Advanced Mxp-536 Скачать руководство пользователя страница 1

 

 

www.advancedco.com 

Peripheral Zone Card 

The operation and functions described in this manual are available from Software Version Mx5000-050-04 onwards. 

 
 
 

 

 
 
 

 

Compatible with Standard or Diode Bases  

 

Up to 32* devices per circuit (*device range dependant) 

 

Individually Configured Zone circuits 

o

 

“Short = Alarm” Option  

o

 

“Intrinsic Safety” Option  

o

 

“Non-latching” Option (from 50-06 onwards) 

o

 

“Alarm Verification” Option (from 50-07b onwards) 

 

Current Limited Zone circuits (48mA under Short Circuit) 

 

Voltage Regulated Zone Circuits  

 

S.M.A.R.T. Power Management  

 
 
 
 

Содержание Mxp-536

Страница 1: ...h Standard or Diode Bases Up to 32 devices per circuit device range dependant Individually Configured Zone circuits o Short Alarm Option o Intrinsic Safety Option o Non latching Option from 50 06 onwa...

Страница 2: ...lity Configurable EOL Item Specification Details Applicable Standards EN54 13 EN54 18 Operating Temperature 5 C to 40 C Relative Humidity 95 Non Condensing maximum PCB 32mm H x 105mm W x 126mm L 150 g...

Страница 3: ...3 1 PSU Monitor 6 2 4 WIRING CONFIGURATION 7 2 4 1 Loop Class A Zone Wiring 7 2 4 2 Radial Class B Zone Wiring 7 2 4 3 485 Comms Wiring 8 2 4 4 Supply Wiring 8 2 5 DETECTOR COMPATIBILITY 9 2 5 1 Radia...

Страница 4: ...ork with standard or Schottky diode bases Complies with applicable standard EN54 13 Can be configured for operation with Intrinsically Safe zones In ring class A mode Up to 4 Conventional zones are su...

Страница 5: ...in a remote enclosure that requires earth monitoring only 1 of the cards should be set to monitoring mode Slide switch to the ON position to enable the earth monitor circuit Radial Class B operation S...

Страница 6: ...particular zone circuit on the card Therefore in stand alone mode only one zone circuit should be used for detection purposes or conversely all zone circuits on the card should be operating in the sam...

Страница 7: ...Device Zone Without Zone Supply Monitoring Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V PBUS A PBUS B B Notes For c...

Страница 8: ...N 0V 24V PBUS A PBUS B B Z 1 Z 2 Z 3 Z 4 A Out In Out Out Out In In In Z 1 Z 2 Z 3 Z 4 Z 5 Z 6 Z 7 Z 8 NC Mxp 536 Peripheral Zone Card COM NO Relay 1 NC COM NO Relay 2 NC COM NO Relay 3 PSU MON 0V 24V...

Страница 9: ...1 0 Yes SPC ET Beam 10 10 0 Yes SLR E3 Optical 32 21 0 Yes DCD AE3 Heat RofR 60deg 32 21 0 Yes DCD CE3 Heat RofR 90deg 32 21 0 Yes HF 24 UV flame 13 13 0 Yes DFG 60E Heat waterproof 32 21 0 Yes DFJ AE...

Страница 10: ...51E standard base no resistor Heat 78deg 32 0 0 No 5351E standard base no resistor Heat RofR 32 0 0 No 2 5 2 Ring Class A Nittan Maximum Devices Device Type Sensortec 0R base no resistor All except UV...

Страница 11: ...tion mode Class A B and add it to the design The device should be added to the same address as the one set on the card The selected operation mode should match the mode set on the card failure to do s...

Страница 12: ...one circuit can be individually configured to operate in Intrinsically Safe mode which is intended for use only with an appropriate I S Barrier and I S Devices Each zone can be configured for Alarm Ve...

Страница 13: ...s at all times when handling printed circuit boards Wear an anti static earth strap connected to panel enclosure earth point The unit must be grounded this is normally achieved via the screw terminals...

Страница 14: ...www advancedco com 14 This page is intentionally left blank...

Страница 15: ...www advancedco com USER NOTES...

Страница 16: ...nced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 188 Revision 01D F...

Отзывы: