15
Function 4 - CLOCK PROGRAMMING
-
The clock time is programmed by pressing the Function key, 4
and then entering the current time, date and then pressing the Enter key. The time is entered in military format
HHMM and the date is entered as MMDDYY.
Function 5 - pH1 4 BUFFER/ ORP1 CALIBRATE
-
If pH1 is enabled, Function 5 is used to calibrate
the pH sensor to a pH 4 buffer. For further details, refer to the pH section of the manual. If ORP1 and ORP2
are enabled, Function 5 is used to calibrate the ORP1 sensor. For further details, refer to the ORP section
of the manual.
Function 6 - pH1 7 BUFFER
-
If pH 1 is enabled, Function 6 is used to calibrate the pH sensor to a pH 7
buffer. For further details, refer to the pH section of the manual.
Function 7 - pH2 4 BUFFER/ ORP1 CALIBRATE/ ORP2 CALIBRATE
-
If pH2 is enabled, Function 7
is used to calibrate the pH sensor to a pH 4 buffer. For further details, refer to the pH section of the manual. If only
ORP1 is enabled, Function 7 is used to calibrate the ORP sensor. If ORP1 and ORP2 are enabled, Function 7 is
used to calibrate the ORP2 sensor. For further details, refer to the ORP section of the manual.
Function 8 - pH2 7 BUFFER
-
If pH 2 is enabled, Function 8 is used to calibrate the pH sensor to a pH 7
buffer. For further details, refer to the pH section of the manual.
IV. Setpoints
A.
Set Standard Setpoints
SETPOINT DESCRIPTION
RANGE DEFAULT
001
PS1 LO
0-9999
0
002
PS1 HI
0-9999
0
003
PS1 DELAY
0-999
5
004
PS1 WARNING/SHUTDOWN
0-3
0
005
PS1 OFFSET
0-99
50
006
PS1 SPAN
0-9999
307
007
PS2 LO
0-9999
0
008
PS2 HI
0-9999
0
009
PS2 DELAY
0-999
5
010
PS2 WARNING/SHUTDOWN
0-3
0
011
PS2 OFFSET
0-99
50
012
PS2 SPAN
0-9999
307
013
PS3 LO
0-9999
0
014
PS3 HI
0-9999
0