2.3.5  AC Filter Card 

If two or more power supplies are to be installed in the panel then, to meet conducted emissions requirements 
of the EMC Directive, an AC Filter Card must be installed. 

This also benefits in that a single AC Feed is supplied to the panel with pluggable connections for each power 
supply. 

[1] Mount the PCB onto the pillars in the upper right hand corner of the back box using the supplied screws. 

[2] Fit the earth cable to the stud in the back box and secure using the supplied nuts and washers. Plug the 
connector onto the spade tab located on the filter card. 

[3] Affix the connection / warning label 

to the 

back box to the left of the card as 
shown in the diagram. 

[4] Wire the supplied leads to the 
terminal blocks in the relevant 
modules.  

Two sizes of cable are supplied 
(200mm and 500mm).  

Use the 200mm long lead for the 
module located in the upper part of 

the 

enclosure.  

Use the 500mm long leads for 
modules located in the middle and 

lower 

parts of the enclosure. Ensure the 

leads 

are tie-wrapped securely to the 
module enclosure next to the terminal 

block. 

 

Item 

Specification Details 

AC Supply Voltage 

200-240V, 47-63Hz AC 

6

 

AC Supply Current 

Maximum 4A 

7

 

Module Rating 

Module 

Voltage 

Maximum  

(I

MAXB

 @ 200V) 

8

 

Typical  

(I

MAXB

 @ 230V) 

Typical  

(I

MAXA

 @ 230V) 

MX5100R 

200-240V, 47-63Hz AC 

1.0A 

0.6A 

0.35A 

MX5200R 

200-240V, 47-63Hz AC 

1.4A 

1.0A 

0.55A 

MX5400R 

200-240V, 47-63Hz AC 

1.4A 

1.0A 

0.55A 

MXS-049 

220-240V, 47-63Hz AC 

0.4A 

0.3A 

0.20A 

MXS-050 

200-240V, 47-63Hz AC 

1.0A 

0.6A 

0.40A 

MXS-051 

200-240V, 47-63Hz AC 

1.4A 

1.0A 

0.60A 

Fuse 

T5AH250 (Ceramic 5mm x 20mm, time delay) 

 

 

 

 

 

 

 

                                                        

6

 The AC Supply range depends on the modules installed. 

7

 The sum of the installed modules maximum ratings should not exceed 4A. 

8

 This is the maximum AC current when the unit is loaded to maximum (I

MAXB

 or I

MAXA

 + Maximum charging current) quoted at minimum AC 

input voltage.  
NOTE: I

MAXA

 is the maximum quiescent load of the panel and I

MAXB

 is the maximum alarm load of the panel 

– refer to the main panel or 

product manuals for further information. 

 

 

L

 

 

 

  

N   

 

 

 

WARNING

 

 

 

MAINS VOLTAGE

 

 

 

ISOLATE

 

 

 

ELSEWHERE!

 

 

 

FUSE: T5H250

 

 

 

Fixing Screws 
x4 

Fuse 

Earth Cable 

AC Input 

To internal 
power supply 
terminal 
blocks 

Содержание Mx-5101xR

Страница 1: ...www advancedco com 5000 Series Rack Panels The operation and functions described in this manual are available from Software Version Mx5000 050 04 onwards...

Страница 2: ...Door with LED Aperture Mxm 513 D3 Enclosure Utility Module 6U Door with Aperture Mxm 513 FP Enclosure Utility Module 6U Fascia Plate Blank Mxm 513 MF Enclosure Utility Module 6U Switch LED Mounting F...

Страница 3: ...ECHANICAL SPECIFICATIONS 8 2 2 1 Enclosure 16U 8 2 2 2 Enclosure Other Sizes 9 2 2 3 Enclosure Commercial 9 2 2 4 Battery Gas Venting 9 2 2 5 Battery Shelf Chassis Plate DIN Rail 9 2 2 5 1 MXM 510 BS...

Страница 4: ...put to Fault Routing Equipment Investigation Delays to Outputs Dependency on more than one alarm signal Fault Signals from Points Disablement of Points Alarm Counter Test Condition Standardised Input...

Страница 5: ...ddition the module assemblies can be mounted into commercial rack mount enclosures This manual covers the installation of the rack mount 5000R 5000VR Series Fire Alarm Control Panel assemblies and enc...

Страница 6: ...code of practice or national standard regulations for fire systems installation for example BS5839 1 2002 appropriate to the country and location of the installation 1 5 2 Wiring Regulations The panel...

Страница 7: ...l model refer the separate sections in this manual Visual indicators can be seen through the glass panel The outer door is not locked to provide access to Level 1 and Level 2 controls An optional key...

Страница 8: ...re and can be fitted behind Zone LED modules or blanking plates Mount the enclosure on the wall using fixing hardware suitable for the size and weight of the complete enclosure 2 The fixing holes are...

Страница 9: ...le for the IP rating required 2 2 5 Battery Shelf Chassis Plate DIN Rail 2 2 5 1 MXM 510 BS Up to two battery shelves can be fitted for mounting of 7Ah or 18Ah batteries The shelves rest on the side w...

Страница 10: ...her two peripheral bus modules Screw these M3 pillars into the captive nuts on the chassis plate and then mount and affix the modules using the M3 screws supplied with the module The PSE module fits d...

Страница 11: ...ox is 125 mm The panel module weight is 6 kg The door is securely locked using the standard Advanced Electronics Ltd panel key The internal arrangement of the panel module is shown in the following di...

Страница 12: ...Keep the AC wiring away from the circuit boards and all other wiring The mains input connector is shown in the diagram below Note the positions of the earth neutral and live terminal connections These...

Страница 13: ...e battery leads Use the supplied tie wraps to tie the sensor cable to the battery leads so that the encapsulated sensor is located close to the batteries The sensor cable is 500mm in length NOTE If th...

Страница 14: ...unting frame using 4x M4 Nuts and washers Connect the ribbon cable to the display card Route the cable through the lower hole in the left hand side of the panel module enclosure and connect to the inp...

Страница 15: ...be fitted 2 3 3 1 Chassis The utility chassis plate can accept the following module types 1x PSE Module Mxs 049 Mxs 050 or Mxs 051 and 1x Mxp 510 BMS Interface4 or 1x Mxp 554 ipGateway or 2x standard...

Страница 16: ...the Mxs 049 to the upper four holes and fit the Mxs 050 and Mxs 051 to the outer four holes Fit the terminal block to the enclosure using the two supplied M3 Screws and affix the integral earth lead t...

Страница 17: ...r hole in the left hand side of the panel module enclosure Route the cable through the lower hole in the left hand side of the utility module enclosure and connect to the input connector top of the fi...

Страница 18: ...e can be drilled and screen printing for the required graphic indicator diagram Mimic area 350 W x 180 H Up to two Mxp 539 Input Output Cards are required to be mounted to the chassis LED and Switch o...

Страница 19: ...blank plate in the door can be removed so that it can be drilled and screen printed as required for fitting of switches and LED indicators 2 3 4 1 Chassis 6U The 6U Chassis can be fitted refer to pre...

Страница 20: ...051 and Up to 4x Mxp 539 Mimic Interface Modules Up to 192 LED and up to 64 Switches 5 Mxp 020 and Mxp 045 modules can also be fitted in this one location An additional Mxs 027 can be also be fitted...

Страница 21: ...es and fit the Mxs 050 and Mxs 051 to the outer four holes Fit the terminal block to the enclosure using the two supplied M3 Screws and affix the integral earth lead to the stud using the supplied M4...

Страница 22: ...he enclosure Ensure the leads are tie wrapped securely to the module enclosure next to the terminal block Item Specification Details AC Supply Voltage 200 240V 47 63Hz AC 6 AC Supply Current Maximum 4...

Страница 23: ...www advancedco com USER NOTES...

Страница 24: ...nced Electronics Ltd Moorland Way Cramlington Northumberland NE23 1WE UK Tel 44 0 1670 707 111 Fax 44 0 1670 707 222 Email sales advancedco com Web www advancedco com Doc Number 680 195 Revision 01A F...

Отзывы: