2  Configuration 

The Mxp-024 and Mxp-025 are pre-

configured to show zone numbers 1…20. 

The Mxp-013 can be configured from a DIL switch to any of the zone ranges in the table below. 

 

DIL switch (SW1) settings 

Zone Range 

(Note 1) 

Off 

Off 

Off 

Off 

1 - 100 

Off 

Off 

Off 

On 

101 - 200 

Off 

Off 

On 

Off 

201 - 300 

Off 

Off 

On 

On 

301 - 400 

Off 

On 

Off 

Off 

401 - 500 

Off 

On 

Off 

On 

501 - 600 

Off 

On 

On 

Off 

601 - 700 

Off 

On 

On 

On 

701 - 800 

On 

Off 

Off 

Off 

801 - 900 

On 

Off 

Off 

On 

901 - 1000 

On 

On 

On 

On 

Test Mode 

 

Notes: 

1. Mxp-013-050 indicates the first 50 zones in each of the ranges. 

 

3  Operation: 

When  a  zone  changes  state  to  a  fire  condition,  the  corresponding  zone  LED  will  illuminate.  The  Zone  LED 
Indicators will be turned off when the panel is manually reset. 

The Mxp-013 incorporates a power saving feature so that in the event of a major fire with more than 50 zones 
all in a fire condition occurring in the same zone range, the zone LED’s will change from being continuously on 
to flashing in order to minimise power drawn from the standby battery. 

3.1  Testing the Zonal LED Indicators 

Enter  th

e  “TEST”  menu  and  select  “DISPLAY”.  All  of  the  zonal  LED’s  will  then  flash  on  and  off  for  several 

seconds.  

 

 

 

 

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание Mx Pro 4

Страница 1: ...el The Mxp 013 050F Mxp 013 100F and Mxp 200F incorporate 50 100 or 200 LED indicators respectively and are compatible with all of the MxPro 4 series multi loop panels The zone range on the 100 way ca...

Страница 2: ...ted from 1 to 1000 E g 1 100 101 200 901 1000 The 20 and 50 zone cards display zones 1 20 and zones 1 50 respectively In the event of more than 50 zones entering a fire condition the LED s will change...

Страница 3: ...LATION 4 1 1 MXP 024F 4 1 2 MXP 025F 4 1 3 MXP 013 XXXF 5 1 3 1 Mxp 013 050 Mxp 013 100 5 1 3 2 Mxp 013 200 5 2 CONFIGURATION 6 3 OPERATION 6 3 1 TESTING THE ZONAL LED INDICATORS 6 www acornfiresecuri...

Страница 4: ...lace with the 4x nuts d Re connect the ribbon cable to the LED card e Test the LED operation refer to Operation Section Mxs 024 Interconnecting Cable Display Card 4x M3 Nut NOTE If a network interface...

Страница 5: ...range refer to Configuration Section f Test the LED operation refer to Operation Section 1 3 2 Mxp 013 200 The Mxp 013 200 consists of 2x 100 LED Indicator cards mounted on the fascia plate and connec...

Страница 6: ...the first 50 zones in each of the ranges 3 Operation When a zone changes state to a fire condition the corresponding zone LED will illuminate The Zone LED Indicators will be turned off when the panel...

Страница 7: ...USER NOTES www acornfiresecurity com www acornfiresecurity com...

Страница 8: ...www acornfiresecurity com www acornfiresecurity com...

Отзывы: