28 

2.5.3  Detector Loop Installation 

 

 

Section 12.5.2 

Maximum of 32 Sensors / Call Points in a Zone (between Isolators). 

 
The Detection Loop Circuit should be installed as a continuous 
loop with isolator modules such that a short circuit condition 
does not remove more than one zone or 32 input devices. 

 

 

Section 13.7 

Not more than 512 fire detectors and / or manual call points 
and their associated mandatory functions shall be affected as a 
result of a system fault in the C.I.E.  
 

The panel should be installed with not more than 512 fire input devices. 
See Appendix 9 for further details on network installations.  

Form the loop starting at the Loop Out + and 

– 

terminals on the base card. 

Route the wires around the loop connecting all 
devices in accordance with the manufacturers’ 
data sheet supplied with each unit. 

Ensure that the devices are correctly installed with 
regard to their positive and negative terminal 
polarity (especially Loop Isolator Modules). 

Connect the return wires to the Loop IN + and 

– 

terminals on the base card. 

The diagram opposite shows the typical 
arrangement of the loop connections on the base 
cards.  

Refer to Sectio

2.3

 for details on installing 

additional loop drivers on the multi-loop panels. 

 

IN 

 

IN

 +

  

OUT

 –

 

OUT

 +

  

 

Base Card Terminations (Typical). 

 

 

When screened cable is used, it is vital to connect the screen / drain wire to the chassis / earth at 
the cable gland input / earth stud in the panel. Always ensure that all segments of the cable loop 
have continuity of the screen and take care to ensure that the screen is not exposed to any other 
earth point (e.g. metalwork, cable trays, junction boxes, etc.).  

The Loop Driver Circuit on the Base card is 
equipped with in-built isolators to take care of 
short circuit conditions on the wiring between the 
panel and the first device on the loop. Do not fit 
loop isolators at the panel outputs. 

The diagram opposite shows a typical loop 
arrangement.  

Maximum recommended cable loop length is 1500 
to 2000 Metres. Refer to 

Appendix 2 

– 

Recommended Fire Rated Cables

 for further 

information on cable types to be used. 

+

-

+

-

Isolators

 

Typical Loop Arrangement. 

 

 

Take care that the voltage drop at full load is within the detector rating – refer to the detector 
manufacturers’ data sheet for minimum values. 
To maintain signal line wiring supervision, break the wiring run at each loop device.  

 

 

The loop circuits support monitoring with an Active EOL device (embedded on the 
loop driver) to ensure circuit integrity in accordance with the requirements of EN54-
13. 

 

V d S 

2095 

Clause 6.2.5  
Not more than 128 
devices per loop 

 

V d S 

2095 

Not more than 512 
devices per panel 
or 12000m

2

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Mx Pro5 Mx-5100

Страница 1: ...Fire Alarm Panels Product Manual The operation and functions described in this manual are available from Software Version 5000 050 04 onwards www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...A High Efficiency Off Line Switched Mode 2x On board 24V DC 5A High Efficiency Off Line Switched Mode Output Voltage1 18 0V 28 0V 18 0V 28 0V 18 0V 28 0V 18 0V 28 0V Ripple Vpkpk 1 0V 1 0V 1 0V 1 0V M...

Страница 3: ...BUS MODULES 20 2 4 1 Routing Interface Card Plug In 20 2 4 2 2 Way Relay Card Plug In 21 2 4 3 Network Card 21 2 4 4 Peripheral Module Chassis Mounting 22 2 4 5 VdS Interface Module Chassis Mounting...

Страница 4: ...anel finds Devices Missing 46 3 3 3 3 Procedure if the Panel finds Devices Added 46 3 3 3 4 Procedure if the Panel finds Devices Changed 47 3 3 4 Loop Calibrate 47 3 3 5 Loop History 47 3 3 6 Loop Met...

Страница 5: ...DIX 2 RECOMMENDED FIRE RATED CABLES 64 5 2 1 Detector Loop Lengths Apollo Hochiki and AV 64 5 2 2 Sounder Circuit Lengths 65 5 2 3 Fire Fault Routing Circuit Lengths 65 5 2 4 Network Cables 65 5 3 APP...

Страница 6: ...uts Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input Output EN54 4 1997 A1 2002 A2 2006 Power supply equipment f...

Страница 7: ...arm Control Panels This manual provides generic programming and installation information Refer to the appropriate protocol application note for further and specific information for each protocol Refer...

Страница 8: ...ts Co incidence Detection Alarm Counter Fault Signals from Points Output to Fault Routing Equipment Disablement of Points Test Condition Standardised I O 7 8 7 9 7 10 7 11 7 12 Type B Type C 7 13 8 3...

Страница 9: ...e Requires installation of a routing interface card Refer to Sections 2 4 1 2 5 12 3 3 20 and 3 3 21 for further information Section 7 11 Delays to Outputs The C I E has provision for Output and Inves...

Страница 10: ...6 Installation Approvals 1 6 1 Fire System Installations The panel must be installed and configured for operation in accordance with these instructions and the applicable code of practice or national...

Страница 11: ...for eight key switches or four key switches and a printer Option for a 50 Zone LED card WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside Display Loop Driver Base Card Chassi...

Страница 12: ...LED Card Optional Key Switches Door Lock Ratings Label L D Enclosures comprises Back Box Base Card with 2x Loop Drivers mounted onto a Chassis Plate Door with Display Card mounted onto a fascia plate...

Страница 13: ...The MX 5800 consists of two independent systems comprising of 4 LP Base Cards and Display Cards only one display is normally visible and each system capable of supporting 512 detection devices Networ...

Страница 14: ...r Rittal or in Advanced MXM 510 XXU Rack enclosures Weight 6Kg For more information on the rack system and optional modules see document 680 195 MXM 510 16U Rack Enclosure 730 x 535 x 230 Steel 22Kg G...

Страница 15: ...rews fully the chassis plate has keyhole style mounting holes Carefully remove the chassis from the rear enclosure and place in a safe place to prevent accidental damage Do not lift the chassis by hol...

Страница 16: ...5 183 5 Knockouts x2 271 M Enclosure Size and Fixing Point Dimensions L Enclosure Size and knockouts top D Enclosure Size and knockouts top 447 472 431 26 183 5 183 5 Knockouts L x2 D x3 378 L D Encl...

Страница 17: ...2 2 4 Remounting the Chassis Carefully replace the chassis and fix into place using the two screws Reconnect the chassis earth cable to the spade terminal in the rear of the enclosure reconnect the di...

Страница 18: ...r information on cable types to be used Refer to specific sections on how to install AC Mains input and loop sounder relay and AUX outputs circuits WARNING HIGH VOLTAGE INSID DO NOT REMOVE COVER No Se...

Страница 19: ...rinted circuit boards Observe anti static precautions at all times when handling printed circuit boards A section of the Base Card identifying the locations for each loop driver is shown in the pictur...

Страница 20: ...Routing Interface Card Plug In Outputs to Routing Equipment Clauses 7 9 and 8 9 Output to Fire Protection Equipment Clause 7 10 The Routing Interface Card provides monitored outputs for connection to...

Страница 21: ...p 503 STD or an Mxp 509 FT Network Card can be installed onto the base card The card is fitted to the base card using 1x M3 screw and 3x plastic pillars A metal pillar is pre fitted to the base card R...

Страница 22: ...ther information The screw fixing is essential for EMC Immunity protection WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside Mxp 034 Power and Data Route along edge of chassi...

Страница 23: ...r before installing or removing printed circuit boards 2 4 5 1 Option Relay Card An optional Mxp 508 8 Way Relay Card can be mounted on top of the interface card to provide additional relay output cir...

Страница 24: ...ght corner only Keep the AC wiring away from the circuit boards and all other wiring FUSE Brown Green LIVE EARTH NEUTRAL Panel Wiring Blue 3 15A AC Mains terminations The fuse is rated as follows T 3...

Страница 25: ...the negative terminal of battery 2 Connect the negative of battery 1 to the positive of battery 2 using the supplied link cable Ensure that the battery terminals do not short out against any part of t...

Страница 26: ...WARNING HIGH VOLTAGE INSIDE DO NOT REMOVE COVER No Serviceable Parts Inside 2 5 2 3 Large Enclosure The diagrams opposite show the recommended location and orientation for 7Ah 17AH batteries within t...

Страница 27: ...grams opposite show the recommended location and orientation for 7Ah 38AH 45AH batteries within the panel WARNING HIGH VOLTAGE INSID DO NOT REMOVE COVER No Serviceable Parts Inside www acornfiresecuri...

Страница 28: ...ase Card Terminations Typical When screened cable is used it is vital to connect the screen drain wire to the chassis earth at the cable gland input earth stud in the panel Always ensure that all segm...

Страница 29: ...have continuity of the screen and take care to ensure that the screen is not exposed to any other earth point e g metalwork cable trays junction boxes etc The sounder outputs support monitoring with a...

Страница 30: ...rst panel to the IN socket on the next panel as follows SCN B A A B SCN IN OUT To Base Card OUT Screen B A Screen B A IN STD Up to 32 nodes The IN terminals on the first node and the OUT terminals on...

Страница 31: ...N54 2 compliant 2 5 7 Auxiliary Supply Output The MxPro 5 Series are equipped with an auxiliary 24V DC 500mA power supply output This can be used for powering ancillary equipment and must only be used...

Страница 32: ...t for a user text description The switch cable connector plugs into the display card connector as show opposite Switch Input Connector Optional Key Switches 87654321 Route the switch cables along the...

Страница 33: ...n by another fire routing output located on a separate panel Routing Interface FIRE 1 FAULT FAILSAFE INPUT Output from another panel OUT IN OUT IN FSI OUT IN FIRE 2 470R 10K MONITORED INPUT CIRCUIT Ty...

Страница 34: ...itored default If set to monitored EOL 10K Active Resistance 470 1 2 3 4 15 16 17 18 11 12 13 14 5 6 7 8 9 10 FAT FBF FSD E AUSG S red E RS232 To base card To relay card Learn Circuit Typical Arrangem...

Страница 35: ...d connect specific types RS485 Connection RS232 Connection Note Units connected via RS232 must be wired in rigid conduit and located 3 metres from the panel FAT 1 2 3 4 FAT FBF RXD RXD UB1 UB1 RS485 C...

Страница 36: ...1 2 3 4 FAT FBF RS232 ADP N3S 0V TX RX TX RX 0V PANEL 1 PANEL n AUSG AUSG V 27 V 26 UB2 UB2 SIO2 SIO2 UB1 UB1 SIO1 SIO1 UB2 UB2 SIO2 SIO2 UB1 UB1 SIO1 SIO1 UB2 UB2 SIO2 SIO2 UB1 UB1 SIO1 SIO1 UB1 UB1...

Страница 37: ...system fault condition the fail safe input is automatically connected to the E output The router should be provided with power from a separate power supply Router Coil 200 5000ohm 24V DC 11 12 13 14...

Страница 38: ...Passwords If this number is lost it is not possible to enter commission mode functions Refer to section 5 1 for further formation Default 7654 3 1 2 Memory Lock The configuration memory may be protect...

Страница 39: ...g the button to obtain the required character wait for 1 second and the character will be entered and the cursor will move to the next character in the text description Pressing another button will im...

Страница 40: ...re reporting an alarm condition during test Disabled View Zones Inputs and Outputs that are disabled Inputs View the current state of Zones and Inputs Outputs View the current operational condition of...

Страница 41: ...Press the buttons to scroll through the list of loops available and then press the button to select the loop required Note For the 5100 and as there is only one possible circuit the display will imme...

Страница 42: ...32 Use the number keys to change the meldergruppe number assigned to the device 3 3 2 5 Device Text This parameter shows the 26 character location text assigned to this device For guidance on how to...

