www.advancedco.com
Specifications:
Models, Sales Order Parts:
Mxp-537 Peripheral Input Card
Applications / Limitations:
Volt free Inputs.
Power Supply must be local to the card.
Earth Monitoring circuit must be disabled if operating on the same ground plane as the Fire Panel
Compatibility:
Mx-5000 Range of Fire Panels
MxP-053 Latch-Stretch Input Module
ExP-005 Switch EOL Module
Requires PC Configuration Tool Version 6.10 Onwards
Requires Firmware Version 1.2 Onwards and Panel Version 50-08 Onwards for access to the
following functionality:
EN54-13 Fault state reporting
Item
Specification Details
Applicable Standards
BS EN54-18, BS EN54-13
Operating Temperature
-5°C to 40°C
Relative Humidity
95% Non Condensing (maximum)
PCB
20mm H x 105mm W x 125mm L, 105 grams
D.C. Supply
24V (17V to 28V) DC
Quiescent Current
25mA (10 I/Ps wired with 6K8 EOLs, Vs = 24V)
Max Current
30mA (10 I/Ps wired with 6K8 EOLs, Vs = 20V)
Input Circuits Available
10, Individually Configurable, Volt Free
Input (Imax)
30mA, Under Short Circuit
Input (V)
15V ± 5%
Input EOL
6K8
Input Active
470R
Max Line Resistance
50R
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice