1  Introduction 

The  Mxp-537  Peripheral  Input  Card,  on-board  I/O  module,  is  an  internal  peripheral  for  use  with  the  Mx-5000 
range of fire alarm control panels 

Each card provides monitoring of up to 10, volt free, Switch inputs that can be individually configured to operate 
in monitored or unmonitored mode 

Cards are protocol Independent.   

Up to 16 cards may be connected to a panel, allowing for up to 160 extra volt free inputs per panel.  

Easily configured with the PC Configuration Tool 

2  General Installation & Operation  

2.1  Module Overview  

 

 

The Mxp-537 Peripheral Input card offers 10 individually configurable, volt free, input monitoring circuits, as well 
as including an Earth Monitor circuit in the event that the card is mounted remotely to its parent Fire Panel. 

With  up  to  16  supported  cards,  this  allows  an  extra  160  monitored  inputs  to  be  operated  from  a  single  Fire 
Panel. 

The  Mxp-537  Peripheral  Input  card  makes  use  of 

S

oftware 

M

onitoring 

A

nd 

R

eal 

T

ime  Power  Management 

techniques.  This  allows  the  card  to  minimise  energy  requirements  without  compromising  input  monitoring 
capabilities.     

Switch Input 10 has a dual operation mode. Its default behaviour is to act as a PSU fault monitor but this can be 
overridden  at  the  hardware  level  (via  the  on  board  DIP  switches)  to  allow  it  to  be  configured  as  a 
monitored/unmonitored input (configured via the PC Configuration Tool). 

If monitoring of very fast input pulses is required (< 0.5s) the Mxp-537 can be coupled with the Mxp-053, Latch-
Stretch Input Module, for a fast and reliable solution that can detect input pulses down to 200ms. 

 

 

 

Содержание Mxp-537

Страница 1: ...pheral Input Card The operation and functions described in this manual are available from Software Version Mx5000 050 04 onwards Individually Configurable Inputs Monitored Unmonitored Operation Mode S M A R T Power Management ...

Страница 2: ...cess to the following functionality EN54 13 Fault state reporting Item Specification Details Applicable Standards BS EN54 18 BS EN54 13 Operating Temperature 5 C to 40 C Relative Humidity 95 Non Condensing maximum PCB 20mm H x 105mm W x 125mm L 105 grams D C Supply 24V 17V to 28V DC Quiescent Current 25mA 10 I Ps wired with 6K8 EOLs Vs 24V Max Current 30mA 10 I Ps wired with 6K8 EOLs Vs 20V Input ...

Страница 3: ... 2 1 MODULE OVERVIEW 4 2 2 BASIC CONFIGURATION 5 2 2 1 PSU Mon Input 10 5 2 2 2 Disabling PSU Mon Input 10 5 2 3 WIRING CONFIGURATION 6 2 3 1 Supply Wiring 6 2 3 2 Comms Wiring 7 2 3 3 Input Wiring 7 3 CARD CONFIGURATION SETUP 8 ADDING A CARD TO THE DESIGN 8 CONFIGURING INPUTS 8 4 GENERAL NOTES 9 ...

Страница 4: ...nitor circuit in the event that the card is mounted remotely to its parent Fire Panel With up to 16 supported cards this allows an extra 160 monitored inputs to be operated from a single Fire Panel The Mxp 537 Peripheral Input card makes use of Software Monitoring And Real Time Power Management techniques This allows the card to minimise energy requirements without compromising input monitoring ca...

Страница 5: ...l Operation PSU Monitor Ok EOL Missing Open Circuit Fault PSU Monitor Fault Short Active PSU Fault PSU Monitor Fault When set to behave as a PSU Monitor the input becomes task specific Monitored Unmonitored settings assigned by the configuration tool are ignored The input is always interpreted by the Fire Panel as a PSU Fault regardless of any other action if any that is assigned to it in the PC C...

Страница 6: ...heral Input Card 24V GND PSU MON 485 A B A B I P 1 I P 2 I P 3 I P 4 I P 5 I P 6 I P 7 I P 8 I P 9 I P 10 Mxp 537 Peripheral Input Card GND NO COM Supply wiring with Remote PSU monitoring PSU 24V Fault Relay Com NC NO Supervising Relay To Peripheral Loop Input Module 24V GND PSU MON 485 A B A B I P 1 I P 2 I P 3 I P 4 I P 5 I P 6 I P 7 I P 8 I P 9 I P 10 Mxp 537 Peripheral Input Card 24V GND PSU M...

Страница 7: ...al Input Card Set PBUS EOL to ON on last card 2 3 3 Input Wiring PSU Fault Relay Un Monitored Monitored EOL 470R EOL PSU Monitor SW 1 OUT SW 2 OUT SW 1 IN SW 2 IN Mxp 053 Latch Stretch I P Module The Mxp 053 is an optional module that provides Latch Stretch functionality for fast inputs 200ms It also provides Input Isolation The MXP 053 Should be located local to the MXP 537 The MXP 537 Input shou...

Страница 8: ...ust be added to the same DIP Switch address as the one set on the card Configuring Inputs Input configuration is performed along the same line as configuring any other input device Setting the Input Action to No Action has the following impact Input is disabled at the hardware end overall power consumption is reduced End of Line resistors are not required for unused inputs By default all inputs ar...

Страница 9: ...ply should be configured for earth monitoring This equipment is constructed with static sensitive components Observe anti static precautions at all times when handling printed circuit boards Wear an anti static earth strap connected to panel enclosure earth point The unit must be grounded this is normally achieved via the screw terminals used to secure the card to the enclosure Should this not be ...

Страница 10: ...www advancedco com 10 This page is intentionally left blank ...

Страница 11: ...www advancedco com USER NOTES ...

Страница 12: ...anced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 189 Revision 01A First Issued 2013 mm dd ...

Отзывы: