Advanced PSU EN54-4 Скачать руководство пользователя страница 3

 

 

www.advancedco.com 

 

Specifications: 

Item 

Specification Details 

Approvals 

All Power Supply Units comply with the requirements of EN54-4:1997 +A1:2002 +A2:2006, EN55022 
class B emissions limits & EN60950-1:2006 safety standards. 

 

Input Supply 

1.5A PSE 

220-240V AC, 50/60Hz, Fuse T3.15H250 

3.0A/5.0A PSE  : 

200-240V AC, 50/60Hz, Fuse T3.15H250 

Output Voltage  

Max 28.5V DC, Min 19.7V DC at minimum battery voltage of 21V

1

with mains disconnected (Output 

voltage is V

BAT

 

– 1.3V max. at I

max.a

Ripple 200mV max (Note: 1V p-p including switching frequency noise). 

Charger Voltage 

27.4V DC nominal at 20°C temperature compensated over the range -5°C to +40°C 

Output Current 

(I

max.a 

= I

max.b

(I

min

 = 10mA) 

1.5A PSE 

1.0A continuous load, 0.5A battery charge 

3.0A PSE 

2.0A continuous load, 1.0A battery charge [3.0A to load if configured for PSE only

2

5.0A PSE 

3.0A continuous load, 2.0A battery charge [5.0A to load if configured for PSE only

2

] 

Dimensions Enclosure 
IP30 (H x W x D) 

MXP-049 

320 x 345 x 88mm 

3Kg without batteries 

MXP-050-001  : 

320 x 345 x 88mm 

3Kg without batteries 

MXP-050-002  : 

425 x 406 x 125mm 

5Kg without batteries 

MXP-051 

425 x 406 x 125mm 

5Kg without batteries 

MXP-051/D 

425 x 406 x 190mm 

7Kg without batteries 

MXP-549 

263 x 246 x 85mm 

3Kg without batteries 

MXP-550 

378 x 338 x 110mm 

5Kg without batteries 

MXP-550D 

410 x 363 x 185mm 

7Kg without batteries 

MXP-551 

378 x 338 x 110mm 

5Kg without batteries 

MXP-551D 

410 x 363 x 185mm 

7Kg without batteries 

 

Dimensions Cage 

(H x W x D) 

1.5A PSE 

105 x 94 x 38mm 

250g 

3.0/5.0A PSE 

184 x 94 x 58mm 

690g 

Environment 

Indoor, Dry 

Operating 
Temperature 

-5ºC to +40ºC @ full load output 

Relative Humidity 

95% non-condensing (maximum) 

Standby Battery and 
Internal Resistance 

2 x 12V Sealed Lead-Acid Type (Yuasa or Powersonic recommended) 

1.5A PSE 

3.3Ω  1.2Ah minimum to 7Ah maximum 

3.0A PSE 

1.6Ω  1.2Ah minimum to 18/24Ah maximum 

5.0A PSE 

0.8Ω  1.2Ah minimum to 38Ah maximum 

Fault Output 

Volt free change-over contacts rated 1A @ 30V dc (all models) 

External Indication 

Green: Power indicator, Amber: Fault indicator 

On board indication 

Mains Fail, Charger Fail, Battery open circuit, Battery Low & Heartbeat 

Deep Discharge  

All models incorporate battery deep discharge protection (19V) 

As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice. E&OE 

 
 
 

 

                                                        

1

 The battery final discharge voltage recommended by battery manufacturer. 

2

 NOT EN54-4 Compliant. EN54-4 specifies the provision of two power sources. These should comprise a main supply (AC mains) and a 

stand-by supply (battery). 

Содержание PSU EN54-4

Страница 1: ...www advancedco com PSU EN54 4 Power Supplies ...

Страница 2: ...sure SPARES Mxs 049 1 5A Caged Unit only Mxs 050 3 0A Caged Unit only Mxs 051 5 0A Caged Unit only Supplied with AC lead and terminal block Mxp 501 Remote Temp Sensor Applications Limitations For any fire alarm system that specifies EN54 4 power supplies e g BS5839 code of practice Compatibility These power supply units can be used in fire alarm installations requiring a 24Volt supply for operatio...

Страница 3: ...thout batteries MXP 549 263 x 246 x 85mm 3Kg without batteries MXP 550 378 x 338 x 110mm 5Kg without batteries MXP 550D 410 x 363 x 185mm 7Kg without batteries MXP 551 378 x 338 x 110mm 5Kg without batteries MXP 551D 410 x 363 x 185mm 7Kg without batteries Dimensions Cage H x W x D 1 5A PSE 105 x 94 x 38mm 250g 3 0 5 0A PSE 184 x 94 x 58mm 690g Environment Indoor Dry Operating Temperature 5ºC to 4...

Страница 4: ...its can be used for any fire alarm system installation that specifies EN54 4 Power Supply Equipment Suited for almost any application except for CIE in separate cabinet the power supply unit battery charger has been developed using the latest surface mount technology to provide a high efficiency switch mode power supply The power supply units are available in fully enclosed construction providing ...

Страница 5: ...nput supply lead with AC Mains Terminal Block is supplied in the kit 4 NB The batteries must not be mounted in an enclosure separate from the power supply since this could affect the temperature compensating charging characteristics resulting in incorrectly charged batteries The power supply modules are also incorporated into other boxed peripheral units The information in this document is applica...

Страница 6: ...ed when the panel is finally mounted An example of the Mxp 051 is shown opposite 3 1 1 1 Mounting Peripheral Cards or OEM equipment Space is provided in which to mount ancillary equipment or printed circuit cards 5 3 1 1 2 Fixing Points and Dimensions 135 135 340 24 315 255 Power Fault Earth Lead to Cover 7Ah Enclosure 135 135 340 30 420 255 Power Fault Earth Lead to Cover 17Ah 38Ah Enclosure 5 Ad...

Страница 7: ...ecure the panel to the wall For example drill the required holes in the supporting wall using a drill bit diameter 7 0 mm and plug with a suitable 40mm long expansion plug Affix the panel to the wall with M5 screws length 40mm or No 10 screws length 1 The cover is hinged on the left hand side Ensure that there is sufficient space to allow the cover to be opened when the panel is finally mounted 3 ...

Страница 8: ... 551 D 3 1 3 Mxs 049 Mxs 050 Mxs 051 PSE Modules The PSE modules can be installed in Mx 5000 Rack and other Utility enclosures Refer to the relevant product manuals for further information The dimensions and fixing points are shown below 105 98 66 94 1 5A PSE 184 174 66 94 3 0A 5 0A PSE 24Ah 38Ah 24Ah 38Ah ...

Страница 9: ... models Replace with correct rating and specification only Connect the PSE to the mains supply via a readily accessible disconnect device Isolation Switch and suitable earth fault protection incorporated in the building installation wiring FUSE Brown Grn Yel LIVE EARTH NEUTRAL PSU Internal Mains Wiring Blue Field Connections AC Mains terminations Mxp 049 The Mains cable should be a minimum cable s...

Страница 10: ...0 024Ω m Cable Resistance RCABLE for 2 5mm 2 is 0 015Ω m BAT BAT VO VO COM N O N C Remote LED Start from battery Switch Fault Output Configuration Serial Link Common Arrangement Not on 1 5A SE Remote Temp Sensor Jumper Link for local temperature sensor Observe that the load is connected with the correct polarity Route the wiring away from any mains connections 3 2 2 2 To Battery The system is desi...

Страница 11: ... 4 5 6 2 1 3 4 6 2 1 MAINS FAILURE AC Mains Supply failure 30 seconds 2 CHARGER FAULT Battery charger output failure 2 minutes 3 BATTERY OC Battery disconnected 2 minutes 4 BATTERY LOW Battery High Cell Resistance 3 minutes 5 BATTERY ON Output Voltage is supplied from the battery 6 HEARTBEAT Microprocessor is running flashes 3 2 2 5 Charger PSE Only6 Configuration The 3 0A and 5 0A PSE models can ...

Страница 12: ...t used ensure the jumper is fitted to the centre two pins BAT BAT VO VO COM N O N C Remote LED Start from battery Switch Fault Output Configuration Serial Link Common Arrangement Not on 1 5A PSE Remote Temp Sensor Jumper Link for local temperature sensor If neither a jumper nor a remote sensor is fitted the PSE module will indicate a charger fault condition Remove the jumper and plug the Mxp 501 i...

Страница 13: ...tors should be OFF the Heartbeat indicator should be FLASHING 5 The Fault relay should be energised Check that there is a connection between common and normally open N O This connection should indicate a short circuit when checked with a test meter on the continuity setting The following table indicates the charger voltage against temperature when the batteries are fully charged Ambient Temperatur...

Страница 14: ...H PS 1250 F1 7AH NP7 12 7AH PS 1270 12AH NP12 12 12AH PS 12100 F1 18AH NP18 12 18AH PS 12180 NB 24AH NP24 12B 26AH PS 12260 NB 38AH NP38 12 40AH PS 12400 STOP For optimum performance and charge retention Yuasa recommend that batteries up to 6 months old from date of manufacture are top charged prior to installation To perform the top charging use a separate supply and charge at 2 4V per cell i e 1...

Страница 15: ...www advancedco com 15 USER NOTES ...

Страница 16: ...cedco com Advanced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 132 Revision 07 ...

Отзывы: