3.2.2.7 Remote Temperature Sensor
Provision is made on the 3.0A and 5.0A PSE
models for the connection of a remote battery
temperature sensor (Mxp-501). This is for
applications where the modules are installed in
rack mount enclosures or in large enclosures and
where the batteries are not located immediately
next to the module.
A latching pin header, PL3, is provided for
connection of the temperature sensor
– see
opposite and below.
If a remote temperature sensor is not used,
ensure the jumper is fitted to the centre two pins.
BAT
–
BAT +
VO
–
VO +
COM
N/O
N/C
Remote LED
Start from
battery Switch
Fault
Output
Configuration
Serial Link
Comm
on A
rrang
ement
Not on 1
.5A
P
SE
Remote Temp
Sensor
Jumper Link for local
temperature sensor
If neither a jumper nor a remote sensor is fitted, the PSE
module will indicate a charger fault condition.
Remove the jumper and plug the Mxp-501 into the connector. Route the sensor cable along with the battery
leads. Use the supplied tie-wraps to tie the sensor cable to the battery leads so that the encapsulated sensor is
located close to the batteries. The sensor cable is 500mm in length.