www.advancedco.com
22
2.3.5 AC Filter Card
If two or more power supplies are to be installed in the panel then, to meet conducted emissions requirements
of the EMC Directive, an AC Filter Card must be installed.
This also benefits in that a single AC Feed is supplied to the panel with pluggable connections for each power
supply.
[1] Mount the PCB onto the pillars in the upper right hand corner of the back box using the supplied screws.
[2] Fit the earth cable to the stud in the back box and secure using the supplied nuts and washers. Plug the
connector onto the spade tab located on the filter card.
[3] Affix the connection / warning label
to the
back box to the left of the card as
shown in the diagram.
[4] Wire the supplied leads to the
terminal blocks in the relevant
modules.
Two sizes of cable are supplied
(200mm and 500mm).
Use the 200mm long lead for the
module located in the upper part of
the
enclosure.
Use the 500mm long leads for
modules located in the middle and
lower
parts of the enclosure. Ensure the
leads
are tie-wrapped securely to the
module enclosure next to the terminal
block.
Item
Specification Details
AC Supply Voltage
200-240V, 47-63Hz AC
6
AC Supply Current
Maximum 4A
7
Module Rating
Module
Voltage
Maximum
(I
MAXB
@ 200V)
8
Typical
(I
MAXB
@ 230V)
Typical
(I
MAXA
@ 230V)
MX5100R
200-240V, 47-63Hz AC
1.0A
0.6A
0.35A
MX5200R
200-240V, 47-63Hz AC
1.4A
1.0A
0.55A
MX5400R
200-240V, 47-63Hz AC
1.4A
1.0A
0.55A
MXS-049
220-240V, 47-63Hz AC
0.4A
0.3A
0.20A
MXS-050
200-240V, 47-63Hz AC
1.0A
0.6A
0.40A
MXS-051
200-240V, 47-63Hz AC
1.4A
1.0A
0.60A
Fuse
T5AH250 (Ceramic 5mm x 20mm, time delay)
6
The AC Supply range depends on the modules installed.
7
The sum of the installed modules maximum ratings should not exceed 4A.
8
This is the maximum AC current when the unit is loaded to maximum (I
MAXB
or I
MAXA
+ Maximum charging current) quoted at minimum AC
input voltage.
NOTE: I
MAXA
is the maximum quiescent load of the panel and I
MAXB
is the maximum alarm load of the panel
– refer to the main panel or
product manuals for further information.
L
N
WARNING
MAINS VOLTAGE
ISOLATE
ELSEWHERE!
FUSE: T5H250
Fixing Screws
x4
Fuse
Earth Cable
AC Input
To internal
power supply
terminal
blocks