Inhibit Line Test (optional) 

– Follow this step only if you installed the inhibit switch 

described in the wiring section on page 6.  This is to verify that the optional inhibit switch is 
functioning and the drive is initially powered up in a disabled state. 

1.  Disconnect the motor power by unplugging the white connector on CBL-P01-10.  

Unplugging this connection allows you to power up the system without the possibility 

of spinning the motor. 

2.  Apply power to the drive.  Toggle the inhibit switch and verify that you can cause the 

LED color to change from Red to Green.  Set the switch so the LED is Red. 

3.  Remove power from the drive and reconnect the white connector on CBL-P01-10. 

 

 

System Power Up 

1.  Apply power to the drive.  If an inhibit switch has been installed, enable the drive by 

toggling the inhibit switch so the LED turns Green. 

2.  The motor should turn at a smooth controlled speed. 
3.  If the motor turns then the system has been hooked up correctly.  Remove power 

and continue to the next section.  If not then go to Troubleshooting

4.  To stop the motor from turning, turn the Test/Offset switch (SW4) to the OFF 

position.  Then use the offset pot (Pot 4) to set the speed to zero. 

 
 

 
Troubleshooting 
LED not lit. 

Verify that power has been applied to the drive. 

Motor doesn’t have holding torque 

Verify that the LED is Green.

 

LED doesn’t turn Green. 

Verify all cables are connected. 
If an Inhibit Switch has been installed, toggle the 

Inhibit switch. 

Motor doesn’t turn but has holding 
torque 

Turn Pot 4 (Test/Offset) in either direction.  This will 
change the amount of offset in the drive. 

Contact Factory - If you can’t get the motor turning within a few minutes, please call and 

ask for technical support!  805-389-1935.  We want to get you up and running quickly! 
 
 

 

ELECTROMATE

Toll Free Phone  (877) SERVO98

Toll Free Fax  (877) SERV099

www.electromate.com

[email protected]

Sold & Serviced By:

Содержание QUICKSTART BR2303NI-A01-DC080

Страница 1: ...Plug n Play Servo System with analog drive brushed motor and cables Continuous 3 1 lb in 4700 rpm v 1 02 ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales el...

Страница 2: ...kdays from 8am to 5pm Pacific Time at 805 389 1935 We can also be contacted via email through our website www a m c com go to Contact Us 4 steps to success 1 Getting Started What s included with Quick...

Страница 3: ...within 5 minutes All systems are initially configured in velocity or voltage mode to turn the motor shaft at 30 20 rpm This is an indication that when put together it works out of the box No pots to...

Страница 4: ...rements Output voltage between 20 80VDC Current output of 6A continuous Isolation transformer between the AC input and DC output Selected AMC Power supplies 1st choice PS16L60 PS16L72 PS16L80 2nd choi...

Страница 5: ...tor Connect the white connector on the motor to the corresponding connector on cable CBL P01 10 Connect the red and black wires to the P2 connector on the drive Black Motor P2 1 Red Motor P2 2 System...

Страница 6: ...Interface Board This switch disables power to the motor until you are ready Opening the switch Enables the drive closing the switch Disables the drive Cautions Unexpected motion To avoid the motor fro...

Страница 7: ...Motion Controls 3805 Calle Tecate Camarillo CA 93012 Phone 805 389 1935 Fax 805 389 1165 www a m c com 7 ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales el...

Страница 8: ...e the drive by toggling the inhibit switch so the LED turns Green 2 The motor should turn at a smooth controlled speed 3 If the motor turns then the system has been hooked up correctly Remove power an...

Страница 9: ...e at two locations on the SIB However to avoid ground loops there should only be one connection between the drive signal ground and the controller signal ground Don t add a connection if there is alre...

Страница 10: ...reewheeling condition If your controller has an inhibit function then we highly recommend that you use it Inhibit Connection Controller SIB Inhibit C3 11 Inhibit Note The inhibit input is configured t...

Страница 11: ...r try to find separate paths that maintain distance between the two A rule of thumb for the minimum distance between these wires is 1cm for every 1m of cable length Grounding Bring all ground wires to...

Страница 12: ...controller Some controllers require that the drive be in torque mode Other controllers require that the drive be in velocity mode Check the documentation on your controller or contact the manufacturer...

Страница 13: ...ection Full CW or Full CCW means the pot has been turned to the end of its travel where it begins to click on every turn These potentiometers have a 14 turn range before they start to click The number...

Страница 14: ...le Voltage Mode SW1 On SW2 Off SW3 Off Switches SW4 Off Pot1 Loop Gain 11 turns Pot2 Current Limit 8 4 turns Pot3 Reference Gain Full CW Pots Pot4 Offset Set for no torque Current Limit with these set...

Страница 15: ...st the Loop Gain Turn the Loop Gain pot to the full counterclockwise position Enable the drive Turn the Loop Gain pot clockwise When the system begins to make a loud buzzing noise turn the pot in the...

Страница 16: ...application such as Additional features Different power range Smaller size Different form factor such as plug in style drives Network connectivity Then our applications engineers can help optimize yo...

Страница 17: ...93012 Phone 805 389 1935 Fax 805 389 1165 www a m c com 17 Appendix A System Specifications B Drive C Motor D Cables E System Interface Board ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877...

Страница 18: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 19: ...em Specifications Torque peak 6 88 lb in 0 777 Torque continuous 3 13 lb in 0 35 Nm Velocity Maximum 4700 Supply Voltage 20 80VDC Encoder Resolution NA this package does not come with an encoder Speed...

Страница 20: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 21: ...IP switch selectable current voltage velocity analog position loop Four quadrant regenerative operation Agency Approvals BLOCK DIAGRAM ADVANCED MOTION CONTROLS 3805 Calle Tecate Camarillo CA 93012 Tel...

Страница 22: ...LS POWER STAGE SPECIFICATIONS 12A8 25A8 20A14 20A20 DC SUPPLY VOLTAGE 20 80 V 20 80 V 40 140 V 40 190 V PEAK CURRENT 2 sec Max internally limited 12 A 25 A 20 A 20 A MAXIMUM CONTINUOUS CURRENT interna...

Страница 23: ...continuous current limit I 11 INHIBIT This TTL level input signal turns off all four power devices of the H bridge drive when pulled to ground This inhibit will cause a FAULT condition and a red LED F...

Страница 24: ...TIONS POTENTIOMETER DESCRIPTION TURNING CW Pot 1 Loop gain adjustment in voltage velocity modes Turn this pot fully ccw in current mode Increases loop gain Pot 2 Current limit It adjusts both continuo...

Страница 25: ...to adjust the current limit turn the potentiometer fully counter clockwise then turn clockwise to the appropriate value If the desired limit is for example 10 amperes and the servo amplifier peak cur...

Страница 26: ...Models 12A8X 25A8X 20A14X and 20A20X X indicates the current revision letter MOUNTING DIMENSIONS See page F 7 ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sal...

Страница 27: ...Mounting Dimensions F 7 ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 28: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 29: ...oz in 2 47 350 SPEED RATED VOLTAGE RPM 4700 RATED VOLTAGE V dc 60 CONTINUOUS CURRENT A 3 7 PEAK CURRENT A 26 1 TORQUE CONSTANT Nm A oz in A 0 1050 14 87 VOLTAGE CONSTANT V KRPM 11 RESISTANCE ohms 2 0...

Страница 30: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 31: ...k 3 4 REF IN green 4 5 REF IN green white 5 Shield Shield Shell NOTE For cables with only twisted pairs single wires can be paired with other single or unused wires Creating a twisted pair from these...

Страница 32: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 33: ...ck Crimp 4 Shield Shield grey Spade A 4 Pin Molex Connector Terminals P N 39 01 3043 P N 39 00 0081 Common Side 2 CABLE CBL P01 10 Side 1 DIAGRAM Flying Leads Single Wires 10 ft Connector A Shield Spa...

Страница 34: ...ELECTROMATE Toll Free Phone 877 SERVO98 Toll Free Fax 877 SERV099 www electromate com sales electromate com Sold Serviced By...

Страница 35: ...s Pin Function 1 5V 3mA 2 SGND 3 5V 3mA 4 Ref In 5 Ref In 6 Tach In 7 Tach Gnd 8 Curr Mon Out 9 Curr Ref Out 10 Cont Curr Lim 11 Inhibit 12 Inhibit 13 Inhibit 14 Fault Out 15 NC 16 NC 17 18 19 SGND En...

Отзывы: