2 Logic Card

Contrast

Adjust

Note:  Use GND and N.O. 

for N.O. dry contact relay or 

use GND and N.C. for N.C. 

dry contact relay.

1
2

3

4

5

ON

OFF

Reset

Battery

CAUTION

1.  There are live circuits inside the controller even when the power switch on the front panel is in 

the OFF position. Never open the front panel without first disconnecting power from the outlet. 

Prewired controllers are supplied with an 8 foot, 18 AWG power cord with USA style plug. A #1 

Phillips driver is required to open the front panel.

2. 

Low voltage signal wires (probes, flow switch, water meter,  etc.) should never be run    

in conduit with high voltage (like 115VAC) wires.

3. 

Never attempt to land connections to the controller without first disconnecting power from the outlet.

4. 

Do not block access to disconnect power during mounting and installation.

5.  The controller should be connected to its own isolated circuit breaker, and for best  

 

results,  the ground should be a true earth ground, not shared. Any attempt to bypass the grounding 

will compromise the safety of users and property.

6. 

The  electrical  installation  of  the  controller  must  be  performed  by  trained  personnel  only  and 

conform to all applicable National, State and Local codes.

7. 

Operation of this product in a manner not specified by Advantage Controls may result in damage 

to equipment or persons. 

8. 

Avoid  mounting  in  locations  that  expose  the  controller  to  direct  sunlight,  vapors,  vibration, 

liquid  spills  or  extreme  temperatures;  less  than  0°F  (-17.8°C)  or  greater  than  120°F  (50°C). 

EMI(electromagnetic interference) from radio transmissions and electric motors can also cause 

damage or interference and should be avoided.

!

!

Содержание NANO-N

Страница 1: ... mA Input Installation Maintenance Repair Manual Advantage Controls 4700 Harold Abitz Dr Muskogee OK 74402 Phone 918 686 6211 Fax 888 686 6212 www advantagecontrols com email support advantagecontrols com 4 2019 ENTER ...

Страница 2: ...nstallation Mounting Instructions 4 Electrical Wiring 4 Relay Cards 4 Logic Cards 5 IV Front Panel Description 6 V System Operation Overview 6 Description of Menus 6 VI Maintenance 7 VII Troubleshooting 7 VIII NanoTron mA Menu Map 8 IX Warranty 30 Day Billing Memo Policy 10 ...

Страница 3: ...her external devices via two control relay outputs The pulse output can pace a metering pump or convert a mA flow rate into contact style water meter pulses like used in a MegaTron Follow the steps below to program the Pulse Out based on the mA range of the flow device using an example of 500 gpm as the max 20mA signal 1 In the Configure menu set the Pulse output to ON 2 In the Configure menu defi...

Страница 4: ...side the controller even when the power switch on the front panel is in the OFF position Never open the front panel without first disconnecting power from the outlet Prewired controllers are supplied with an 8 foot 18 AWG power cord with USA style plug A 1 Phillips driver is required to open the front panel 2 Low voltage signal wires probes flow switch water meter etc should never be run in condui...

Страница 5: ...al 24 VDC Power Output J2 NanoTron N Logic Card Contrast Power 1 2 3 4 5 ON OFF If the mA OUT Power switch is on INT the unit s internal 24 VDC is applied to the output If set for EXT the external loop out power supplied is used on the output Pulse Out mA OUT Flow Switch WM or Dig In mA IN Internal 24 VDC Ext Out Loop Power Input Device Input Device Jump from 24 to mA IN Wiring for two wire input ...

Страница 6: ...ill read system values If an alarm is present the display flashes with the alarm status The Run menu will display values such as day time date and other values depending upon the features present on the unit The unit will automatically return to the Run mode if no keys are pressed for three minutes Menu This mode is used to make adjustments to settings and readings on the controller To access the ...

Страница 7: ...g needs to be done less often VII Troubleshooting The Advantage NanoTron controller is designed for many years of trouble free operation Should a problem occur refer to the following chart to help identify the problem If replacement is required follow the procedures listed in the Warranty and Factory Service portion of this manual SYMPTOM POSSIBLE CAUSE SOLUTION False reading Bad or dirty electrod...

Страница 8: ...Password 0000 Flow Sw Close DigIn W Meter Feed OK w Ctrl No Feed No Flow Pulse ON 4 20 Output 4 mA 000 0 Sim 4mA OF 20mA 999 9 Sim 20mA OF Set 4 and 20 out at desired sensor readin Sim 4 and 20 will force outp to either 4 or regardless of reading 4mA applied N 4mA In 04350 20mA applied N 20mA In 21350 Press Enter only if a 4mA or 20mA signal is being received when in those calibration screens Sele...

Страница 9: ...ate is sensor reading for high pulse rate LoRate 000 0 Set 4 and 20mA out at desired sensor reading Sim 4 and 20mA will force output to either 4 or 20 regardless of reading Select if Pulse Output of mA input is on off Set the decimal for displayed numerical format and the 4mA and 20mA for what the value of that range desired at those two mA values CAL 20 2948 CAL 4 0590 Set Default N Increase the ...

Страница 10: ...n If we are unable to diagnose and solve your problem over the phone a fully warranted replacement unit will be shipped usually within 48 hours on a 30 Day Billing Memo This service requires a purchase order and the replacement unit is billed to your regular account for payment The replacement unit will be billed at current list price for that model less any applicable resale discount Upon return ...

Страница 11: ...11 Notes ...

Страница 12: ...ollers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage 5 4 3 2 1 ENTER HELP 5 4 3 CHANGE RUN SET UP 0 9 8 2 1 7 6 HOME BACK 3 4 5 2 1 8 9 0 7 6 SET UP RUN CANCEL HELP BACK ENTER HOME ...

Отзывы: