www.advancedco.com
Specifications:
Models, Sales Order Parts:
Mxp-536 Peripheral Zone Card
Applications / Limitations:
Cards must be mounted locally to their power supply
Earth Monitoring circuit must be disabled if operating on the same ground plane as the Fire Panel
Volt free (PSU Monitor / Reset Input)
Compatibility:
Mx-5000 Range of Fire Panels
Exp-006 Active End of Line Module
Requires PC Config Tool Version 6.13 Onwards for access to all the configuration options.
Requires Panel Version 50-06 Onwards for access to the following functionality
Class A zones
Non-Latching zone configuration
Requires Panel Version 50-07b, And Card Firmware Version 1.05, Onwards for access to the
following functionality
Alarm Verification
Requires Panel Version 50-08 Onwards for access to the following functionality
Configurable EOL
Item
Specification Details
Applicable Standards
EN54-13, EN54-18
Operating Temperature
-5°C to 40°C
Relative Humidity
95% Non Condensing (maximum)
PCB
32mm H x 105mm W x 126mm L
150 grams (assembled with top plate)
D.C. Supply
24V (17V to 28V) DC
Min Quiescent Current
100mA (Vs = 24V, 8 Zones = Min Load, EOL = 6K8)
Max Quiescent Current
120mA (Vs = 24V, 8 Zones = Max Load, EOL = 6K8, Relays Off)
Max Current (O/Ps On)
135mA (Vs = 24V, 8 Zones = Max Load, EOL = 6K8, 3 Relays On)
Max Alarm Current
300mA (Vs = 20V, 8 Zones = Max Alarm Load, 3 Relays On)
Zone Circuits Available
8 Radial (Class B) / 4 Loop (Class A), Conventional
Zone Current (Iz) Limit
48mA, Under Short Circuit
Zone Voltage (Vz)
24V ± 5%
Max Line Resistance
32R
Radial Zone EOL
Configurable (6K8, 4K7 or 3K9), Advanced Exp-006 AEOL Module
PSU Monitor Input
Volt Free
PSU Monitor EOL
10K
PBUS EOL
150R
Relay Outputs
SELV, Change Over
As our policy is one of constant product improvement the right is therefore reserved to modify product specifications without prior notice