Страница 43: ...lication note for further information This parameter shows if the device sensitivity is set to its DEFAULT or CUSTOM settings For example Loop 1 Devices More Address Sensitivity 001 0 DEFAULT 002 0 DE...

Страница 44: ...5s Min Value 8 SAM SSM In the above example the panel is using special sensitivity mode 5 and time clock number 2 Enter 0 in the SSM Clock field to cancel Special Sensitivity Mode A number must be en...

Страница 45: ...uminate the detector LED and individual outputs sounders and relays can be tested to check output connections and operation While the address field is highlighted press the buttons to scroll through t...

Страница 46: ...ss is suspended and the display shows a pop up window with options For example KEEP THIS DEVICE DELETE THIS DEVICE KEEP ALL MISSING DELETE ALL MISSING Address 002 DEVICE MISSING If the missing device...

Страница 47: ...CCEPT ALL NEW DEVICES REJECT ALL NEW DEVICES Address 002 TYPE CHANGE This situation could arise for example if a heat detector has been installed in place of an optical smoke detector If the new devic...

Страница 48: ...e that the device was last re enabled Created The date and time that the device was either auto learnt at the panel or added to the device list from a PC configuration 3 3 6 Loop Meter Displays loop o...

Страница 49: ...ample Commission Menu 1 Please Enter Your Password Next Menu If the password is incorrect this will be indicated or if the password is not entered within 5 seconds the display will revert to the Commi...

Страница 50: ...tion allows the time and date in the panel to be changed On entry to the function the display shows the current time and date with confirmation of the day of the week on the bottom line For example SE...

Страница 51: ...user manual 3 3 17 Setup The Setup Options Menu enables the configuration of panel generic operating parameters When the option is selected the display shows a list of the available parameters For exa...

Страница 52: ...what level is stored in the Event Log There are three options STANDARD the normal operating mode logging fire alarm fault and warning conditions as they occur STANDARD an extended version of the stan...

Страница 53: ...configuration data A note of this number can be taken and then checked on the next service visit to see if any changes have been made to the configuration data Setup CONFIG DATA APOLLO More To change...

Страница 54: ...ption shows a list of the internal panel circuits and provides a means to change their default configuration settings Only use this menu if changes are to be made to the default settings for the panel...

Страница 55: ...ply but the fault condition is only reported after the delay time default 10s has elapsed SENSITIVITY ADJUST MODE MONITOR Alarm Pre Alarm Delay 10s Min Value 372 SAM SSM To delay the reporting of an A...

Страница 56: ...n enter the number of the output group required using the number buttons The display always shows the Output Group is shown in the top left corner Press the buttons to scroll through the list of zones...

Страница 57: ...pes in which case a combination of input events will result in an output action If there is a combination of input events the CAUSE display above shows this extended programming by adding a to the tex...

Страница 58: ...an be programmed to turn on differently such as ON The wait time can be set in intervals of 1 second up to a maximum of 250 seconds Press the button to step on to the wait field and change the setting...

Страница 59: ...med to turn on all outputs immediately 3 3 22 Test This function is the same as User Level 2 function refer to User Manual for further information The following functions can be tested Zones Inputs Di...

Страница 60: ...addressed check the event log in the panel and take the necessary remedial actions b Visually inspect the panel for any moisture ingress or other deterioration check all battery connections and test c...

Страница 61: ...o battery manufacturer for further information Manufacturer Part Numbers YUASA POWERSONIC 4AH NP4 12 5AH PS 1250 7AH NP7 12 7AH PS 1270 12AH NP12 12 12AH PS 12110 17AH NP18 12 18AH PS 12170 24AH NP24...

Страница 62: ...iption MXS 501 1 LP Base Card only AP HO MXS 501V 1 LP Base Card only AV MXS 501N 1 LP Base Card only NITTAN MXS 502 2 LP Base Card only AP HO MXS 502V 2 LP Base Card only AV MXS 502N 2 LP Base Card o...

Отзывы: