13
2.1.3 5400
/L, /D Enclosures
comprises:
Back Box
Base Card with 1-4
Loop Drivers mounted
onto a Chassis Plate
Door with Display Card
mounted onto a fascia
plate. Key-Lock.
Option for eight key-
switches or four key-
switches and a printer.
Option for two 50-Zone
LED cards.
The deep (/D)
enclosure arrangement
is identical.
WARNING:
HIGH VOLTAGE INSID
DO NOT REMOVE COVER
No Serviceable Parts Inside
Display
Loop Drivers 1-4
Base Card
Chassis
Door
Back box
Hinge Pin
AC Input
Optional Zone
LED Cards
Optional Key
Switches
Door
Lock
Display
Cable
Ratings Label
2.1.4 5800
/E Enclosures comprises:
Back Box
Door with Display Card mounted onto a
fascia plate. Key-Lock (2).
Option for eight key-switches or four key-
switches and a printer.
Option for MXP-513-XXX LED cards fitted
to door.
The MX-5800 consists of two independent
systems comprising of 4-LP Base Cards
and Display Cards (only one display is
normally visible) and each system capable
of supporting 512 detection devices.
Network cards are fitted as standard and
wired internally. Additional information on
networking is detailed in document 680-
502.
For redundancy of indications and controls,
install an MX-5030 Remote Terminal.
For redundancy of parent functions (i.e.
Fire Alarm Routing, Fire Brigade Terminals,
etc.) install these with redundant
connection from each chassis using the
appropriate interfaces.
AC MAINS Input
Filter Card
Chassis #1
(Mx-5400 & Mx-5800)
Chassis #2
(Mx-5800 Only)
Display #1
Display #2
Optional LED Indicators
Optional Mounting positions for Peripheral Bus
Module OR for IFAM Redundant Ring Controller
Ratings Label
MX-5400E arrangement is identical but without Chassis
#2 and Display #2.
For more information see document 680-208