background image

 

 

www.advancedco.com 

 

RELEASE ACTIVATED 
00:00:10 Elapsed 

When the discharge is complete (either time elapsed or flow 
detected) the display indicates the discharge is complete.  

 

 

DISCHARGE COMPLETE 
(No Flow Detected) 
 
 

 

RELEASE ACTIVATED 
00:00:10 Elapsed 

If confirmed by the detection of the flow of the extinguishant, the 
display shows RELEASE CONFIRMED (Released Condition) and 
the RELEASED LED turns ON steady. 

If previously silenced, the internal buzzer will re-sound. Press the 

 

button to silence the buzzer. 

 
RELEASE CONFIRMED 
DISCHARGE COMPLETE 
 

 

RELEASE ACTIVATED 
00:00:20 Elapsed 

When the extinguishant has been fully released and if  
automatically or manually activated, the output to control the 
extract fan will be turned on. 

This is indicated on the display as EXTRACT RUNNING  

When the discharge is complete, the display prompts that the 
panel can be reset 

– reset must be performed at the control panel. 

 
DISCHARGE COMPLETE 
EXTRACT RUNNING 
RESET ALLOWED 

 
To reset the panel, press the RESET button on the control panel. 

 

 

Section 

4.12.2

 

Reset of the Activated Condition / Release Signal. 

 

NOTE: In accordance with EN 12094-1, the ECD shall not permit a reset until 
either the RELEASED condition has been established (flow detected) or until 
after a programmable time following activation of the mechanism to release the 
extinguishant. 

 
NOTE: Depending on programming, the EXTRACT condition may persist after the panel is reset for up to 120 
minutes. This will be indicated on the normal status display (Extract Running). 

 

 

Section 

4.11

 

Released Condition. 

NOTE: In accordance with EN 12094-1, the activated / release condition may be 
established without the detection of a fire alarm or manual release. If the panel 
detects the release of extinguishant, it will immediately indicate the released 
condition. 

2.2.3 

Hold Condition 

 COUNTDOWN ON HOLD 
(Remove HOLD resume) 
 

-15 

If any hold button is activated, the imminent release countdown is 
held for as long as the button is pressed. 

The display shows the HOLD condition and the TIMER HELD LED 
is illuminated. 

 

 

When the hold button is release, the panel will resume the imminent release countdown either from the time 
remaining or from the maximum time programmed. 

Содержание ExGo Series

Страница 1: ...www advancedco com Remote Status Indicators Installation and Commissioning The operation and functions described in this manual are available from Software Version Ex 3000 V2 05C onwards...

Страница 2: ...f 1 Relay Outputs Optional 2x rated at 1A 30VAC DC max 10mA 5V min programmable requires EXP 007 Key Switches 1x programmable Optional Fitted Optional Fitted Manual Release No No Yes Yes External Inpu...

Страница 3: ...Abort Condition 10 2 2 5 Fault Condition 10 2 2 6 Warning Condition 10 2 3 LEVEL 1 MENU FUNCTIONS 11 2 3 1 Navigating through Level 1 Menus 11 2 3 2 View 11 2 3 2 1 Faults 11 2 3 2 2 Disables 12 2 3...

Страница 4: ...se of the Ex 3000 Series Remote Status Indicating Panels The Ex 3020 is an RSI with Liquid Crystal Display and LED Indicators The Ex 3021 is an RSI with Liquid Crystal Display LED Indicators and Mode...

Страница 5: ...3030 but is without the Manual Release function 2 1 1 1 Display The LCD along with the LED Indicators shows the operating status of the system Examples of the information presented is shown below Nor...

Страница 6: ...anel has detected the folw of the extinguishant released TIMER HELD Yellow Indicates that the imminent release of extinguishant is temproraily suspended ABORTED Yellow Indicates that the imminent rele...

Страница 7: ...ions of these are programmable and the installer will have inserted a label to indicate their use Typical uses are AUTO MANUAL MANUAL ONLY Selection EXTRACT OVERRIDE Depending on the key switch mechan...

Страница 8: ...nel press the RESET button on the control panel NOTE If the programming of the panel is such that the release condition is immediately invoked on detection of a single fire alarm then the display will...

Страница 9: ...n on the control panel Section 4 12 2 Reset of the Activated Condition Release Signal NOTE In accordance with EN 12094 1 the ECD shall not permit a reset until either the RELEASED condition has been e...

Страница 10: ...UNAFFECTED NOTE The fault condition is non latching except System Fault and the indications will automatically be cleared when the fault is remedied Press the RESET key to clear a System Fault NOTE If...

Страница 11: ...u option and then press the button to select it Press the button from within a menu option to return to the previous menu The display will revert to the status mode display after 60 seconds on no acti...

Страница 12: ...e warning conditions Press the buttons to scroll through the list of warnings Press the button to return to the previous menu 2 3 2 4 Software Versions The display shows the revision of software insta...

Страница 13: ...Indicator ZONE 2 ZONE 3 SYSTEM FAULT MODE SUPPLY INPUTS 485 IN 485 OUT USB REBOOT SWITCH CONTRAST ADJUST RUN PROG COVER FIXING SCREWS The panel comprises a back box and cover chassis assembly The chas...

Страница 14: ...n the diagram below Remove the chassis before installing the enclosure retain in a safe place Ensure that there is sufficient space to allow the cover to be removed opened when the panel is finally mo...

Страница 15: ...a Safety Extra Low Voltage SELV supply Connect the 24V DC supply feed input to the SUPPLY 24V and 0V terminals on the interface card Use cables of sufficient size to ensure that the power input voltag...

Страница 16: ...t conditions see typical arrangement below EOL 6800 Maximum line impedance 50 Connect to volt free switches relay contacts only MANUAL ONLY AUTO MANUAL DISABLED FAULT TIMER HELD ABORTED RELEASE IMMINE...

Страница 17: ...description into the pocket in the fascia label Plug the connector into the respective connector on the card Key Switch assemblies are available in both trapped and non trapped versions The function...

Страница 18: ...www advancedco com 18 This page is intentionally left blank...

Страница 19: ...www advancedco com 19 USER NOTES...

Страница 20: ...ystem Emergency Abort Device Activation of Alarm Devices with Different Signals Response delay activated condition maximum 3s Response delay triggering of outputs maximum 1s EN54 2 1997 A1 Control and...

Отзывы: